Skip to Navigation | Skip to Main Content | Skip to Site Map

MyFloridaHouse.gov | Mobile Site

Senate Tracker: Sign Up | Login

The Florida Senate

2024 Florida Statutes

Chapter 633
FIRE PREVENTION AND CONTROL
CHAPTER 633
CHAPTER 633
FIRE PREVENTION AND CONTROL
PART I
GENERAL PROVISIONS
(ss. 633.102-633.1423)
PART II
FIRE SAFETY AND PREVENTION
(ss. 633.202-633.228)
PART III
FIRE PROTECTION AND SUPPRESSION
(ss. 633.302-633.3482)
PART IV
FIRE STANDARDS AND TRAINING
(ss. 633.402-633.446)
PART V
FLORIDA FIREFIGHTERS OCCUPATIONAL SAFETY AND HEALTH
ACT
(ss. 633.502-633.536)
PART I
GENERAL PROVISIONS
633.102 Definitions.
633.104 State Fire Marshal; authority; duties; rules.
633.106 State Fire Marshal; disciplinary authority; administrative fine and probation in lieu of suspension, revocation, or refusal to issue a license, permit, or certificate.
633.107 Exemption from disqualification from licensure or certification.
633.108 State Fire Marshal; chapter and rules; force and effect.
633.112 State Fire Marshal; hearings; investigations; recordkeeping and reports; subpoenas of witnesses; orders of circuit court.
633.114 State Fire Marshal agents; authority; duties; compensation.
633.116 Agents; powers to make arrests, conduct searches and seizures, serve summonses, and carry firearms.
633.118 Persons authorized to enforce laws and rules of State Fire Marshal.
633.122 Impersonating State Fire Marshal, firefighter, volunteer firefighter, or firesafety inspector; criminal penalties.
633.124 Penalty for violation of law, rule, or order to cease and desist or for failure to comply with corrective order.
633.126 Investigation of fraudulent insurance claims and crimes; immunity of insurance companies supplying information.
633.128 Division of State Fire Marshal; powers, duties.
633.132 Fees.
633.134 Gifts and grants.
633.135 Firefighter Assistance Grant Program.
633.136 Fire and Emergency Incident Information Reporting Program; duties; fire reports.
633.137 Firefighter Cancer Decontamination Equipment Grant Program.
633.138 Notice of change of address of record; notice of felony actions.
633.142 Reduced Cigarette Ignition Propensity Standard and Firefighter Protection Act; preemption.
633.1423 State Fire Marshal direct-support organization.
633.102 Definitions.As used in this chapter, the term:
(1) “Board” means the Florida Fire Safety Board.
(2) “Contracting” means engaging in business as a contractor.
(3)(a) “Contractor I” means a contractor whose business includes the execution of contracts requiring the ability to lay out, fabricate, install, inspect, alter, repair, and service all types of fire protection systems, excluding preengineered systems.
(b) “Contractor II” means a contractor whose business is limited to the execution of contracts requiring the ability to lay out, fabricate, install, inspect, alter, repair, and service water sprinkler systems, water spray systems, foam-water sprinkler systems, foam-water spray systems, standpipes, combination standpipes and sprinkler risers, all piping that is an integral part of the system beginning at the point of service as defined in this section, sprinkler tank heaters, air lines, thermal systems used in connection with sprinklers, and tanks and pumps connected thereto, excluding preengineered systems.
(c) “Contractor III” means a contractor whose business is limited to the execution of contracts requiring the ability to fabricate, install, inspect, alter, repair, and service carbon dioxide systems, foam extinguishing systems, dry chemical systems, and Halon and other chemical systems, excluding preengineered systems.
(d) “Contractor IV” means a contractor whose business is limited to the execution of contracts requiring the ability to lay out, fabricate, install, inspect, alter, repair, and service automatic fire sprinkler systems for detached one-family dwellings, detached two-family dwellings, and mobile homes, excluding preengineered systems and excluding single-family homes in cluster units, such as apartments, condominiums, and assisted living facilities or any building that is connected to other dwellings. A Contractor IV is limited to the scope of practice specified in NFPA 13D.
(e) “Contractor V” means a contractor whose business is limited to the execution of contracts requiring the ability to fabricate, install, alter, repair, and service the underground piping for a fire protection system using water as the extinguishing agent beginning at the point of service as defined in this act and ending no more than 1 foot above the finished floor. A Contractor V may inspect underground piping for a water-based fire protection system under the direction of a Contractor I or Contractor II.

This subsection may not be construed to include engineers or architects within the defined terms and does not limit or prohibit a licensed fire protection engineer or architect with fire protection design experience from designing any type of fire protection system. A distinction is made between system design concepts prepared by the design professional and system layout as defined in this section and typically prepared by the contractor. However, a person certified under this chapter as a Contractor I or Contractor II may design new fire protection systems of 49 or fewer sprinklers; may design the alteration of an existing fire sprinkler system if the alteration consists of the relocation, addition, or deletion of 49 or fewer sprinklers, notwithstanding the size of the existing fire sprinkler system; and may design the alteration of an existing fire sprinkler system if the alteration consists of the relocation or deletion of 249 or fewer sprinklers and the addition of up to 49 sprinklers, as long as the cumulative total number of fire sprinklers being added, relocated, or deleted does not exceed 249, notwithstanding the size of the existing fire sprinkler system, if there is no change of occupancy of the affected areas, as defined in the Florida Building Code and the Florida Fire Prevention Code, and there is no change in the water demand as defined in NFPA 13, “Standard for the Installation of Sprinkler Systems,” and if the occupancy hazard classification as defined in NFPA 13 is reduced or remains the same as a result of the alteration. Conflicts between the Florida Building Code and the Florida Fire Prevention Code shall be resolved pursuant to s. 553.73(1)(d). A person certified as a Contractor I, Contractor II, or Contractor IV may design a new fire protection system or design the alteration of an existing fire protection system, the scope of which complies with NFPA 13D, “Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes,” as adopted by the State Fire Marshal, notwithstanding the number of fire sprinklers. Contractor-developed plans may not be required by any local permitting authority to be sealed by a registered professional engineer.

(4) “Department” means the Department of Financial Services.
(5) “Division” means the Division of State Fire Marshal within the Department of Financial Services.
(6) “Explosives” means any chemical compound or mixture that has the property of yielding readily to combustion or oxidation upon the application of heat, flame, or shock and is capable of producing an explosion and is commonly used for that purpose, including but not limited to dynamite, nitroglycerin, trinitrotoluene, ammonium nitrate when combined with other ingredients to form an explosive mixture, blasting caps, and detonators; but the term does not include cartridges for firearms or fireworks as defined in chapter 791.
(7)(a) “Fire equipment dealer Class A” means a licensed fire equipment dealer whose business is limited to servicing, recharging, repairing, installing, or inspecting all types of fire extinguishers and conducting hydrostatic tests on all types of fire extinguishers.
