12  recommended the following substitute for amendment (593808):
13  
14         Senate Amendment (with title amendment) 
15         Delete everything after the enacting clause
16  
17  and insert:  
18         Section 1.  Section 399.036, Florida Statutes, is
19  created to read:
20         399.036  Alternate generated power source for
21  residential multifamily dwellings.--
22         (1)  Any person, firm, or corporation that owns,
23  manages, or operates a residential multifamily dwelling,
24  including a condominium, which is at least 75 feet high and
25  contains a public elevator, as described in s. 399.035(2) and
26  (3), must have at least one public elevator that is capable of
27  operating on an alternate generated power source for the
28  purpose of allowing all residents access for a number of hours
29  each day over a 5-day period following a natural disaster,
30  manmade disaster, emergency, or other civil disturbance that
31  disrupts the normal supply of electricity. The alternate
                                  1
    6:23 PM   03/02/06                             s0860d-ds36-j02

Florida Senate - 2006 COMMITTEE AMENDMENT Bill No. SB 860 Barcode 831804 1 generated power source must be capable of powering any 2 connected fire alarm system in the building which controls 3 elevator operations. 4 (2) At a minimum, the elevator must be appropriately 5 prewired and prepared to accept such alternate generated power 6 and must have a connection on the line side of the main 7 disconnect, pursuant to National Electric Code Handbook, 8 Article 700. In addition to the required power source for the 9 elevator and connected fire alarm system in the building, the 10 alternate power supply must be sufficient to provide emergency 11 lighting to the internal lobbies, internal hallways, and other 12 internal portions of the building used by the public. 13 Residential multifamily dwellings must have an available 14 generator and fuel source on the property or have proof of a 15 current guaranteed service contract for such equipment and 16 fuel source to operate the elevator on-call within 24 hours 17 after a request. Local building inspectors must provide 18 verification of engineering plans for alternate generated 19 power capability for such buildings to the emergency 20 management director of the county by December 31, 2006. 21 Verification of installation and operational capability must 22 be made by local building inspectors to the emergency 23 management director of the county by December 31, 2007. 24 (3) Each newly constructed residential multifamily 25 dwelling, as defined in this section, which has an operating 26 elevator must have at least one public elevator that is 27 capable of operating on an alternate generated power source 28 for the purpose of allowing all residents access for a number 29 of hours each day over a 5-day period following a natural 30 disaster, manmade disaster, emergency, or other civil 31 disturbance that disrupts the normal supply of electricity. 2 6:23 PM 03/02/06 s0860d-ds36-j02
Florida Senate - 2006 COMMITTEE AMENDMENT Bill No. SB 860 Barcode 831804 1 The alternate generated power source must be capable of 2 powering any connected fire alarm system in the building which 3 controls elevator operations. In addition to the required 4 power source for the elevator and connected fire alarm system 5 in the building, the alternate power supply must be sufficient 6 to provide emergency lighting to the internal lobbies, 7 internal hallways, and other internal portions of the building 8 used by the public. Engineering plans and verification of 9 operational capability must be provided by the local building 10 inspector to the emergency management director of the local 11 county before occupancy of the newly constructed building. 12 (4) Each person, firm, corporation, managing 13 association, or other entity that is required to maintain 14 alternate generated power under this section shall maintain a 15 written emergency operations plan that details the sequence of 16 operations before, during, and after a natural or manmade 17 disaster or other emergency situation. The plan must include, 18 at a minimum, a life-safety plan for evacuation, maintenance 19 of the electrical and lighting supply, and provision for the 20 health, safety, and welfare of the residents. In addition, the 21 owner, managing entity, or operator of the residential 22 multifamily dwelling must keep a log containing a list of 23 quarterly inspections to keep life-safety and alternate power 24 generation equipment in good and working condition and any 25 contracts for alternate power generation equipment. The 26 written emergency operations plan and log shall be open for 27 periodic inspections by local and state government agencies, 28 as deemed necessary. The owner, managing entity, or operator 29 must keep a generator key in a lockbox posted at or near any 30 installed generator unit. 31 (5) As a part of the annual elevator inspection 3 6:23 PM 03/02/06 s0860d-ds36-j02
Florida Senate - 2006 COMMITTEE AMENDMENT Bill No. SB 860 Barcode 831804 1 required in s. 399.061, certified inspectors shall confirm 2 that all installed generators required by this chapter are in 3 working order, that the logs are current, and that the 4 required generator key is present in the lockbox posted at or 5 near the installed generator. If a building does not have an 6 installed generator, the inspector shall confirm that the 7 appropriate wiring and switching capabilities are operational 8 and that a contract for contingent services for alternate 9 generated power is current for the operating period. 10 Section 2. This act shall take effect upon becoming a 11 law. 12 13 14 ================ T I T L E A M E N D M E N T =============== 15 And the title is amended as follows: 16 Delete everything before the enacting clause 17 18 and insert: 19 A bill to be entitled 20 An act relating to emergency preparedness; 21 creating s. 399.036, F.S.; requiring an owner, 22 managing entity, or operator of a specified 23 residential multifamily dwelling to have at 24 least one public elevator that is capable of 25 operating on an alternate generated power 26 source following certain disasters and 27 emergencies; requiring that the alternate 28 generated power source be capable of powering a 29 connected fire alarm system; requiring 30 elevators to be prewired to accept alternate 31 generated power; requiring the alternate power 4 6:23 PM 03/02/06 s0860d-ds36-j02
Florida Senate - 2006 COMMITTEE AMENDMENT Bill No. SB 860 Barcode 831804 1 supply to be sufficient to provide emergency 2 lighting to certain portions of the building 3 used by the public; requiring a residential 4 multifamily dwelling to have a generator and 5 fuel source available on the property or proof 6 of a guaranteed service contract; requiring a 7 local building inspector to provide 8 verification of certain engineering plans and 9 capabilities for alternate generated power to 10 the emergency management director of the county 11 by certain dates; requiring a newly constructed 12 residential multifamily dwelling to have an 13 alternate generated power source for use 14 following a disaster or emergency; requiring a 15 local building inspector to provide certain 16 engineering plans for alternate generated power 17 to the emergency management director prior to 18 occupancy of the building; requiring an owner, 19 managing entity, or operator to maintain a 20 written emergency operations plan and a log of 21 inspections; requiring an owner, managing 22 entity, or operator to keep a generator key 23 near an installed generator unit; requiring an 24 elevator inspector to confirm requiring 25 capabilities and a contract for contingent 26 services; providing an effective date. 27 28 29 30 31 5 6:23 PM 03/02/06 s0860d-ds36-j02