Florida Senate - 2012                              CS for SB 704
       
       
       
       By the Committee on Community Affairs; and Senator Bennett
       
       
       
       
       578-01861-12                                           2012704c1
    1                        A bill to be entitled                      
    2         An act relating to building construction and
    3         inspection; amending s. 162.12, F.S.; revising the
    4         authorized methods of sending notices to violators of
    5         local codes; amending s. 381.0065, F.S.; revising the
    6         definition of the term “bedroom” for purposes of
    7         requirements governing onsite sewage treatment and
    8         disposal systems; conforming a cross-reference;
    9         providing that a permit for the installation,
   10         modification, or repair of an onsite sewage treatment
   11         and disposal system approved by the Department of
   12         Health transfers along with the title to the property
   13         in a real estate transaction; prohibiting the
   14         transferred title from being encumbered by new permit
   15         requirements; providing criteria for an abandoned
   16         onsite sewage treatment and disposal system; providing
   17         guidelines for the reconnection of an abandoned
   18         system; providing for the applicability of rules to
   19         the construction of an onsite sewage treatment and
   20         disposal system; providing certain exemptions for a
   21         remodeled single-family home; amending s. 468.604,
   22         F.S.; authorizing a building code administrator or
   23         building official to approve the electronic filing of
   24         building plans and related documents; amending s.
   25         468.609, F.S.; revising the eligibility requirements
   26         of a building code inspector or plans examiner;
   27         revising criteria for the issuance of provisional
   28         certificates; amending s. 489.105, F.S.; revising the
   29         definition of the term “demolish” for purposes of
   30         describing the scope of work of a contractor to
   31         include all buildings or residences, rather than
   32         buildings or residences of certain heights; reenacting
   33         s. 489.105(6), F.S., relating to the definition of the
   34         term “contracting”; clarifying the intent of the
   35         Legislature in the adoption of certain amendments to
   36         s. 489.105(6), F.S., and specifying that the
   37         amendments were intended to be remedial in nature,
   38         clarify existing law, and apply retroactively to any
   39         contract for the sale of manufactured or factory-built
   40         buildings that will be completed on site and otherwise
   41         comply with the requirements under state law; amending
   42         ss. 489.127 and 489.531, F.S.; increasing the maximum
   43         civil penalties that may be assessed against
   44         unlicensed contractors; amending s. 553.721, F.S.;
   45         allocating a portion of the funds derived from a
   46         surcharge on permit fees to the Florida Building Code
   47         Compliance and Mitigation Program; making technical
   48         and grammatical changes; amending s. 553.73, F.S.;
   49         exempting certain buildings or structures used for
   50         hunting from the Florida Building Code; requiring the
   51         Florida Building Commission to adopt by rule a method
   52         of alternative screen enclosure design to accommodate
   53         wind resistance and to keep the screen enclosure
   54         intact; requiring the contractor to provide certain
   55         notice to the homeowner and the local building
   56         department; requiring the rules to be incorporated
   57         into the Florida Building Code; providing for
   58         expiration of the requirement upon incorporation into
   59         the Florida Building Code; providing an effective
   60         date.
   61  
   62  Be It Enacted by the Legislature of the State of Florida:
   63  
   64         Section 1. Subsection (1) of section 162.12, Florida
   65  Statutes, is amended to read:
   66         162.12 Notices.—
   67         (1) All notices required by this part must shall be
   68  provided to the alleged violator by:
   69         (a) Certified mail to, return receipt requested, provided
   70  if such notice is sent under this paragraph to the owner of the
   71  property in question at the address listed in the tax
   72  collector’s office for tax notices, or to and at any other
   73  address provided by the property owner in writing to the local
   74  government for the purpose of receiving notices. For property
   75  owned by a corporation, notices may be provided by certified
   76  mail, return receipt requested, to the registered agent of the
   77  corporation. If any notice sent by certified mail is not signed
   78  as received within 30 days after the date of mailing by such
   79  owner and is returned as unclaimed or refused, notice may be
   80  provided by posting as described in subparagraphs (2)(b)1. and
   81  2. and by first class mail directed to the addresses furnished
   82  to the local government with a properly executed proof of
   83  mailing or affidavit confirming the first class mailing;
   84         (b) Hand delivery by the sheriff or other law enforcement
   85  officer, code inspector, or other person designated by the local
   86  governing body;
   87         (c) Leaving the notice at the violator’s usual place of
   88  residence with any person residing therein who is above 15 years
   89  of age and informing such person of the contents of the notice;
   90  or
   91         (d) In the case of commercial premises, leaving the notice
   92  with the manager or other person in charge.
   93  
   94  Evidence that an attempt has been made to hand deliver or mail
   95  notice as provided in subsection (1), together with proof of
   96  publication or posting as provided in subsection (2), shall be
   97  sufficient to show that the notice requirements of this part
   98  have been met, without regard to whether or not the alleged
   99  violator actually received such notice.
  100         Section 2. Present paragraphs (b) through (p) of subsection
  101  (2) of section 381.0065, Florida Statutes, are redesignated as
  102  paragraphs (c) through (q), respectively, a new paragraph (b) is
  103  added to that subsection, and paragraphs (w) through (z) are
  104  added to subsection (4) of that section, to read:
  105         381.0065 Onsite sewage treatment and disposal systems;
  106  regulation.—
  107         (2) DEFINITIONS.—As used in ss. 381.0065-381.0067, the
  108  term:
  109         (b)1.“Bedroom” means a room that can be used for sleeping
  110  and that:
  111         a. For site-built dwellings, has a minimum of 70 square
  112  feet of conditioned space;
  113         b. For manufactured homes, is constructed according to the
  114  standards of the United States Department of Housing and Urban
  115  Development and has a minimum of 50 square feet of floor area;
  116         c. Is located along an exterior wall;
  117         d. Has a closet and a door or an entrance where a door
  118  could be reasonably installed; and
  119         e. Has an emergency means of escape and rescue opening to
  120  the outside.