(b) “Fire equipment dealer Class B” means a licensed fire equipment dealer whose business is limited to servicing, recharging, repairing, installing, or inspecting all types of fire extinguishers, including recharging carbon dioxide units and conducting hydrostatic tests on all types of fire extinguishers, except carbon dioxide units.
(c) “Fire equipment dealer Class C” means a licensed fire equipment dealer whose business is limited to servicing, recharging, repairing, installing, or inspecting all types of fire extinguishers, except recharging carbon dioxide units, and conducting hydrostatic tests on all types of fire extinguishers, except carbon dioxide units.
(d) “Fire equipment dealer Class D” means a licensed fire equipment dealer whose business is limited to servicing, recharging, repairing, installing, hydrotesting, or inspecting of all types of preengineered fire extinguishing systems.
(8) “Fire extinguisher” means a cylinder that:
(a) Is portable and can be carried or is on wheels.
(b) Is manually operated.
(c) May use a variety of extinguishing agents that are expelled under pressure.
(d) Is rechargeable or nonrechargeable.
(e) Is installed, serviced, repaired, recharged, inspected, and hydrotested according to applicable procedures of the manufacturer, standards of the National Fire Protection Association, and the Code of Federal Regulations.
(f) Is listed by a nationally recognized testing laboratory.
(9) “Firefighter” means an individual who holds a current and valid Firefighter Certificate of Compliance or Special Certificate of Compliance issued by the division under s. 633.408.
(10) “Fire hydrant” means a connection to a water main, elevated water tank, or other source of water for the purpose of supplying water to a fire hose or other fire protection apparatus for fire suppression operations. The term does not include a fire protection system.
(11) “Fire protection system” means a system individually designed to protect the interior or exterior of a specific building or buildings, structure, or other special hazard from fire. Such systems include, but are not limited to, water sprinkler systems, water spray systems, foam-water sprinkler systems, foam-water spray systems, carbon dioxide systems, foam extinguishing systems, dry chemical systems, and Halon and other chemical systems used for fire protection use. Such systems also include any overhead and underground fire mains; fire hydrants and hydrant mains; standpipes and hoses connected to sprinkler systems; sprinkler tank heaters; air lines; thermal systems used in connection with fire sprinkler systems; tanks providing water supply or pump fuel, including piping for such tanks; and pumps connected to fire sprinkler systems.
(12) “Firesafety inspector” means an individual who holds a current and valid Fire Safety Inspector Certificate of Compliance issued by the division under s. 633.216 who is officially assigned the duties of conducting firesafety inspections of buildings and facilities on a recurring or regular basis on behalf of the state or any county, municipality, or special district with fire safety responsibilities.
(13) “Fire service provider” means a municipality or county, the state, the division, or any political subdivision of the state, including authorities and special districts, that employs firefighters or uses volunteer firefighters to provide fire extinguishment or fire prevention services for the protection of life and property. The term includes any organization under contract or other agreement with such entity to provide such services.
(14) “Fire service support personnel” means an individual who does not hold a current and valid certificate issued by the division and who may only perform support services.
(15) “Handling” means touching, holding, taking up, moving, controlling, or otherwise affecting with the hand or by any other agency.
(16) “Highway” means every way or place of whatever nature within the state open to the use of the public, as a matter of right, for purposes of vehicular traffic and includes public streets, alleys, roadways, or driveways upon grounds of colleges, universities, and institutions and other ways open to travel by the public, notwithstanding that the same have been temporarily closed for the purpose of construction, reconstruction, maintenance, or repair. The term does not include a roadway or driveway upon grounds owned by a private person.
(17) “Hot zone” means the area immediately around an incident where serious threat of harm exists, which includes the collapse zone for a structure fire.
(18) “Keeping” means possessing, holding, retaining, maintaining, or having habitually in stock for sale.
(19) “Layout” means the layout of risers, cross mains, branch lines, sprinkler heads, sizing of pipe, hanger locations, and hydraulic calculations in accordance with the design concepts established through the Responsibility Rules adopted by the Board of Professional Engineers.
(20) “Manufacture” means the compounding, combining, producing, or making of anything or the working of anything by hand, by machinery, or by any other agency into forms suitable for use.
(21) “Minimum firesafety standard” means a requirement or group of requirements adopted pursuant to s. 633.208 by a county, municipality, or special district with firesafety responsibilities, or by the State Fire Marshal pursuant to s. 394.879, for the protection of life and property from loss by fire which shall be met, as a minimum, by every occupancy, facility, building, structure, premises, device, or activity to which it applies.
(22) “Minimum Standards Course” means training of at least 360 hours as prescribed by rule adopted by the division which is required to obtain a Firefighter Certificate of Compliance under s. 633.408.
(23) “Motor vehicle” means any device propelled by power other than muscular power in, upon, or by which any individual or property is or may be transported or drawn upon a highway, except a device moved or used exclusively upon stationary rails or tracks.
(24) “Point-of-service” means the point at which the underground piping for a fire protection system as defined in this section using water as the extinguishing agent becomes used exclusively for the fire protection system.
(25)(a) “Preengineered system” means a fire suppression system which:
1. Uses any of a variety of extinguishing agents.
2. Is designed to protect specific hazards.
3. Must be installed according to pretested limitations and configurations specified by the manufacturer and applicable National Fire Protection Association (NFPA) standards. Only those chapters within the National Fire Protection Association standards which pertain to servicing, recharging, repairing, installing, hydrotesting, or inspecting any type of preengineered fire extinguishing system may be used.
4. Must be installed using components specified by the manufacturer or components that are listed as equal parts by a nationally recognized testing laboratory such as Underwriters Laboratories, Inc., or Factory Mutual Laboratories, Inc.
5. Must be listed by a nationally recognized testing laboratory.
(b) Preengineered systems consist of and include all of the components and parts providing fire suppression protection, but do not include the equipment being protected, and may incorporate special nozzles, flow rates, methods of application, pressurization levels, and quantities of agents designed by the manufacturer for specific hazards.
(26) “Private carrier” means a motor vehicle, aircraft, or vessel operating intrastate in which there is identity of ownership between freight and carrier.
(27) “Sale” means the act of selling; the act whereby the ownership of property is transferred from one person to another for a sum of money or, loosely, for any consideration. The term includes the delivery of merchandise with or without consideration.
(28) “Sprinkler system” means a type of fire protection system, manual or automatic, using water as an extinguishing agent and installed in accordance with applicable National Fire Protection Association standards.
(29) “Storing” means accumulating, laying away, or depositing for preservation or as a reserve fund in a store, warehouse, or other source from which supplies may be drawn or within which they may be deposited. The term is limited in meaning and application to storage having a direct relationship to transportation.
(30) “Support services” means those activities that a fire service provider has trained an individual to perform safely outside the hot zone of an emergency scene, including pulling hoses, opening and closing fire hydrants, driving and operating apparatus, carrying tools, carrying or moving equipment, directing traffic, manning a resource pool, or similar activities.
(31) “Suspension” means the temporary withdrawal of a license, certificate, or permit issued pursuant to this chapter.
