Florida Senate - 2006                      COMMITTEE AMENDMENT
    Bill No. CS for SB 1774
                        Barcode 301660
                            CHAMBER ACTION
              Senate                               House
                                   .                    
                                   .                    
 1           Comm: RCS             .                    
       04/18/2006 03:22 PM         .                    
 2                                 .                    
                                   .                    
 3                                 .                    
                                   .                    
 4  ______________________________________________________________
 5  
 6  
 7  
 8  
 9  
10  ______________________________________________________________
11  The Committee on Regulated Industries (Posey) recommended the
12  following amendment:
13  
14         Senate Amendment (with title amendment) 
15         On page 18, between lines 20 and 21,
16  
17  insert:  
18         Section 6.  Present subsections (8) through (27) of
19  section 633.021, Florida Statutes, are redesignated as
20  subsections (9) through (28), respectively, and a new
21  subsection (8) is added to that section, to read:
22         633.021  Definitions.--As used in this chapter:
23         (8)  A "fire hydrant" is a connection to a water main,
24  elevated water tank, or other source of water for the purpose
25  of supplying water to a fire hose or other fire protection
26  apparatus for fire-suppression operations.
27         Section 7.  Section 633.082, Florida Statutes, is
28  amended to read:
29         633.082  Inspection of fire control systems, fire
30  hydrants, and fire protection systems.--
31         (1)  The State Fire Marshal shall have the right to
                                  1
    10:30 AM   04/18/06                          s1774c1c-ri24-t01

Florida Senate - 2006 COMMITTEE AMENDMENT Bill No. CS for SB 1774 Barcode 301660 1 inspect any fire control system during and after construction 2 to determine that such system meets the standards set forth in 3 the laws and rules of the state. 4 (2) Fire hydrants and fire protection systems 5 installed in public and private properties, except one-family 6 or two-family dwellings, in this state shall be inspected 7 following procedures established in the nationally recognized 8 inspection, testing, and maintenance standards NFPA-24 and 9 standard NFPA-25 as set forth in the edition adopted by the 10 State Fire Marshal. Quarterly, annual, 3-year, and 5-year 11 inspections consistent with the contractual provisions with 12 the owner shall be conducted by the certificateholder or 13 permittees employed by the certificateholder pursuant to s. 14 633.521. 15 (3) The inspecting contractor shall provide to the 16 building owner or hydrant owner and the local authority having 17 jurisdiction a copy of the applicable inspection report 18 established under this chapter s. 633.071(3). The maintenance 19 of fire hydrant and fire protection systems as well as 20 corrective actions on deficient systems is the responsibility 21 of the owner of the system or hydrant. This section does not 22 prohibit governmental entities from inspecting and enforcing 23 firesafety codes. 24 (4) At least once each year, each fire hydrant shall 25 be opened fully and the water allowed to flow until all 26 foreign materials have cleared the hydrant. The flow shall be 27 maintained for not less than 1 minute. 28 (5) If a fire hydrant is made nonfunctional by the 29 closing of a water supply valve, the valve must immediately be 30 tagged with a red tag that is boldly marked "nonfunctional" 31 and the local fire authority notified that the hydrant is 2 10:30 AM 04/18/06 s1774c1c-ri24-t01
Florida Senate - 2006 COMMITTEE AMENDMENT Bill No. CS for SB 1774 Barcode 301660 1 nonfunctional. 2 Section 8. Section 633.5391, Florida Statutes, is 3 repealed. 4 5 (Redesignate subsequent sections.) 6 7 8 ================ T I T L E A M E N D M E N T =============== 9 And the title is amended as follows: 10 On page 1, line 21, after the semicolon, 11 12 insert: 13 amending s. 633.021, F.S.; defining the term 14 "fire hydrant" for the purpose of the Florida 15 Fire Prevention Code; amending s. 633.082, 16 F.S.; providing for the inspection of fire 17 hydrants by the State Fire Marshal; requiring 18 that each fire hydrant be opened fully at least 19 once each year to clear foreign materials in 20 the system; providing that a fire hydrant made 21 nonfunctional by the closing of a water supply 22 valve must immediately be tagged with a red tag 23 that is boldly marked "nonfunctional"; 24 repealing s. 633.5391, F.S., relating to 25 backflow prevention assembly inspection; 26 27 28 29 30 31 3 10:30 AM 04/18/06 s1774c1c-ri24-t01