  121         2. A room may not be considered a bedroom if it is used to
  122  access another room except a bathroom or closet.
  123         3. “Bedroom” does not include a hallway, bathroom, kitchen,
  124  living room, family room, dining room, den, breakfast nook,
  125  pantry, laundry room, sunroom, recreation room, media/video
  126  room, or exercise room.
  127         (4) PERMITS; INSTALLATION; AND CONDITIONS.—A person may not
  128  construct, repair, modify, abandon, or operate an onsite sewage
  129  treatment and disposal system without first obtaining a permit
  130  approved by the department. The department may issue permits to
  131  carry out this section, but shall not make the issuance of such
  132  permits contingent upon prior approval by the Department of
  133  Environmental Protection, except that the issuance of a permit
  134  for work seaward of the coastal construction control line
  135  established under s. 161.053 shall be contingent upon receipt of
  136  any required coastal construction control line permit from the
  137  Department of Environmental Protection. A construction permit is
  138  valid for 18 months from the issuance date and may be extended
  139  by the department for one 90-day period under rules adopted by
  140  the department. A repair permit is valid for 90 days from the
  141  date of issuance. An operating permit must be obtained prior to
  142  the use of any aerobic treatment unit or if the establishment
  143  generates commercial waste. Buildings or establishments that use
  144  an aerobic treatment unit or generate commercial waste shall be
  145  inspected by the department at least annually to assure
  146  compliance with the terms of the operating permit. The operating
  147  permit for a commercial wastewater system is valid for 1 year
  148  from the date of issuance and must be renewed annually. The
  149  operating permit for an aerobic treatment unit is valid for 2
  150  years from the date of issuance and must be renewed every 2
  151  years. If all information pertaining to the siting, location,
  152  and installation conditions or repair of an onsite sewage
  153  treatment and disposal system remains the same, a construction
  154  or repair permit for the onsite sewage treatment and disposal
  155  system may be transferred to another person, if the transferee
  156  files, within 60 days after the transfer of ownership, an
  157  amended application providing all corrected information and
  158  proof of ownership of the property. There is no fee associated
  159  with the processing of this supplemental information. A person
  160  may not contract to construct, modify, alter, repair, service,
  161  abandon, or maintain any portion of an onsite sewage treatment
  162  and disposal system without being registered under part III of
  163  chapter 489. A property owner who personally performs
  164  construction, maintenance, or repairs to a system serving his or
  165  her own owner-occupied single-family residence is exempt from
  166  registration requirements for performing such construction,
  167  maintenance, or repairs on that residence, but is subject to all
  168  permitting requirements. A municipality or political subdivision
  169  of the state may not issue a building or plumbing permit for any
  170  building that requires the use of an onsite sewage treatment and
  171  disposal system unless the owner or builder has received a
  172  construction permit for such system from the department. A
  173  building or structure may not be occupied and a municipality,
  174  political subdivision, or any state or federal agency may not
  175  authorize occupancy until the department approves the final
  176  installation of the onsite sewage treatment and disposal system.
  177  A municipality or political subdivision of the state may not
  178  approve any change in occupancy or tenancy of a building that
  179  uses an onsite sewage treatment and disposal system until the
  180  department has reviewed the use of the system with the proposed
  181  change, approved the change, and amended the operating permit.
  182         (n) Evaluations for determining the seasonal high-water
  183  table elevations or the suitability of soils for the use of a
  184  new onsite sewage treatment and disposal system shall be
  185  performed by department personnel, professional engineers
  186  registered in the state, or such other persons with expertise,
  187  as defined by rule, in making such evaluations. Evaluations for
  188  determining mean annual flood lines shall be performed by those
  189  persons identified in paragraph (2)(j) (2)(i). The department
  190  shall accept evaluations submitted by professional engineers and
  191  such other persons as meet the expertise established by this
  192  section or by rule unless the department has a reasonable
  193  scientific basis for questioning the accuracy or completeness of
  194  the evaluation.
  195         (w) A permit that is approved by the department and issued
  196  for the installation, modification, or repair of an onsite
  197  sewage treatment and disposal system shall be transferred along
  198  with the title to the property in a real estate transaction. A
  199  title may not be encumbered at the time of transfer by new
  200  permit requirements by a governmental entity for an onsite
  201  sewage treatment and disposal system which differ from the
  202  permitting requirements in effect at the time the system was
  203  permitted, modified, or repaired.
  204         (x)1. An onsite sewage treatment and disposal system is not
  205  considered abandoned if the system is disconnected from a
  206  structure that was made unusable or destroyed following a
  207  disaster and was properly functioning at the time of
  208  disconnection and was not adversely affected by the disaster.
  209  The onsite sewage treatment and disposal system may be
  210  reconnected to a rebuilt structure if:
  211         a. The reconnection of the system is to the same type of
  212  structure which contains the same number of bedrooms or fewer,
  213  provided that the square footage of the structure is less than
  214  or equal to 110 percent of the original square footage of the
  215  structure that existed before the disaster;
  216         b. The system is not a sanitary nuisance; and
  217         c. The system has not been altered without prior
  218  authorization.
  219         2. An onsite sewage treatment and disposal system that
  220  serves a property that is foreclosed upon is not considered
  221  abandoned.
  222         (y) If an onsite sewage treatment and disposal system
  223  permittee receives, relies upon, and undertakes construction of
  224  a system based upon a validly issued construction permit under
  225  rules applicable at the time of construction but a change to a
  226  rule occurs after the approval of the system for construction
  227  but before the final approval of the system, the rules
  228  applicable and in effect at the time of construction approval
  229  apply at the time of final approval if fundamental site
  230  conditions have not changed between the time of construction
  231  approval and final approval.
  232         (z) A modification, replacement, or upgrade of an onsite
  233  sewage treatment and disposal system is not required for a
  234  remodeling addition to a single-family home if a bedroom is not
  235  added.