(32) “Transportation” means the conveying or carrying of property from one place to another by motor vehicle (except a motor vehicle subject to s. 316.302), aircraft, or vessel, subject to such limitations as are set forth in s. 552.12, in which only the motor vehicles, aircraft, or vessels of the Armed Forces and other federal agencies are specifically exempted.
(33) “Uniform firesafety standard” means a requirement or group of requirements for the protection of life and property from loss by fire which shall be met by every building and structure specified in s. 633.206, and is not weakened or exceeded by law, rule, or ordinance of any other state agency or political subdivision or county, municipality, or special district with firesafety responsibilities.
(34) “Use” means application, employment; that enjoyment of property which consists of its employment, occupation, exercise, or practice.
(35) “Volunteer firefighter” means an individual who holds a current and valid Volunteer Firefighter Certificate of Completion issued by the division under s. 633.408.
History.s. 2, ch. 65-216; s. 6, ch. 71-271; s. 2, ch. 75-240; s. 1, ch. 80-342; s. 27, ch. 82-186; s. 1, ch. 84-107; s. 1, ch. 84-143; s. 1, ch. 84-243; s. 34, ch. 86-191; s. 4, ch. 87-287; s. 2, ch. 88-209; s. 2, ch. 88-362; s. 14, ch. 89-233; s. 1, ch. 91-189; s. 43, ch. 95-210; s. 6, ch. 95-379; s. 1, ch. 98-170; s. 52, ch. 98-419; s. 44, ch. 2000-372; s. 2, ch. 2001-64; s. 22, ch. 2005-147; s. 8, ch. 2006-65; s. 46, ch. 2010-176; s. 2, ch. 2011-79; s. 2, ch. 2013-183; s. 156, ch. 2014-17; s. 19, ch. 2016-132; s. 23, ch. 2021-113; s. 1, ch. 2021-123; s. 2, ch. 2023-224.
Note.Former s. 633.021.
633.104 State Fire Marshal; authority; duties; rules.
(1) The Chief Financial Officer is designated as “State Fire Marshal.” The State Fire Marshal has authority to adopt rules pursuant to ss. 120.536(1) and 120.54 to implement this chapter. Rules must be in substantial conformity with generally accepted standards of firesafety; must take into consideration the direct supervision of children in nonresidential child care facilities; and must balance and temper the need of the State Fire Marshal to protect all Floridians from fire hazards with the social and economic inconveniences that may be caused or created by the rules. The department shall adopt the Florida Fire Prevention Code.
(2) Subject to the limitations of subsection (1), it is the intent of the Legislature that the State Fire Marshal shall have the responsibility to minimize the loss of life and property in this state due to fire. The State Fire Marshal shall enforce all laws and provisions of this chapter, and any rules adopted pursuant thereto, relating to:
(a) The prevention of fire and explosion through the regulation of conditions which could cause fire or explosion, the spread of fire, and panic resulting therefrom;
(b) Installation and maintenance of fire alarm systems and fire protection systems, including fire suppression systems, fire-extinguishing equipment, and fire sprinkler systems;
(c)1. Servicing, repairing, recharging, testing, marking, inspecting, installing, maintaining, and tagging of fire extinguishers, preengineered systems, and individually designed fire protection systems;
2. The training and licensing of persons engaged in the business of servicing, repairing, recharging, testing, marking, inspecting, installing, maintaining, and tagging fire extinguishers, preengineered systems, and individually designed fire protection systems;
(d) The maintenance of fire cause and loss records; and
(e) Suppression of arson and the investigation of the cause, origin, and circumstances of fire.
(3) The State Fire Marshal shall establish by rule guidelines and procedures for quadrennial renewal of firesafety inspector requirements for certification.
(4) It is the intent of the Legislature that the rules promulgated by the State Fire Marshal pursuant to this section be enforced in such a manner as to prohibit the displacement of currently placed mobile homes unless there is a threat of imminent danger to the health, safety, or welfare of the general public.
(5) It is the intent of the Legislature that there are to be no conflicting requirements between the Florida Fire Prevention Code and the Florida Building Code or conflicts in their enforcement and interpretation. Potential conflicts shall be resolved through coordination and cooperation of the State Fire Marshal and the Florida Building Commission as provided by this chapter and part IV of chapter 553.
(6) Only the State Fire Marshal may issue, and, when requested in writing by any substantially affected person or a local enforcing agency, the State Fire Marshal shall issue declaratory statements pursuant to s. 120.565 relating to the Florida Fire Prevention Code.
(7) The State Fire Marshal, in consultation with the Department of Education, shall adopt and administer rules prescribing standards for the safety and health of occupants of educational and ancillary facilities pursuant to ss. 633.206, 1013.12, 1013.37, and 1013.371. In addition, in any county, municipality, or special district that does not employ or appoint a firesafety inspector certified under s. 633.216, the State Fire Marshal shall assume the duties of the local county, municipality, or independent special fire control district as defined in s. 191.003 with respect to firesafety inspections of educational property required under s. 1013.12(3)(b), and the State Fire Marshal may take necessary corrective action as authorized under s. 1013.12(7).
(8) The State Fire Marshal or her or his duly appointed hearing officer may administer oaths and take testimony about all matters within the jurisdiction of this chapter. Chapter 120 governs hearings conducted by or on behalf of the State Fire Marshal.
(9) The State Fire Marshal may contract with any qualified public entity or private company in accordance with chapter 287 to provide examinations for any applicant for any examination administered under the jurisdiction of the State Fire Marshal. The State Fire Marshal may direct payments from each applicant for each examination directly to such contracted entity or company.
History.s. 1, ch. 20671, 1941; s. 1, ch. 65-216; s. 1, ch. 67-78; ss. 13, 35, ch. 69-106; s. 3, ch. 70-299; s. 5, ch. 71-271; s. 3, ch. 87-287; s. 13, ch. 89-233; s. 1, ch. 90-359; s. 5, ch. 95-379; s. 207, ch. 98-200; s. 57, ch. 98-287; ss. 100, 101, ch. 2000-141; s. 2, ch. 2002-287; s. 93, ch. 2003-1; s. 1391, ch. 2003-261; s. 61, ch. 2007-217; s. 156, ch. 2008-4; s. 1, ch. 2011-79; s. 3, ch. 2013-183.
Note.Former s. 633.01.
633.106 State Fire Marshal; disciplinary authority; administrative fine and probation in lieu of suspension, revocation, or refusal to issue a license, permit, or certificate.
(1) The State Fire Marshal may deny, suspend, or revoke the license, certificate, or permit of any individual who does not meet the qualifications established by, or who violates any provision under, this chapter or any rule authorized by this chapter.
(2) If the State Fire Marshal finds that one or more grounds exist for the suspension, revocation, or refusal to issue, renew, or continue any license, certificate, or permit issued under this chapter, the State Fire Marshal may, in its discretion, in lieu of the suspension, revocation, or refusal to issue, renew, or continue, and, except on a second offense or when the suspension, revocation, or refusal to issue, renew, or continue is mandatory, impose upon the licensee, certificateholder, or permittee one or more of the following:
(a) An administrative fine not to exceed $1,000 for each violation, and not to exceed a total of $10,000 in any one proceeding.
