Amendment
Bill No. 0267
Amendment No. 366847
CHAMBER ACTION
Senate House
.
.
.






1Representative Murman offered the following:
2
3Amendment (with title amendment)
4Between lines 175 and 176 insert:
5     Section 6.  Paragraph (a) of subsection (1) of section
6400.441, Florida Statutes, is amended to read:
7     400.441  Rules establishing standards.--
8     (1)  It is the intent of the Legislature that rules
9published and enforced pursuant to this section shall include
10criteria by which a reasonable and consistent quality of
11resident care and quality of life may be ensured and the results
12of such resident care may be demonstrated. Such rules shall also
13ensure a safe and sanitary environment that is residential and
14noninstitutional in design or nature. It is further intended
15that reasonable efforts be made to accommodate the needs and
16preferences of residents to enhance the quality of life in a
17facility. In order to provide safe and sanitary facilities and
18the highest quality of resident care accommodating the needs and
19preferences of residents, the department, in consultation with
20the agency, the Department of Children and Family Services, and
21the Department of Health, shall adopt rules, policies, and
22procedures to administer this part, which must include
23reasonable and fair minimum standards in relation to:
24     (a)  The requirements for and maintenance of facilities,
25not in conflict with the provisions of chapter 553, relating to
26plumbing, heating, cooling, lighting, ventilation, living space,
27and other housing conditions, which will ensure the health,
28safety, and comfort of residents and protection from fire
29hazard, including adequate provisions for fire alarm and other
30fire protection suitable to the size of the structure. Uniform
31firesafety standards shall be established and enforced by the
32State Fire Marshal in cooperation with the agency, the
33department, and the Department of Health.
34     1.  Evacuation capability determination.--
35     a.  The provisions of the National Fire Protection
36Association, NFPA 101A, Chapter 5, 1995 edition, shall be used
37for determining the ability of the residents, with or without
38staff assistance, to relocate from or within a licensed facility
39to a point of safety as provided in the fire codes adopted
40herein. An evacuation capability evaluation for initial
41licensure shall be conducted within 6 months after the date of
42licensure. For existing licensed facilities that are not
43equipped with an automatic fire sprinkler system, the
44administrator shall evaluate the evacuation capability of
45residents at least annually. The evacuation capability
46evaluation for each facility not equipped with an automatic fire
47sprinkler system shall be validated, without liability, by the
48State Fire Marshal, by the local fire marshal, or by the local
49authority having jurisdiction over firesafety, before the
50license renewal date. If the State Fire Marshal, local fire
51marshal, or local authority having jurisdiction over firesafety
52has reason to believe that the evacuation capability of a
53facility as reported by the administrator may have changed, it
54may, with assistance from the facility administrator, reevaluate
55the evacuation capability through timed exiting drills.
56Translation of timed fire exiting drills to evacuation
57capability may be determined:
58     (I)  Three minutes or less: prompt.
59     (II)  More than 3 minutes, but not more than 13 minutes:
60slow.
61     (III)  More than 13 minutes: impractical.
62     b.  The Office of the State Fire Marshal shall provide or
63cause the provision of training and education on the proper
64application of Chapter 5, NFPA 101A, 1995 edition, to its
65employees, to staff of the Agency for Health Care Administration
66who are responsible for regulating facilities under this part,
67and to local governmental inspectors. The Office of the State
68Fire Marshal shall provide or cause the provision of this
69training within its existing budget, but may charge a fee for
70this training to offset its costs. The initial training must be
71delivered within 6 months after July 1, 1995, and as needed
72thereafter.
73     c.  The Office of the State Fire Marshal, in cooperation
74with provider associations, shall provide or cause the provision
75of a training program designed to inform facility operators on
76how to properly review bid documents relating to the
77installation of automatic fire sprinklers. The Office of the
78State Fire Marshal shall provide or cause the provision of this
79training within its existing budget, but may charge a fee for
80this training to offset its costs. The initial training must be
81delivered within 6 months after July 1, 1995, and as needed
82thereafter.
83     d.  The administrator of a licensed facility shall sign an
84affidavit verifying the number of residents occupying the
85facility at the time of the evacuation capability evaluation.
86     2.  Firesafety requirements.--
87     a.  Except for the special applications provided herein,
88effective January 1, 1996, the provisions of the National Fire
89Protection Association, Life Safety Code, NFPA 101, 1994
90edition, Chapter 22 for new facilities and Chapter 23 for
91existing facilities shall be the uniform fire code applied by
92the State Fire Marshal for assisted living facilities, pursuant
93to s. 633.022.
94     b.  Any new facility, regardless of size, that applies for
95a license on or after January 1, 1996, must be equipped with an
96automatic fire sprinkler system. The exceptions as provided in
97section 22-2.3.5.1, NFPA 101, 1994 edition, as adopted herein,
98apply to any new facility housing eight or fewer residents. On
99July 1, 1995, local governmental entities responsible for the
100issuance of permits for construction shall inform, without
101liability, any facility whose permit for construction is
102obtained prior to January 1, 1996, of this automatic fire
103sprinkler requirement. As used in this part, the term "a new
104facility" does not mean an existing facility that has undergone
105change of ownership.
106     c.  Notwithstanding any provision of s. 633.022 or of the
107National Fire Protection Association, NFPA 101A, Chapter 5, 1995
108edition, to the contrary, any existing facility housing eight or
109fewer residents is not required to install an automatic fire
110sprinkler system, nor to comply with any other requirement in
111Chapter 23, NFPA 101, 1994 edition, that exceeds the firesafety
112requirements of NFPA 101, 1988 edition, that applies to this
113size facility, unless the facility has been classified as
114impractical to evacuate. Any existing facility housing eight or
115fewer residents that is classified as impractical to evacuate
116must install an automatic fire sprinkler system within the
117timeframes granted in this section.