  236         Section 3. Section 468.604, Florida Statutes, is amended to
  237  read:
  238         468.604 Responsibilities of building code administrators,
  239  plans examiners, and inspectors.—
  240         (1) It is the responsibility of the building code
  241  administrator or building official to administrate, supervise,
  242  direct, enforce, or perform the permitting and inspection of
  243  construction, alteration, repair, remodeling, or demolition of
  244  structures and the installation of building systems within the
  245  boundaries of their governmental jurisdiction, when permitting
  246  is required, to ensure compliance with the Florida Building Code
  247  and any applicable local technical amendment to the Florida
  248  Building Code. The building code administrator or building
  249  official shall faithfully perform these responsibilities without
  250  interference from any person. These responsibilities include:
  251         (a) The review of construction plans to ensure compliance
  252  with all applicable sections of the code. The construction plans
  253  must be reviewed before the issuance of any building, system
  254  installation, or other construction permit. The review of
  255  construction plans must be done by the building code
  256  administrator or building official or by a person having the
  257  appropriate plans examiner license issued under this chapter.
  258         (b) The inspection of each phase of construction where a
  259  building or other construction permit has been issued. The
  260  building code administrator or building official, or a person
  261  having the appropriate building code inspector license issued
  262  under this chapter, shall inspect the construction or
  263  installation to ensure that the work is performed in accordance
  264  with applicable sections of the code.
  265         (2) It is the responsibility of the building code inspector
  266  to conduct inspections of construction, alteration, repair,
  267  remodeling, or demolition of structures and the installation of
  268  building systems, when permitting is required, to ensure
  269  compliance with the Florida Building Code and any applicable
  270  local technical amendment to the Florida Building Code. Each
  271  building code inspector must be licensed in the appropriate
  272  category as defined in s. 468.603. The building code inspector’s
  273  responsibilities must be performed under the direction of the
  274  building code administrator or building official without
  275  interference from any unlicensed person.
  276         (3) It is the responsibility of the plans examiner to
  277  conduct review of construction plans submitted in the permit
  278  application to assure compliance with the Florida Building Code
  279  and any applicable local technical amendment to the Florida
  280  Building Code. The review of construction plans must be done by
  281  the building code administrator or building official or by a
  282  person licensed in the appropriate plans examiner category as
  283  defined in s. 468.603. The plans examiner’s responsibilities
  284  must be performed under the supervision and authority of the
  285  building code administrator or building official without
  286  interference from any unlicensed person.
  287         (4)The Legislature finds that the electronic filing of
  288  construction plans will increase government efficiency, reduce
  289  costs, and increase timeliness of processing permits. If the
  290  building code administrator or building official provides for
  291  electronic filing, the construction plans, drawings,
  292  specifications, reports, final documents, or documents prepared
  293  or issued by a licensee may be dated and electronically signed
  294  and sealed by the licensee in accordance with ss. 668.001
  295  668.006 and may be transmitted electronically to the building
  296  code administrator or building official for approval.
  297         Section 4. Paragraph (c) of subsection (2) and paragraph
  298  (a) of subsection (7) of section 468.609, Florida Statutes, are
  299  amended to read:
  300         468.609 Administration of this part; standards for
  301  certification; additional categories of certification.—
  302         (2) A person may take the examination for certification as
  303  a building code inspector or plans examiner pursuant to this
  304  part if the person:
  305         (c) Meets eligibility requirements according to one of the
  306  following criteria:
  307         1. Demonstrates 5 years’ combined experience in the field
  308  of construction or a related field, building code inspection, or
  309  plans review corresponding to the certification category sought;
  310         2. Demonstrates a combination of postsecondary education in
  311  the field of construction or a related field and experience
  312  which totals 4 years, with at least 1 year of such total being
  313  experience in construction, building code inspection, or plans
  314  review;
  315         3. Demonstrates a combination of technical education in the
  316  field of construction or a related field and experience which
  317  totals 4 years, with at least 1 year of such total being
  318  experience in construction, building code inspection, or plans
  319  review;
  320         4. Currently holds a standard certificate as issued by the
  321  board, or a fire safety inspector license issued pursuant to
  322  chapter 633, and has a minimum of 2 years verifiable full-time
  323  experience in inspection or plan review and satisfactorily
  324  completes a building code inspector or plans examiner training
  325  program of not less than 200 hours in the certification category
  326  sought. The board shall establish by rule criteria for the
  327  development and implementation of the training programs; or
  328         5. Demonstrates a combination of the completion of an
  329  approved training program in the field of building code
  330  inspection or plan review and a minimum of 2 years’ experience
  331  in the field of building code inspection, plan review, fire code
  332  inspections and fire plans review of new buildings as a
  333  firesafety inspector certified under s. 633.081(2), or
  334  construction. The approved training portion of this requirement
  335  shall include proof of satisfactory completion of a training
  336  program of not less than 300 hours which is approved by the
  337  board in the chosen category of building code inspection or plan
  338  review in the certification category sought with not less than
  339  20 hours of instruction in state laws, rules, and ethics
  340  relating to professional standards of practice, duties, and
  341  responsibilities of a certificateholder. The board shall
  342  coordinate with the Building Officials Association of Florida,
  343  Inc., to establish by rule the development and implementation of
  344  the training program.
  345         (7)(a) The board may provide for the issuance of
  346  provisional certificates valid for 1 year such period, not less
  347  than 3 years nor more than 5 years, as specified by board rule,
  348  to any newly employed or promoted building code inspector or
  349  plans examiner who meets the eligibility requirements described
  350  in subsection (2) and any newly employed or promoted building
  351  code administrator who meets the eligibility requirements
  352  described in subsection (3). The provisional license may be
  353  renewed by the board for just cause; however, a provisional
  354  license is not valid for a period longer than 3 years.