(b) Probation for a period not to exceed 2 years, as specified by the State Fire Marshal in her or his order.
(3) The State Fire Marshal may allow the licensee, certificateholder, or permittee a reasonable period, not to exceed 30 days, within which to pay to the State Fire Marshal the amount of the fine. If the licensee, certificateholder, or permittee fails to pay the administrative fine in its entirety to the State Fire Marshal within such period, the license, permit, or certificate shall stand suspended until payment of the administrative fine.
(4) As a condition to probation or in connection therewith, the State Fire Marshal may specify in her or his order reasonable terms and conditions to be fulfilled by the probationer during the probation period. If during the probation period the State Fire Marshal has good cause to believe that the probationer has violated any of the terms and conditions, she or he shall suspend, revoke, or refuse to issue, renew, or continue the license, certificate, or permit of the probationer, as upon the original ground or grounds referred to in subsection (2).
History.s. 5, ch. 71-141; s. 21, ch. 78-95; s. 9, ch. 84-243; s. 21, ch. 89-233; s. 8, ch. 93-276; s. 4, ch. 2013-183.
Note.Former s. 633.163.
633.107 Exemption from disqualification from licensure or certification.
(1) The department may grant an exemption from disqualification to any person disqualified from licensure or certification by the Division of State Fire Marshal under this chapter because of a criminal record or dishonorable discharge from the United States Armed Forces if the applicant has paid in full any fee, fine, fund, lien, civil judgment, restitution, cost of prosecution, or trust contribution imposed by the court as part of the judgment and sentence for any disqualifying offense and:
(a) At least 5 years have elapsed since the applicant completed or has been lawfully released from confinement, supervision, or nonmonetary condition imposed by the court for a disqualifying offense; or
(b) At least 5 years have elapsed since the applicant was dishonorably discharged from the United States Armed Forces.
(2) For the department to grant an exemption, the applicant must clearly and convincingly demonstrate that he or she would not pose a risk to persons or property if permitted to be licensed or certified under this chapter, evidence of which must include, but need not be limited to, facts and circumstances surrounding the disqualifying offense, the time that has elapsed since the offense, the nature of the offense and harm caused to the victim, the applicant’s history before and after the offense, and any other evidence or circumstances indicating that the applicant will not present a danger if permitted to be licensed or certified.
(3) The department has discretion whether to grant or deny an exemption. The department shall provide its decision in writing which, if the exemption is denied, must state with particularity the reasons for denial. The department’s decision is subject to proceedings under chapter 120, except that a formal proceeding under s. 120.57(1) is available only if there are disputed issues of material fact that the department relied upon in reaching its decision.
(4) An applicant may request an exemption, notwithstanding the time limitations of paragraphs (1)(a) and (b), if by executive clemency his or her civil rights are restored, or he or she receives a pardon, from the disqualifying offense. The fact that the applicant receives executive clemency does not alleviate his or her obligation to comply with subsection (2) or in itself require the department to award the exemption.
(5) The division may adopt rules to administer this section.
History.s. 20, ch. 2016-132.
633.108 State Fire Marshal; chapter and rules; force and effect.This chapter and all rules promulgated by the State Fire Marshal hereunder shall have the same force and effect in each municipality, county, and special district having firesafety responsibilities as the ordinances of each municipality, county, and special district having firesafety responsibilities and shall be enforceable in the courts in the same manner as such ordinances.
History.s. 1, ch. 21847, 1943; ss. 13, 35, ch. 69-106; s. 3, ch. 70-299; s. 1, ch. 77-119; s. 10, ch. 87-287; s. 5, ch. 2013-183.
Note.Former s. 633.15.
633.112 State Fire Marshal; hearings; investigations; recordkeeping and reports; subpoenas of witnesses; orders of circuit court.
(1) The State Fire Marshal may in his or her discretion take or cause to be taken the testimony on oath of a person whom he or she believes to be cognizant of any facts in relation to matters under investigation.
(2) If the State Fire Marshal is of the opinion that there is sufficient evidence to charge a person with an offense, he or she must cause the arrest of such person and must furnish to the prosecuting officer of any court having jurisdiction of the offense all information obtained by him or her, including a copy of all pertinent and material testimony taken, together with the names and addresses of all witnesses. In the conduct of such investigations, the State Fire Marshal may request such assistance as may reasonably be given by such prosecuting officers and other local officials.
(3) The State Fire Marshal may summon and compel the attendance of witnesses before him or her to testify in relation to any matter which is, by this chapter, a subject of inquiry and investigation, and he or she may require the production of any book, paper, or document deemed pertinent thereto by him or her, and may seize furniture and other personal property to be held for evidence.
(4) A person so summoned and so testifying shall be entitled to the same witness fees and mileage as provided for witnesses testifying in the circuit courts of this state, and officers serving subpoenas or orders of the State Fire Marshal shall be paid in like manner for like services in such courts, from the funds herein provided.
(5) Any agent designated by the State Fire Marshal for such purposes may hold hearings, sign and issue subpoenas, administer oaths, examine witnesses, receive evidence, and require by subpoena the attendance and testimony of witnesses and the production of such accounts, records, memoranda, or other evidence, as may be material for the determination of any complaint or conducting any inquiry or investigation under this chapter. In the case of disobedience to a subpoena, the State Fire Marshal or her or his agent may invoke the aid of any court of competent jurisdiction in requiring the attendance and testimony of witnesses and the production of accounts, records, memoranda, or other evidence and any such court may in case of refusal to obey a subpoena issued to a person, issue an order requiring the person to appear before the State Fire Marshal’s agent or produce accounts, records, memoranda, or other evidence, as so ordered, or to give evidence touching any matter pertinent to any complaint or the subject of any inquiry or investigation, and any failure to obey such order of the court shall be punished by the court as contempt.
(6) Upon request, the State Fire Marshal shall investigate the cause, origin, and circumstances of fires and explosions occurring in this state wherein property has been damaged or destroyed and there is probable cause to believe that the fire or explosion was the result of carelessness or design.
(a) Any time a fire or explosion has occurred which results in property damage or destruction in any municipality, county, or special district having an organized fire department, any local fire official whose intent is to request the State Fire Marshal to perform an investigation shall make or shall cause to be made an initial investigation of the circumstances surrounding the cause and origin of the fire or explosion. Law enforcement officers may conduct such initial investigation.
(b) If the fire or explosion occurs in a municipality, county, or special district that does not have an organized fire department or designated arson investigations unit within its law enforcement providers, the municipality, county, or special district may request the State Fire Marshal to conduct the initial investigation.
(c) The State Fire Marshal shall adopt rules to assist local fire officials and law enforcement officers in determining the established responsibilities with respect to the initial or preliminary assessment of fire and explosion scenes, and the determination of whether probable cause exists to refer such scenes to the State Fire Marshal for an investigation.