118     d.  Any existing facility that is required to install an
119automatic fire sprinkler system under this paragraph need not
120meet other firesafety requirements of Chapter 23, NFPA 101, 1994
121edition, which exceed the provisions of NFPA 101, 1988 edition.
122The mandate contained in this paragraph which requires certain
123facilities to install an automatic fire sprinkler system
124supersedes any other requirement.
125     e.  This paragraph does not supersede the exceptions
126granted in NFPA 101, 1988 edition or 1994 edition.
127     f.  This paragraph does not exempt facilities from other
128firesafety provisions adopted under s. 633.022 and local
129building code requirements in effect before July 1, 1995.
130     g.  A local government may charge fees only in an amount
131not to exceed the actual expenses incurred by local government
132relating to the installation and maintenance of an automatic
133fire sprinkler system in an existing and properly licensed
134assisted living facility structure as of January 1, 1996.
135     h.  If a licensed facility undergoes major reconstruction
136or addition to an existing building on or after January 1, 1996,
137the entire building must be equipped with an automatic fire
138sprinkler system. Major reconstruction of a building means
139repair or restoration that costs in excess of 50 percent of the
140value of the building as reported on the tax rolls, excluding
141land, before reconstruction. Multiple reconstruction projects
142within a 5-year period the total costs of which exceed 50
143percent of the initial value of the building at the time the
144first reconstruction project was permitted are to be considered
145as major reconstruction. Application for a permit for an
146automatic fire sprinkler system is required upon application for
147a permit for a reconstruction project that creates costs that go
148over the 50-percent threshold.
149     i.  Any facility licensed before January 1, 1996, that is
150required to install an automatic fire sprinkler system shall
151ensure that the installation is completed within the following
152timeframes based upon evacuation capability of the facility as
153determined under subparagraph 1.:
154     (I)  Impractical evacuation capability, 24 months.
155     (II)  Slow evacuation capability, 48 months.
156     (III)  Prompt evacuation capability, 60 months.
157
158The beginning date from which the deadline for the automatic
159fire sprinkler installation requirement must be calculated is
160upon receipt of written notice from the local fire official that
161an automatic fire sprinkler system must be installed. The local
162fire official shall send a copy of the document indicating the
163requirement of a fire sprinkler system to the Agency for Health
164Care Administration.
165     j.  It is recognized that the installation of an automatic
166fire sprinkler system may create financial hardship for some
167facilities. The appropriate local fire official shall, without
168liability, grant two 1-year extensions to the timeframes for
169installation established herein, if an automatic fire sprinkler
170installation cost estimate and proof of denial from two
171financial institutions for a construction loan to install the
172automatic fire sprinkler system are submitted. However, for any
173facility with a class I or class II, or a history of uncorrected
174class III, firesafety deficiencies, an extension must not be
175granted. The local fire official shall send a copy of the
176document granting the time extension to the Agency for Health
177Care Administration.
178     k.  A facility owner whose facility is required to be
179equipped with an automatic fire sprinkler system under Chapter
18023, NFPA 101, 1994 edition, as adopted herein, must disclose to
181any potential buyer of the facility that an installation of an
182automatic fire sprinkler requirement exists. The sale of the
183facility does not alter the timeframe for the installation of
184the automatic fire sprinkler system.
185     l.  Existing facilities required to install an automatic
186fire sprinkler system as a result of construction-type
187restrictions in Chapter 23, NFPA 101, 1994 edition, as adopted
188herein, or evacuation capability requirements shall be notified
189by the local fire official in writing of the automatic fire
190sprinkler requirement, as well as the appropriate date for final
191compliance as provided in this subparagraph. The local fire
192official shall send a copy of the document to the Agency for
193Health Care Administration.
194     m.  Except in cases of life-threatening fire hazards, if an
195existing facility experiences a change in the evacuation
196capability, or if the local authority having jurisdiction
197identifies a construction-type restriction, such that an
198automatic fire sprinkler system is required, it shall be
199afforded time for installation as provided in this subparagraph.
200
201Facilities that are fully sprinkled and in compliance with other
202firesafety standards are not required to conduct more than one
203of the required fire drills between the hours of 11 p.m. and 7
204a.m., per year. In lieu of the remaining drills, staff
205responsible for residents during such hours may be required to
206participate in a mock drill that includes a review of evacuation
207procedures. Such standards must be included or referenced in the
208rules adopted by the State Fire Marshal. Pursuant to s.
209633.022(1)(b), the State Fire Marshal is the final
210administrative authority for firesafety standards established
211and enforced pursuant to this section. All licensed facilities
212must have an annual fire inspection conducted by the local fire
213marshal or authority having jurisdiction.
214     3.  Resident elopement requirements.--Facilities are
215required to conduct a minimum of two resident elopement
216prevention and response drills per year. All administrators and
217direct care staff must participate in the drills which shall
218include a review of procedures to address resident elopement.
219Facilities must document the implementation of the drills and
220ensure that the drills are conducted in a manner consistent with
221the facility's resident elopement policies and procedures.
222
223================ T I T L E  A M E N D M E N T =============
224     Between lines 21 and 22 insert:
225amending s. 400.441, F.S.; requiring facilities to conduct
226resident elopement prevention and response drills and to provide
227documentation thereof;


CODING: Words stricken are deletions; words underlined are additions.