  355         Section 5. Subsection (3) of section 489.105, Florida
  356  Statutes, is amended, and subsection (6) of that section is
  357  reenacted, to read:
  358         489.105 Definitions.—As used in this part:
  359         (3) “Contractor” means the person who is qualified for, and
  360  is only responsible for, the project contracted for and means,
  361  except as exempted in this part, the person who, for
  362  compensation, undertakes to, submits a bid to, or does himself
  363  or herself or by others construct, repair, alter, remodel, add
  364  to, demolish, subtract from, or improve any building or
  365  structure, including related improvements to real estate, for
  366  others or for resale to others; and whose job scope is
  367  substantially similar to the job scope described in one of the
  368  subsequent paragraphs of this subsection. For the purposes of
  369  regulation under this part, the term “demolish” applies only to
  370  demolition of steel tanks more than over 50 feet in height;
  371  towers more than over 50 feet in height; other structures more
  372  than over 50 feet in height; and all, other than buildings or
  373  residences over three stories tall; and buildings or residences
  374  over three stories tall. Contractors are subdivided into two
  375  divisions, Division I, consisting of those contractors defined
  376  in paragraphs (a)-(c), and Division II, consisting of those
  377  contractors defined in paragraphs (d)-(r):
  378         (a) “General contractor” means a contractor whose services
  379  are unlimited as to the type of work which he or she may do, who
  380  may contract for any activity requiring licensure under this
  381  part, and who may perform any work requiring licensure under
  382  this part, except as otherwise expressly provided in s. 489.113.
  383         (b) “Building contractor” means a contractor whose services
  384  are limited to construction of commercial buildings and single
  385  dwelling or multiple-dwelling residential buildings, which do
  386  not exceed three stories in height, and accessory use structures
  387  in connection therewith or a contractor whose services are
  388  limited to remodeling, repair, or improvement of any size
  389  building if the services do not affect the structural members of
  390  the building.
  391         (c) “Residential contractor” means a contractor whose
  392  services are limited to construction, remodeling, repair, or
  393  improvement of one-family, two-family, or three-family
  394  residences not exceeding two habitable stories above no more
  395  than one uninhabitable story and accessory use structures in
  396  connection therewith.
  397         (d) “Sheet metal contractor” means a contractor whose
  398  services are unlimited in the sheet metal trade and who has the
  399  experience, knowledge, and skill necessary for the manufacture,
  400  fabrication, assembling, handling, erection, installation,
  401  dismantling, conditioning, adjustment, insulation, alteration,
  402  repair, servicing, or design, if not prohibited by law, of
  403  ferrous or nonferrous metal work of U.S. No. 10 gauge or its
  404  equivalent or lighter gauge and of other materials, including,
  405  but not limited to, fiberglass, used in lieu thereof and of air
  406  handling systems, including the setting of air-handling
  407  equipment and reinforcement of same, the balancing of air
  408  handling systems, and any duct cleaning and equipment sanitizing
  409  that requires at least a partial disassembling of the system.
  410         (e) “Roofing contractor” means a contractor whose services
  411  are unlimited in the roofing trade and who has the experience,
  412  knowledge, and skill to install, maintain, repair, alter,
  413  extend, or design, if not prohibited by law, and use materials
  414  and items used in the installation, maintenance, extension, and
  415  alteration of all kinds of roofing, waterproofing, and coating,
  416  except when coating is not represented to protect, repair,
  417  waterproof, stop leaks, or extend the life of the roof. The
  418  scope of work of a roofing contractor also includes required
  419  roof-deck attachments and any repair or replacement of wood roof
  420  sheathing or fascia as needed during roof repair or replacement.
  421         (f) “Class A air-conditioning contractor” means a
  422  contractor whose services are unlimited in the execution of
  423  contracts requiring the experience, knowledge, and skill to
  424  install, maintain, repair, fabricate, alter, extend, or design,
  425  if not prohibited by law, central air-conditioning,
  426  refrigeration, heating, and ventilating systems, including duct
  427  work in connection with a complete system if such duct work is
  428  performed by the contractor as necessary to complete an air
  429  distribution system, boiler and unfired pressure vessel systems,
  430  and all appurtenances, apparatus, or equipment used in
  431  connection therewith, and any duct cleaning and equipment
  432  sanitizing that requires at least a partial disassembling of the
  433  system; to install, maintain, repair, fabricate, alter, extend,
  434  or design, if not prohibited by law, piping, insulation of
  435  pipes, vessels and ducts, pressure and process piping, and
  436  pneumatic control piping; to replace, disconnect, or reconnect
  437  power wiring on the load side of the dedicated existing
  438  electrical disconnect switch; to install, disconnect, and
  439  reconnect low voltage heating, ventilating, and air-conditioning
  440  control wiring; and to install a condensate drain from an air
  441  conditioning unit to an existing safe waste or other approved
  442  disposal other than a direct connection to a sanitary system.
  443  The scope of work for such contractor also includes any
  444  excavation work incidental thereto, but does not include any
  445  work such as liquefied petroleum or natural gas fuel lines
  446  within buildings, except for disconnecting or reconnecting
  447  changeouts of liquefied petroleum or natural gas appliances
  448  within buildings; potable water lines or connections thereto;
  449  sanitary sewer lines; swimming pool piping and filters; or
  450  electrical power wiring.
  451         (g) “Class B air-conditioning contractor” means a
  452  contractor whose services are limited to 25 tons of cooling and
  453  500,000 Btu of heating in any one system in the execution of
  454  contracts requiring the experience, knowledge, and skill to
  455  install, maintain, repair, fabricate, alter, extend, or design,
  456  if not prohibited by law, central air-conditioning,
  457  refrigeration, heating, and ventilating systems, including duct
  458  work in connection with a complete system only to the extent
  459  such duct work is performed by the contractor as necessary to
  460  complete an air-distribution system being installed under this
  461  classification, and any duct cleaning and equipment sanitizing
  462  that requires at least a partial disassembling of the system; to
  463  install, maintain, repair, fabricate, alter, extend, or design,
  464  if not prohibited by law, piping and insulation of pipes,
  465  vessels, and ducts; to replace, disconnect, or reconnect power
  466  wiring on the load side of the dedicated existing electrical
  467  disconnect switch; to install, disconnect, and reconnect low
  468  voltage heating, ventilating, and air-conditioning control
  469  wiring; and to install a condensate drain from an air
  470  conditioning unit to an existing safe waste or other approved
  471  disposal other than a direct connection to a sanitary system.