(7) The State Fire Marshal shall keep a record of all fires and explosions occurring in this state upon which she or he had caused an investigation to be made and all facts concerning the same. These records, obtained or prepared by the State Fire Marshal pursuant to her or his investigation, include documents, papers, letters, maps, diagrams, tapes, photographs, films, sound recordings, and evidence. These records are confidential and exempt from the provisions of s. 119.07(1) until the investigation is completed or ceases to be active. For purposes of this section, an investigation is considered “active” while such investigation is being conducted by the department with a reasonable, good faith belief that it may lead to the filing of administrative, civil, or criminal proceedings. An investigation does not cease to be active if the department is proceeding with reasonable dispatch, and there is a good faith belief that action may be initiated by the department or other administrative or law enforcement agency. Further, these documents, papers, letters, maps, diagrams, tapes, photographs, films, sound recordings, and evidence relative to the subject of an investigation shall not be subject to subpoena until the investigation is completed or ceases to be active, unless the State Fire Marshal consents. These records shall be made daily from the reports furnished the State Fire Marshal by her or his agents or others.
(8) Whenever the State Fire Marshal releases an investigative report, any person requesting a copy of the report shall pay in advance, and the State Fire Marshal shall collect in advance, notwithstanding the provisions of s. 624.501(19)(a) and (b), a fee of $10 for the copy of the report, which fee shall be deposited into the Insurance Regulatory Trust Fund. The State Fire Marshal may release the report without charge to any state attorney or to any law enforcement agency or fire department assisting in the investigation.
History.ss. 7, 8, ch. 20671, 1941; s. 9, ch. 65-216; s. 4, ch. 67-78; ss. 13, 35, ch. 69-106; s. 3, ch. 70-299; s. 1, ch. 78-149; s. 2, ch. 85-323; s. 202, ch. 90-363; s. 1, ch. 93-112; s. 6, ch. 93-276; s. 13, ch. 95-379; s. 391, ch. 96-406; ss. 426, 1742, ch. 97-102; s. 99, ch. 2002-1; s. 1397, ch. 2003-261; ss. 6, 7, ch. 2013-183; s. 30, ch. 2016-165.
Note.Former s. 633.08; s. 633.09; s. 633.101; s. 633.111.
633.114 State Fire Marshal agents; authority; duties; compensation.
(1) The State Fire Marshal shall appoint such agents, including agents of the Division of Investigative and Forensic Services, as may be necessary to carry out effectively this chapter, who shall be reimbursed for travel expenses as provided in s. 112.061, in addition to their salary, when traveling or making investigations in the performance of their duties. Such agents, including agents of the Division of Investigative and Forensic Services, shall be at all times under the direction and control of the State Fire Marshal, who shall fix their compensation, and all orders shall be issued in the State Fire Marshal’s name and by her or his authority.
(2) The authority given the State Fire Marshal under this chapter may be exercised by her or his agents, individually or in conjunction with any other state or local official charged with similar responsibilities.
History.s. 2, ch. 20671, 1941; s. 1, ch. 57-102; s. 19, ch. 63-400; s. 4, ch. 67-78; ss. 13, 35, ch. 69-106; s. 3, ch. 70-299; s. 421, ch. 97-102; s. 8, ch. 2013-183; s. 31, ch. 2016-165.
Note.Former s. 633.02.
633.116 Agents; powers to make arrests, conduct searches and seizures, serve summonses, and carry firearms.Agents of the State Fire Marshal shall have the same authority to serve summonses, make arrests, carry firearms, and make searches and seizures, as the sheriff or her or his deputies, in the respective counties where such investigations, hearings, or inspections may be held; and affidavits necessary to authorize any such arrests, searches, or seizures may be made before any trial court judge having authority under the law to issue appropriate processes.
History.s. 1, ch. 21847, 1943; ss. 13, 35, ch. 69-106; s. 3, ch. 70-299; s. 428, ch. 97-102; s. 12, ch. 2004-11; s. 9, ch. 2013-183.
Note.Former s. 633.14.
633.118 Persons authorized to enforce laws and rules of State Fire Marshal.The chiefs of county, municipal, and special-district fire service providers; other fire service provider personnel designated by their respective chiefs; and personnel designated by local governments having no organized fire service providers are authorized to enforce this chapter and all rules prescribed by the State Fire Marshal within their respective jurisdictions. Such personnel acting under the authority of this section shall be agents of their respective jurisdictions, not agents of the State Fire Marshal.
History.s. 9, ch. 20671, 1941; s. 9, ch. 65-216; s. 4, ch. 67-78; ss. 13, 35, ch. 69-106; s. 3, ch. 70-299; s. 5, ch. 76-252; s. 1, ch. 80-215; s. 10, ch. 2013-183.
Note.Former s. 633.11; s. 633.121.
633.122 Impersonating State Fire Marshal, firefighter, volunteer firefighter, or firesafety inspector; criminal penalties.A person who falsely assumes or pretends to be the State Fire Marshal, an agent of the State Fire Marshal, a firefighter, a volunteer firefighter, or a firesafety inspector by identifying herself or himself as the State Fire Marshal, an agent of the State Fire Marshal, a firefighter, a volunteer firefighter, or a firesafety inspector by wearing a uniform or presenting or displaying a badge as credentials that would cause a reasonable person to believe that she or he is a State Fire Marshal, an agent of the State Fire Marshal, a firefighter, a volunteer firefighter, or firesafety inspector commits a felony of the third degree, punishable as provided in ss. 775.082 and 775.083 or, if the impersonation occurs during the commission of a separate felony by that person, commits a felony of the first degree, punishable as provided in ss. 775.082 and 775.083.
History.s. 5, ch. 90-359; s. 429, ch. 97-102; s. 11, ch. 2013-183; s. 32, ch. 2016-165.
Note.Former s. 633.151.
633.124 Penalty for violation of law, rule, or order to cease and desist or for failure to comply with corrective order.
(1) A person who violates any provision of this chapter, any order or rule of the State Fire Marshal, or any order to cease and desist or to correct conditions issued under this chapter commits a misdemeanor of the second degree, punishable as provided in s. 775.082 or s. 775.083.
(2) It is a misdemeanor of the first degree, punishable as provided in s. 775.082 or s. 775.083, to intentionally or willfully:
(a) Render a fire protection system, fire extinguisher, or preengineered system required by statute or by rule inoperative except while the fire protection system, fire extinguisher, or preengineered system is being serviced, hydrotested, tested, repaired, or recharged, except pursuant to court order.
(b) Obliterate the serial number on a fire extinguisher for purposes of falsifying service records.
(c) Improperly service, recharge, repair, hydrotest, test, or inspect a fire extinguisher or preengineered system.
(d) Use the license, certificate, or permit of another person.
(e) Hold a license, certificate, or permit and allow another person to use the license, certificate, or permit.
(f) Use, or allow the use of, any license, certificate, or permit by any individual or organization other than the one to whom the license, certificate, or permit is issued.