  472  The scope of work for such contractor also includes any
  473  excavation work incidental thereto, but does not include any
  474  work such as liquefied petroleum or natural gas fuel lines
  475  within buildings, except for disconnecting or reconnecting
  476  changeouts of liquefied petroleum or natural gas appliances
  477  within buildings; potable water lines or connections thereto;
  478  sanitary sewer lines; swimming pool piping and filters; or
  479  electrical power wiring.
  480         (h) “Class C air-conditioning contractor” means a
  481  contractor whose business is limited to the servicing of air
  482  conditioning, heating, or refrigeration systems, including any
  483  duct cleaning and equipment sanitizing that requires at least a
  484  partial disassembling of the system, and whose certification or
  485  registration, issued pursuant to this part, was valid on October
  486  1, 1988. Only a person who was registered or certified as a
  487  Class C air-conditioning contractor as of October 1, 1988, shall
  488  be so registered or certified after October 1, 1988. However,
  489  the board shall continue to license and regulate those Class C
  490  air-conditioning contractors who held Class C licenses before
  491  October 1, 1988.
  492         (i) “Mechanical contractor” means a contractor whose
  493  services are unlimited in the execution of contracts requiring
  494  the experience, knowledge, and skill to install, maintain,
  495  repair, fabricate, alter, extend, or design, if not prohibited
  496  by law, central air-conditioning, refrigeration, heating, and
  497  ventilating systems, including duct work in connection with a
  498  complete system if such duct work is performed by the contractor
  499  as necessary to complete an air-distribution system, boiler and
  500  unfired pressure vessel systems, lift station equipment and
  501  piping, and all appurtenances, apparatus, or equipment used in
  502  connection therewith, and any duct cleaning and equipment
  503  sanitizing that requires at least a partial disassembling of the
  504  system; to install, maintain, repair, fabricate, alter, extend,
  505  or design, if not prohibited by law, piping, insulation of
  506  pipes, vessels and ducts, pressure and process piping, pneumatic
  507  control piping, gasoline tanks and pump installations and piping
  508  for same, standpipes, air piping, vacuum line piping, oxygen
  509  lines, nitrous oxide piping, ink and chemical lines, fuel
  510  transmission lines, liquefied petroleum gas lines within
  511  buildings, and natural gas fuel lines within buildings; to
  512  replace, disconnect, or reconnect power wiring on the load side
  513  of the dedicated existing electrical disconnect switch; to
  514  install, disconnect, and reconnect low voltage heating,
  515  ventilating, and air-conditioning control wiring; and to install
  516  a condensate drain from an air-conditioning unit to an existing
  517  safe waste or other approved disposal other than a direct
  518  connection to a sanitary system. The scope of work for such
  519  contractor also includes any excavation work incidental thereto,
  520  but does not include any work such as potable water lines or
  521  connections thereto, sanitary sewer lines, swimming pool piping
  522  and filters, or electrical power wiring.
  523         (j) “Commercial pool/spa contractor” means a contractor
  524  whose scope of work involves, but is not limited to, the
  525  construction, repair, and servicing of any swimming pool, or hot
  526  tub or spa, whether public, private, or otherwise, regardless of
  527  use. The scope of work includes the installation, repair, or
  528  replacement of existing equipment, any cleaning or equipment
  529  sanitizing that requires at least a partial disassembling,
  530  excluding filter changes, and the installation of new pool/spa
  531  equipment, interior finishes, the installation of package pool
  532  heaters, the installation of all perimeter piping and filter
  533  piping, and the construction of equipment rooms or housing for
  534  pool/spa equipment, and also includes the scope of work of a
  535  swimming pool/spa servicing contractor. The scope of such work
  536  does not include direct connections to a sanitary sewer system
  537  or to potable water lines. The installation, construction,
  538  modification, or replacement of equipment permanently attached
  539  to and associated with the pool or spa for the purpose of water
  540  treatment or cleaning of the pool or spa requires licensure;
  541  however, the usage of such equipment for the purposes of water
  542  treatment or cleaning does not require licensure unless the
  543  usage involves construction, modification, or replacement of
  544  such equipment. Water treatment that does not require such
  545  equipment does not require a license. In addition, a license is
  546  not required for the cleaning of the pool or spa in a way that
  547  does not affect the structural integrity of the pool or spa or
  548  its associated equipment.
  549         (k) “Residential pool/spa contractor” means a contractor
  550  whose scope of work involves, but is not limited to, the
  551  construction, repair, and servicing of a residential swimming
  552  pool, or hot tub or spa, regardless of use. The scope of work
  553  includes the installation, repair, or replacement of existing
  554  equipment, any cleaning or equipment sanitizing that requires at
  555  least a partial disassembling, excluding filter changes, and the
  556  installation of new pool/spa equipment, interior finishes, the
  557  installation of package pool heaters, the installation of all
  558  perimeter piping and filter piping, and the construction of
  559  equipment rooms or housing for pool/spa equipment, and also
  560  includes the scope of work of a swimming pool/spa servicing
  561  contractor. The scope of such work does not include direct
  562  connections to a sanitary sewer system or to potable water
  563  lines. The installation, construction, modification, or
  564  replacement of equipment permanently attached to and associated
  565  with the pool or spa for the purpose of water treatment or
  566  cleaning of the pool or spa requires licensure; however, the
  567  usage of such equipment for the purposes of water treatment or
  568  cleaning does not require licensure unless the usage involves
  569  construction, modification, or replacement of such equipment.
  570  Water treatment that does not require such equipment does not
  571  require a license. In addition, a license is not required for
  572  the cleaning of the pool or spa in a way that does not affect
  573  the structural integrity of the pool or spa or its associated
  574  equipment.