(3)(a) As used in this subsection, the term:
1. “Pyrotechnic display” means a special effect created through the use of a pyrotechnic material or pyrotechnic device.
2. “Pyrotechnic device” means any device containing pyrotechnic materials and capable of producing a special effect.
3. “Pyrotechnic material” means a chemical mixture used to produce visible or audible effects by combustion, deflagration, or detonation when such chemical mixture consists predominantly of solids capable of producing a controlled, self-sustaining, and self-contained exothermic chemical reaction that results in heat, gas, sound, light, or a combination of such effects, without requiring external oxygen.
(b) A person who initiates a pyrotechnic display within any structure commits a felony of the third degree, punishable as provided in s. 775.082, s. 775.083, or s. 775.084, unless:
1. The structure has a fire protection system installed in compliance with s. 633.334.
2. The owner of the structure has authorized in writing the pyrotechnic display.
3. If the local jurisdiction requires a permit for the use of a pyrotechnic display in an occupied structure, such permit has been obtained and all conditions of the permit complied with or, if the local jurisdiction does not require a permit for the use of a pyrotechnic display in an occupied structure, the person initiating the display has complied with National Fire Protection Association, Inc., Standard 1126, 2021 Edition, Standard for the Use of Pyrotechnics before a Proximate Audience.
(c) This subsection shall not be construed to preclude prosecution for a more general offense resulting from the same criminal transaction or episode. This subsection does not apply to the manufacture, distribution, sale at wholesale or retail, or seasonal sale of products regulated under chapter 791 if the products are not used in an occupied structure.
History.s. 1, ch. 21847, 1943; s. 11, ch. 65-216; ss. 13, 35, ch. 69-106; s. 659, ch. 71-136; s. 7A, ch. 71-141; s. 3, ch. 78-141; s. 13, ch. 87-287; s. 22, ch. 89-233; s. 157, ch. 91-224; s. 6, ch. 98-170; s. 57, ch. 98-419; s. 3, ch. 2005-117; s. 12, ch. 2013-183; s. 26, ch. 2024-140.
Note.Former s. 633.16; s. 633.171.
633.126 Investigation of fraudulent insurance claims and crimes; immunity of insurance companies supplying information.
(1)(a) As used in this section, the term “consultant” means any individual or entity, or employee of the individual or entity, retained by an insurer to assist in the investigation of a fire, explosion, or suspected fraudulent insurance act.
(b) The State Fire Marshal or an agent appointed pursuant to s. 633.114, an agent of the Division of Investigative and Forensic Services, any law enforcement officer as defined in s. 111.065, any law enforcement officer of a federal agency, or any fire service provider official who is engaged in the investigation of a fire or explosion loss may request any insurance company or its agent, adjuster, employee, or attorney, investigating a claim under an insurance policy or contract with respect to a fire or explosion to release any information whatsoever in the possession of the insurance company or its agent, adjuster, employee, or attorney relative to a loss from that fire or explosion. The insurance company shall release the available information to and cooperate with any official authorized to request such information pursuant to this section. The information shall include, but shall not be limited to:
1. Any insurance policy relevant to a loss under investigation and any application for such a policy.
2. Any policy premium payment records.
3. The records, reports, and all material pertaining to any previous claims made by the insured with the reporting company.
4. Material relating to the investigation of the loss, including statements of a person, proof of loss, and other relevant evidence.
5. Memoranda, notes, and correspondence relating to the investigation of the loss in the possession of the insurance company or its agents, adjusters, employees, or attorneys.
(2) If an insurance company has reason to suspect that a fire or explosion loss to its insured’s real or personal property was caused by intentional means, the company shall notify the State Fire Marshal and shall furnish her or him with all material acquired by the company during its investigation. The State Fire Marshal may adopt rules to implement this subsection.
(3) In the absence of fraud, bad faith, or malice, a representative of or consultant to an insurance company or of the National Insurance Crime Bureau employed to adjust or investigate losses caused by fire or explosion is not liable for damages in a civil action for furnishing information concerning fires or explosions suspected to be other than accidental to investigators employed by other insurance companies or the National Insurance Crime Bureau.
(4) No insurance company or person who furnishes information on its behalf shall be liable for damages in a civil action or subject to criminal prosecution for any oral or written statement made or any other action taken that is necessary and required by the provisions of this section.
(5) At such time as the release of the investigative records is required by law, the official or agency in possession of such records shall provide written notice to the insurance company providing the information and to all parties, at least 10 days prior to releasing such records. Official, departmental, or agency personnel may discuss such matters with other official, departmental, or agency personnel, and any insurance company complying with this section, and may share such information, if such discussion is necessary to enable the orderly and efficient conduct of the investigation. These discussions are confidential and exempt from the provisions of s. 286.011.
(6) The actions of an insurance company or of its agents, employees, adjusters, consultants, or attorneys, in complying with the statutory obligation of this section may not be construed by a court as a waiver or abandonment of any privilege or confidentiality of attorney work product, attorney-client communication, or such other privilege or immunity as is provided by law.
(7) Any official described in subsection (1) may be required to testify as to any information in her or his possession regarding an insurance loss in any civil action in which any person seeks recovery under a policy against an insurance company for an insurance loss, subject to the provisions of subsection (6).
(8) No person may intentionally refuse to release any information requested pursuant to this section.
(9) If an insurance company fails or otherwise refuses to comply with this section, the department may impose an administrative fine of not more than $2,000 per day for such failure until the department deems the insurance company to be in compliance.
(10) The Division of Investigative and Forensic Services may adopt reasonable rules as are necessary to administer this section. Such rules must meet all of the following requirements:
(a) They may not enlarge upon or extend the provisions of this section.
(b) They must identify specific factors that determine the grades of penalty.
(c) They must specify mitigating and aggravating factors for a violation of this section.
History.s. 2, ch. 78-149; s. 1, ch. 83-96; s. 3, ch. 88-222; s. 158, ch. 91-224; s. 2, ch. 93-112; s. 15, ch. 95-379; s. 392, ch. 96-406; s. 1744, ch. 97-102; s. 3, ch. 97-124; s. 13, ch. 2013-183; s. 33, ch. 2016-165; s. 4, ch. 2022-169.
Note.Former s. 633.175.
633.128 Division of State Fire Marshal; powers, duties.
(1) The division shall:
(a) Establish, by rule, uniform minimum standards for the training of firefighters and volunteer firefighters.
(b) Establish, by rule, minimum curriculum requirements and criteria used to approve education or training providers, including schools operated by or for any fire service provider, for the specific purpose of training individuals seeking to become a firefighter or volunteer firefighter.
(c) Specify, by rule, standards for the approval, denial of approval, probation, suspension, and revocation of approval of education or training providers and facilities for training firefighters and volunteer firefighters.
(d) Specify, by rule, standards for the certification, denial of certification, probation, and revocation of certification for instructors, including a rule requiring each instructor to complete 40 hours of continuing education every 4 years in order to maintain her or his certification.