  575         (l) “Swimming pool/spa servicing contractor” means a
  576  contractor whose scope of work involves, but is not limited to,
  577  the repair and servicing of a swimming pool, or hot tub or spa,
  578  whether public or private, or otherwise, regardless of use. The
  579  scope of work includes the repair or replacement of existing
  580  equipment, any cleaning or equipment sanitizing that requires at
  581  least a partial disassembling, excluding filter changes, and the
  582  installation of new pool/spa equipment, interior refinishing,
  583  the reinstallation or addition of pool heaters, the repair or
  584  replacement of all perimeter piping and filter piping, the
  585  repair of equipment rooms or housing for pool/spa equipment, and
  586  the substantial or complete draining of a swimming pool, or hot
  587  tub or spa, for the purpose of repair or renovation. The scope
  588  of such work does not include direct connections to a sanitary
  589  sewer system or to potable water lines. The installation,
  590  construction, modification, substantial or complete disassembly,
  591  or replacement of equipment permanently attached to and
  592  associated with the pool or spa for the purpose of water
  593  treatment or cleaning of the pool or spa requires licensure;
  594  however, the usage of such equipment for the purposes of water
  595  treatment or cleaning does not require licensure unless the
  596  usage involves construction, modification, substantial or
  597  complete disassembly, or replacement of such equipment. Water
  598  treatment that does not require such equipment does not require
  599  a license. In addition, a license is not required for the
  600  cleaning of the pool or spa in a way that does not affect the
  601  structural integrity of the pool or spa or its associated
  602  equipment.
  603         (m) “Plumbing contractor” means a contractor whose
  604  contracting business consists of the execution of contracts
  605  requiring the experience, financial means, knowledge, and skill
  606  to install, maintain, repair, alter, extend, or, if not
  607  prohibited by law, design plumbing. A plumbing contractor may
  608  install, maintain, repair, alter, extend, or, if not prohibited
  609  by law, design the following without obtaining an additional
  610  local regulatory license, certificate, or registration: sanitary
  611  drainage or storm drainage facilities; venting systems; public
  612  or private water supply systems; septic tanks; drainage and
  613  supply wells; swimming pool piping; irrigation systems; or solar
  614  heating water systems and all appurtenances, apparatus, or
  615  equipment used in connection therewith, including boilers and
  616  pressure process piping and including the installation of water,
  617  natural gas, liquefied petroleum gas and related venting, and
  618  storm and sanitary sewer lines; and water and sewer plants and
  619  substations. The scope of work of the plumbing contractor also
  620  includes the design, if not prohibited by law, and installation,
  621  maintenance, repair, alteration, or extension of air-piping,
  622  vacuum line piping, oxygen line piping, nitrous oxide piping,
  623  and all related medical gas systems; fire line standpipes and
  624  fire sprinklers if authorized by law; ink and chemical lines;
  625  fuel oil and gasoline piping and tank and pump installation,
  626  except bulk storage plants; and pneumatic control piping
  627  systems, all in a manner that complies with all plans,
  628  specifications, codes, laws, and regulations applicable. The
  629  scope of work of the plumbing contractor applies to private
  630  property and public property, including any excavation work
  631  incidental thereto, and includes the work of the specialty
  632  plumbing contractor. Such contractor shall subcontract, with a
  633  qualified contractor in the field concerned, all other work
  634  incidental to the work but which is specified as being the work
  635  of a trade other than that of a plumbing contractor. This
  636  definition does not limit the scope of work of any specialty
  637  contractor certified pursuant to s. 489.113(6), and does not
  638  require certification or registration under this part of any
  639  authorized employee of a public natural gas utility or of a
  640  private natural gas utility regulated by the Public Service
  641  Commission when disconnecting and reconnecting water lines in
  642  the servicing or replacement of an existing water heater.
  643         (n) “Underground utility and excavation contractor” means a
  644  contractor whose services are limited to the construction,
  645  installation, and repair, on public or private property, whether
  646  accomplished through open excavations or through other means,
  647  including, but not limited to, directional drilling, auger
  648  boring, jacking and boring, trenchless technologies, wet and dry
  649  taps, grouting, and slip lining, of main sanitary sewer
  650  collection systems, main water distribution systems, storm sewer
  651  collection systems, and the continuation of utility lines from
  652  the main systems to a point of termination up to and including
  653  the meter location for the individual occupancy, sewer
  654  collection systems at property line on residential or single
  655  occupancy commercial properties, or on multioccupancy properties
  656  at manhole or wye lateral extended to an invert elevation as
  657  engineered to accommodate future building sewers, water
  658  distribution systems, or storm sewer collection systems at storm
  659  sewer structures. However, an underground utility and excavation
  660  contractor may install empty underground conduits in rights-of
  661  way, easements, platted rights-of-way in new site development,
  662  and sleeves for parking lot crossings no smaller than 2 inches
  663  in diameter if each conduit system installed is designed by a
  664  licensed professional engineer or an authorized employee of a
  665  municipality, county, or public utility and the installation of
  666  such conduit does not include installation of any conductor
  667  wiring or connection to an energized electrical system. An
  668  underground utility and excavation contractor may not install
  669  piping that is an integral part of a fire protection system as
  670  defined in s. 633.021 beginning at the point where the piping is
  671  used exclusively for such system.
  672         (o) “Solar contractor” means a contractor whose services
  673  consist of the installation, alteration, repair, maintenance,
  674  relocation, or replacement of solar panels for potable solar
  675  water heating systems, swimming pool solar heating systems, and
  676  photovoltaic systems and any appurtenances, apparatus, or
  677  equipment used in connection therewith, whether public, private,
  678  or otherwise, regardless of use. A contractor, certified or
  679  registered pursuant to this chapter, is not required to become a
  680  certified or registered solar contractor or to contract with a
  681  solar contractor in order to provide services enumerated in this
  682  paragraph that are within the scope of the services such
  683  contractors may render under this part.
  684         (p) “Pollutant storage systems contractor” means a
  685  contractor whose services are limited to, and who has the
  686  experience, knowledge, and skill to install, maintain, repair,
  687  alter, extend, or design, if not prohibited by law, and use
  688  materials and items used in the installation, maintenance,
  689  extension, and alteration of, pollutant storage tanks. Any
  690  person installing a pollutant storage tank shall perform such
  691  installation in accordance with the standards adopted pursuant
  692  to s. 376.303.
  693         (q) “Glass and glazing contractor” means a contractor whose
  694  services are unlimited in the execution of contracts requiring
  695  the experience, knowledge, and skill to install, attach,
  696  maintain, repair, fabricate, alter, extend, or design, in
  697  residential and commercial applications without any height
  698  restrictions, all types of windows, glass, and mirrors, whether
  699  fixed or movable; swinging or sliding glass doors attached to
  700  existing walls, floors, columns, or other structural members of
  701  the building; glass holding or supporting mullions or horizontal
  702  bars; structurally anchored impact-resistant opening protection
  703  attached to existing building walls, floors, columns, or other
  704  structural members of the building; prefabricated glass, metal,
  705  or plastic curtain walls; storefront frames or panels; shower
  706  and tub enclosures; metal fascias; and caulking incidental to
  707  such work and assembly.
  708         (r) “Specialty contractor” means a contractor whose scope
  709  of work and responsibility is limited to a particular phase of
  710  construction established in a category adopted by board rule and
  711  whose scope is limited to a subset of the activities described
  712  in one of the paragraphs of this subsection.
  713         (6) “Contracting” means, except as exempted in this part,
  714  engaging in business as a contractor and includes, but is not
  715  limited to, performance of any of the acts as set forth in
  716  subsection (3) which define types of contractors. The attempted
  717  sale of contracting services and the negotiation or bid for a
  718  contract on these services also constitutes contracting. If the
  719  services offered require licensure or agent qualification, the
  720  offering, negotiation for a bid, or attempted sale of these
  721  services requires the corresponding licensure. However, the term
  722  “contracting” shall not extend to an individual, partnership,
  723  corporation, trust, or other legal entity that offers to sell or
  724  sells completed residences on property on which the individual
  725  or business entity has any legal or equitable interest, or to
  726  the individual or business entity that offers to sell or sells
  727  manufactured or factory-built buildings that will be completed
  728  on site on property on which either party to a contract has any
  729  legal or equitable interest, if the services of a qualified
  730  contractor certified or registered pursuant to the requirements
  731  of this chapter have been or will be retained for the purpose of
  732  constructing or completing such residences.
  733         Section 6. The amendments to s. 489.105(6), Florida
  734  Statutes, as enacted by s. 30 of chapter 2008-240, Laws of
  735  Florida, were intended to protect the sanctity of contracts for
  736  the sale of manufactured or factory-built buildings that will be
  737  completed on site and to ensure that those contracts are legal
  738  and enforceable contracts under state law. The amendments were
  739  intended to be remedial in nature, clarify existing law, and
  740  apply retroactively to any contract for the sale of manufactured
  741  or factory-built buildings that will be completed on site and
  742  otherwise comply with state law.
  743         Section 7. Paragraph (c) of subsection (5) of section
  744  489.127, Florida Statutes, is amended to read:
  745         489.127 Prohibitions; penalties.—
  746         (5) Each county or municipality may, at its option,
  747  designate one or more of its code enforcement officers, as
  748  defined in chapter 162, to enforce, as set out in this
  749  subsection, the provisions of subsection (1) and s. 489.132(1)
  750  against persons who engage in activity for which a county or
  751  municipal certificate of competency or license or state
  752  certification or registration is required.
  753         (c) The local governing body of the county or municipality
  754  is authorized to enforce codes and ordinances against unlicensed
  755  contractors under the provisions of this subsection and may
  756  enact an ordinance establishing procedures for implementing this
  757  subsection, including a schedule of penalties to be assessed by
  758  the code enforcement officer. The maximum civil penalty which
  759  may be levied shall not exceed $2,000 $500. Moneys collected
  760  pursuant to this subsection shall be retained locally, as
  761  provided for by local ordinance, and may be set aside in a
  762  specific fund to support future enforcement activities against
  763  unlicensed contractors.
  764         Section 8. Paragraph (c) of subsection (4) of section
  765  489.531, Florida Statutes, is amended to read:
  766         489.531 Prohibitions; penalties.—
  767         (4) Each county or municipality may, at its option,
  768  designate one or more of its code enforcement officers, as
  769  defined in chapter 162, to enforce, as set out in this
  770  subsection, the provisions of subsection (1) against persons who
  771  engage in activity for which county or municipal certification
  772  is required.
  773         (c) The local governing body of the county or municipality
  774  is authorized to enforce codes and ordinances against unlicensed
  775  contractors under the provisions of this section and may enact
  776  an ordinance establishing procedures for implementing this
  777  section, including a schedule of penalties to be assessed by the
  778  code enforcement officers. The maximum civil penalty which may
  779  be levied shall not exceed $2,000 $500. Moneys collected
  780  pursuant to this section shall be retained locally as provided
  781  for by local ordinance and may be set aside in a specific fund
  782  to support future enforcement activities against unlicensed
  783  contractors.
  784         Section 9. Section 553.721, Florida Statutes, is amended to
  785  read:
  786         553.721 Surcharge.—In order for the Department of Business
  787  and Professional Regulation to administer and carry out the
  788  purposes of this part and related activities, there is hereby
  789  created a surcharge, to be assessed at the rate of 1.5 percent
  790  of the permit fees associated with enforcement of the Florida
  791  Building Code as defined by the uniform account criteria and
  792  specifically the uniform account code for building permits
  793  adopted for local government financial reporting pursuant to s.
  794  218.32. The minimum amount collected on any permit issued shall
  795  be $2. The unit of government responsible for collecting a
  796  permit fee pursuant to s. 125.56(4) or s. 166.201 shall collect
  797  the such surcharge and electronically remit the funds collected
  798  to the department on a quarterly calendar basis beginning not
  799  later than December 31, 2010, for the preceding quarter, and
  800  continuing each third month thereafter. The, and such unit of
  801  government shall retain 10 percent of the surcharge collected to
  802  fund the participation of building departments in the national
  803  and state building code adoption processes and to provide
  804  education related to enforcement of the Florida Building Code.