(e) Issue certificates of competency to persons who, by reason of experience and completion of basic inservice training, advanced education, or specialized training, are especially qualified for particular aspects or classes of firefighting duties.
(f) Establish, by rule, minimum training qualifications for persons serving as firesafety coordinators for their respective departments of state government and certify persons who satisfy such qualifications.
(g) Establish a uniform lesson plan to be followed by firesafety instructors in the training of state employees in firesafety and emergency evacuation procedures.
(h) Have complete jurisdiction over, and complete management and control of, the Florida State Fire College and be invested with full power and authority to make all rules necessary for the governance of the institution.
(i) Appoint a superintendent of the Florida State Fire College and such other instructors, experimental helpers, and laborers as may be necessary and remove the same as in the division’s judgment and discretion may be best, fix their compensation, and provide for their payment.
(j) Have full management, possession, and control of the lands, buildings, structures, and property belonging to the Florida State Fire College.
(k) Provide for the courses of study and curriculum of the Florida State Fire College.
(l) Make rules for the admission of trainees to the Florida State Fire College.
(m) Visit and inspect the Florida State Fire College and provide for the proper keeping of accounts and records thereof.
(n) Make and prepare all necessary budgets of expenditures for the enlargement, proper furnishing, maintenance, support, and conduct of the Florida State Fire College.
(o) Select and purchase all property, furniture, fixtures, and paraphernalia necessary for the Florida State Fire College.
(p) Build, construct, change, enlarge, repair, and maintain any and all buildings or structures of the Florida State Fire College that may at any time be necessary for the institution and purchase and acquire all lands and property necessary for same, of every nature and description whatsoever.
(q) Care for and maintain the Florida State Fire College and do and perform every other matter or thing requisite to the proper management, maintenance, support, and control of the institution, necessary or requisite to carry out fully the purpose of this chapter and for raising it to, and maintaining it at, the proper efficiency and standard as required in and by part IV.
(r) Issue a license, certificate, or permit of a specific class to an individual who successfully completes the training, education, and examination required under this chapter or by rule for such class of license, certificate, or permit.
(2) The division, subject to the limitations and restrictions imposed in this chapter, may:
(a) Adopt rules for the administration of this chapter pursuant to chapter 120.
(b) Adopt a seal and alter the same at its pleasure.
(c) Sue and be sued.
(d) Acquire any real or personal property by purchase, gift, or donation, and have water rights.
(e) Exercise the right of eminent domain to acquire any property and lands necessary to the establishment, operation, and expansion of the Florida State Fire College.
(f) Make contracts and execute necessary or convenient instruments.
(g) Undertake by contract or contracts, or by its own agent and employees, and otherwise than by contract, any project or projects, and operate and maintain such projects.
(h) Accept grants of money, materials, or property of any kind from a federal agency, private agency, county, municipality, corporation, partnership, or individual upon such terms and conditions as the grantor may impose.
(i) Perform all acts and do all things necessary or convenient to carry out the powers granted herein and the purposes of this chapter.
(3) The title to all property referred to in part IV, however acquired, shall be vested in the department and shall only be transferred and conveyed by it.
History.ss. 5, 9, ch. 25097, 1949; ss. 18, 35, ch. 69-106; ss. 1, 9, ch. 75-151; s. 1, ch. 77-174; s. 3, ch. 82-189; s. 27, ch. 89-233; s. 8, ch. 90-359; s. 12, ch. 99-205; s. 26, ch. 2000-157; s. 1406, ch. 2003-261; s. 14, ch. 2013-183.
Note.Former s. 163.534; s. 633.45.
633.132 Fees.
(1) The division shall collect in advance the following fees that it deems necessary to be charged:
(a) Pursuant to part III of this chapter:
1. Contractor certificate initial application: $300 for each class of certificate.
2. Contractor biennial renewal fee: $150 for each class of certificate.
3. Contractor permit initial application fee: $100 for each class of permit.
4. Contractor permit biennial renewal fee: $50 for each class of permit.
5. Contractor examination or reexamination fee: $100 for each class of certificate.
6. Fire equipment dealer license:
a. Class A: $250.
b. Class B: $150.
c. Class C: $150.
d. Class D: $200.
7. Fire equipment dealer or contractor application and renewal fee for an inactive license: $75.
8. Fire equipment dealer license or permit exam or reexamination: $50.
9. Reinspection fee for a dealer equipment inspection conducted by the State Fire Marshal under s. 633.304(1): $50 for each reinspection.
10. Permit for a portable fire extinguisher installer/repairer/inspector: $90.
11. Permit for a preengineered fire extinguishing system installer/repairer/inspector: $120.
12. Conversion of a fire equipment dealer’s license to a different category: $10 for each permit and license.
(b) Pursuant to part IV of this chapter:
1. Certificate of compliance: $30.
2. Certificate of competency: $30.
3. Renewal fee for a certificate of compliance, competency, or instruction: $15.
(c) Duplicate or change of address for any license, permit, or certificate: $10.
(2) All moneys collected by the State Fire Marshal pursuant to this chapter shall be deposited into the Insurance Regulatory Trust Fund.
History.s. 15, ch. 2013-183.
633.134 Gifts and grants.The division may accept for any of its purposes and functions any donations of property and grants of money from any governmental unit, public agency, institution, person, firm, or corporation. Such moneys shall be deposited, disbursed, and administered in a trust fund as provided by law.
History.ss. 13, 17, ch. 69-323; s. 1, ch. 70-110; ss. 1, 6, ch. 75-151; s. 16, ch. 2013-183.
Note.Former s. 163.515; s. 633.39.
633.135 Firefighter Assistance Grant Program.
(1) The Firefighter Assistance Grant Program is created within the division to improve the emergency response capability of volunteer fire departments and combination fire departments. The program shall provide financial assistance to improve firefighter safety and enable such fire departments to provide firefighting, emergency medical, and rescue services to their communities. For purposes of this section, the term “combination fire department” means a fire department composed of a combination of career and volunteer firefighters.
(2) The division shall administer the program and annually award grants to volunteer fire departments and combination fire departments using the annual Florida Fire Service Needs Assessment Survey. The purpose of the grants is to assist such fire departments in providing volunteer firefighter training and procuring necessary firefighter personal protective equipment, self-contained breathing apparatus equipment, and fire engine pumper apparatus equipment. However, the division shall prioritize the annual award of grants to combination fire departments and volunteer fire departments demonstrating need as a result of participating in the annual Florida Fire Service Needs Assessment Survey.
(3) The State Fire Marshal shall adopt rules and procedures for the program that require grant recipients to:
(a) Report their activity to the division for submission in the Fire and Emergency Incident Information Reporting System created pursuant to s. 633.136;
(b) Annually complete and submit the Florida Fire Service Needs Assessment Survey to the division;
(c) Comply with the Florida Firefighters Occupational Safety and Health Act, ss. 633.502-633.536;
(d) Comply with any other rule determined by the State Fire Marshal to effectively and efficiently implement, administer, and manage the program; and
(e) Meet the definition of the term “fire service provider” in s. 633.102.