  805  All funds remitted to the department pursuant to this section
  806  shall be deposited in the Professional Regulation Trust Fund.
  807  Funds collected from the such surcharge shall be allocated to
  808  fund used exclusively for the duties of the Florida Building
  809  Commission and the Florida Building Code Compliance and
  810  Mitigation Program under s. 553.841. Funds allocated to the
  811  Florida Building Code Compliance and Mitigation Program shall be
  812  $925,000 each fiscal year. The funds collected from the
  813  surcharge may and the Department of Business and Professional
  814  Regulation under this chapter and shall not be used to fund
  815  research on techniques for mitigation of radon in existing
  816  buildings. Funds used by the department as well as funds to be
  817  transferred to the Department of Health shall be as prescribed
  818  in the annual General Appropriations Act. The department shall
  819  adopt rules governing the collection and remittance of
  820  surcharges pursuant to in accordance with chapter 120.
  821         Section 10. Subsection (10) of section 553.73, Florida
  822  Statutes, is amended, and subsection (18) is added to that
  823  section, to read:
  824         553.73 Florida Building Code.—
  825         (10) The following buildings, structures, and facilities
  826  are exempt from the Florida Building Code as provided by law,
  827  and any further exemptions shall be as determined by the
  828  Legislature and provided by law:
  829         (a) Buildings and structures specifically regulated and
  830  preempted by the Federal Government.
  831         (b) Railroads and ancillary facilities associated with the
  832  railroad.
  833         (c) Nonresidential farm buildings on farms.
  834         (d) Temporary buildings or sheds used exclusively for
  835  construction purposes.
  836         (e) Mobile or modular structures used as temporary offices,
  837  except that the provisions of part II relating to accessibility
  838  by persons with disabilities shall apply to such mobile or
  839  modular structures.
  840         (f) Those structures or facilities of electric utilities,
  841  as defined in s. 366.02, which are directly involved in the
  842  generation, transmission, or distribution of electricity.
  843         (g) Temporary sets, assemblies, or structures used in
  844  commercial motion picture or television production, or any
  845  sound-recording equipment used in such production, on or off the
  846  premises.
  847         (h) Storage sheds that are not designed for human
  848  habitation and that have a floor area of 720 square feet or less
  849  are not required to comply with the mandatory wind-borne-debris
  850  impact standards of the Florida Building Code. In addition, such
  851  buildings that are 400 square feet or less and that are intended
  852  for use in conjunction with one- and two-family residences are
  853  not subject to the door height and width requirements of the
  854  Florida Building Code.
  855         (i) Chickees constructed by the Miccosukee Tribe of Indians
  856  of Florida or the Seminole Tribe of Florida. As used in this
  857  paragraph, the term “chickee” means an open-sided wooden hut
  858  that has a thatched roof of palm or palmetto or other
  859  traditional materials, and that does not incorporate any
  860  electrical, plumbing, or other nonwood features.
  861         (j) Family mausoleums not exceeding 250 square feet in area
  862  which are prefabricated and assembled on site or preassembled
  863  and delivered on site and have walls, roofs, and a floor
  864  constructed of granite, marble, or reinforced concrete.
  865         (k) A building or structure having less than 1,000 square
  866  feet which is constructed and owned by a natural person for
  867  hunting and which is repaired or reconstructed to the same
  868  dimension and condition as existed on January 1, 2011, if the
  869  building or structure:
  870         1. Is not rented or leased or used as a principal
  871  residence;
  872         2. Is not located within the 100-year floodplain according
  873  to the Federal Emergency Management Agency’s current Flood
  874  Insurance Rate Map; and
  875         3. Is not connected to an off-site electric power or water
  876  supply.
  877  
  878  With the exception of paragraphs (a), (b), (c), and (f), in
  879  order to preserve the health, safety, and welfare of the public,
  880  the Florida Building Commission may, by rule adopted pursuant to
  881  chapter 120, provide for exceptions to the broad categories of
  882  buildings exempted in this section, including exceptions for
  883  application of specific sections of the code or standards
  884  adopted therein. The Department of Agriculture and Consumer
  885  Services shall have exclusive authority to adopt by rule,
  886  pursuant to chapter 120, exceptions to nonresidential farm
  887  buildings exempted in paragraph (c) when reasonably necessary to
  888  preserve public health, safety, and welfare. The exceptions must
  889  be based upon specific criteria, such as under-roof floor area,
  890  aggregate electrical service capacity, HVAC system capacity, or
  891  other building requirements. Further, the commission may
  892  recommend to the Legislature additional categories of buildings,
  893  structures, or facilities which should be exempted from the
  894  Florida Building Code, to be provided by law. The Florida
  895  Building Code does not apply to temporary housing provided by
  896  the Department of Corrections to any prisoner in the state
  897  correctional system.
  898         (18) The Florida Building Commission shall adopt by rule a
  899  method of alternative screen enclosure design that requires the
  900  removal of a section of the screen in order to accommodate wind
  901  resistance and keep the screen enclosure intact. The rules for
  902  an alternative screen enclosure design must require that the
  903  contractor provide notice to the homeowner and local building
  904  department that the homeowner must cut, retract, or remove a
  905  panel of the screen from the enclosure in accordance with
  906  engineering instructions when wind speeds are expected to exceed
  907  75 miles per hour and that the contractor will provide a
  908  replacement screen at the initial point of sale to repair the
  909  screen enclosure for designs that require cutting. The Florida
  910  Building Commission shall adopt the method before October 1,
  911  2012, and incorporate the requirements into the next version of
  912  the Florida Building Code. This subsection expires upon adoption
  913  and implementation of the requirements of this subsection into
  914  the Florida Building Code.
  915         Section 11. This act shall take effect July 1, 2012.