(4) Funds shall be used to:
(a) Provide firefighter training to individuals to obtain a Volunteer Firefighter Certificate of Completion pursuant to s. 633.408. Training must be provided at no cost to the fire department or student by a division-approved instructor and must be documented in the division’s electronic database.
(b) Purchase firefighter personal protective equipment, including structural firefighting protective ensembles and individual ensemble elements such as garments, helmets, gloves, and footwear, that complies with NFPA No. 1851, “Standard on Selection, Care, and Maintenance of Protective Ensembles for Structural Fire Fighting and Proximity Fire Fighting,” by the National Fire Protection Association.
(c) Purchase self-contained breathing apparatus equipment that complies with NFPA No. 1852, “Standard on Selection, Care, and Maintenance of Open-Circuit Self-Contained Breathing Apparatus.”
(d) Purchase fire engine pumper apparatus equipment. Funds provided under this paragraph may be used to purchase the equipment or subsidize a federal grant from the Federal Emergency Management Agency to purchase the equipment.
(e) Purchase other equipment and tools that improve firesafety and fire rescue capabilities for firefighters.
(f) Purchase protective clothing and equipment compliant with NFPA 1977, “Standard on Protective Clothing and Equipment for Wildland Fire Fighting and Urban Interface Fire Fighting.”
History.s. 21, ch. 2016-132; s. 55, ch. 2022-138.
633.136 Fire and Emergency Incident Information Reporting Program; duties; fire reports.
(1)(a) The Fire and Emergency Incident Information Reporting Program is created within the division. The program shall:
1. Establish and maintain an electronic communication system capable of transmitting fire and emergency incident information to and between fire service providers.
2. Initiate a Fire and Emergency Incident Information Reporting System that is responsible for:
a. Receiving fire and emergency incident information from fire service providers.
b. Preparing and disseminating annual reports to the Governor, the President of the Senate, the Speaker of the House of Representatives, fire service providers, and, upon request, the public. Each report must include, but not be limited to, the information listed in the National Fire Incident Reporting System.
c. Upon request, providing other states and federal agencies with fire and emergency incident data of this state.
3. Adopt rules to effectively and efficiently implement, administer, manage, maintain, and use the Fire and Emergency Incident Information Reporting Program. The rules shall be considered minimum requirements and may not preclude a fire service provider from implementing its own requirements that may not conflict with the rules of the division.
4. By rule, establish procedures and a format for each fire service provider to voluntarily monitor its records and submit reports to the program.
5. Maintain an electronic information database that is accessible and searchable by fire service providers.
(b) The division shall consult with the Florida Forest Service of the Department of Agriculture and Consumer Services and the State Surgeon General of the Department of Health to coordinate data, ensure accuracy of the data, and limit duplication of efforts in data collection, analysis, and reporting.
(2) The Fire and Emergency Incident Information System Technical Advisory Panel is created within the division. The panel shall advise, review, and recommend to the State Fire Marshal with respect to the requirements of this section. The membership of the panel consists of the 15 members of the Firefighters Employment, Standards, and Training Council as established in s. 633.402.
(3) As used in this section, the term “fire service provider” has the same meaning as in s. 633.102.
History.s. 2, ch. 2005-117; s. 75, ch. 2012-7; s. 112, ch. 2012-184; s. 17, ch. 2013-183; s. 24, ch. 2021-113.
Note.Former s. 633.115.
633.137 Firefighter Cancer Decontamination Equipment Grant Program.
(1) The Firefighter Cancer Decontamination Equipment Grant Program is created within the division to help protect the health and safety of firefighters in this state. The program shall provide financial assistance to help fire departments, including volunteer fire departments, procure equipment, supplies, and educational training designed to mitigate exposure to hazardous, cancer-causing chemicals.
(2) The division shall administer the program and annually award grants to fire departments on a need-based basis. The division shall distribute equipment and training in a manner that leads to the greatest reduction in incidences of firefighters being exposed to hazardous postfire contaminants.
(3) The State Fire Marshal shall adopt rules and procedures for the program, including for the approval of applications and development of need-based criteria. These criteria shall include, but are not limited to, the decontamination equipment and supply needs of the fire department, the financial needs of the fire department, and the level of nonstate matching funds proposed in the application. Grant applications must include a minimum of 25 percent nonstate funding.
(4) Grant recipients must:
(a) Report their activity to the division for submission in the Fire and Emergency Incident Information Reporting System created under s. 633.136.
(b) Comply with the Florida Firefighters Occupational Safety and Health Act, ss. 633.502-633.536.
(c) Comply with any other rule determined by the State Fire Marshal to effectively and efficiently implement, administer, and manage the program.
History.s. 1, ch. 2020-96.
633.138 Notice of change of address of record; notice of felony actions.
(1) Any individual issued a license, permit, or certificate under this chapter shall notify the division in writing of any changes to her or his current mailing address, e-mail address, and place of practice as specified in rule adopted by the division.
(2) Notwithstanding any other provision of law, delivery by regular mail or e-mail to a licensee, permittee, or certificateholder, using the last known mailing address or e-mail address on record with the division, constitutes adequate and sufficient notice to the licensee, permittee, or certificateholder of any official communication by the division.
(3) Any individual issued a license, permit, or certificate under this chapter shall notify the division in writing within 30 days after pleading guilty or nolo contendere to, or being convicted or found guilty of, any felony or a crime punishable by imprisonment of 1 year or more under the law of the United States or of any state thereof, or under the law of any other country, without regard to whether a judgment of conviction has been entered by the court having jurisdiction of the case.
History.s. 18, ch. 2013-183.
633.142 Reduced Cigarette Ignition Propensity Standard and Firefighter Protection Act; preemption.
(1) SHORT TITLE.This section may be cited as the “Reduced Cigarette Ignition Propensity Standard and Firefighter Protection Act.”
(2) LEGISLATIVE FINDINGS AND INTENT.The Legislature finds and declares that:
(a) Cigarettes are the leading cause of fire deaths in this state and in the nation.
(b) Each year in the United States, between 700 and 900 persons are killed and around 3,000 persons are injured in fires ignited by cigarettes, while in this state 153 residential fires and 5 fatalities were attributable to fires caused by cigarettes in 2006.
(c) A high percentage of the victims of cigarette fires are nonsmokers, including senior citizens and young children.
(d) Fires caused by cigarettes result in billions of dollars in property losses and damages in the United States and millions of dollars in property losses and damages in this state.
(e) Cigarette fires unnecessarily jeopardize the safety of firefighters and result in avoidable emergency response costs for municipalities.
(f) In 2004, the State of New York implemented a cigarette firesafety regulation requiring cigarettes sold in that state to meet a firesafety performance standard; in 2005, Vermont and California enacted cigarette firesafety laws directly incorporating New York’s regulation into statute; and in 2006, Illinois, New Hampshire, and Massachusetts joined these states in enacting similar laws.
(g) In 2005, Canada implemented the New York State firesafety standard, becoming the first country to have a nationwide cigarette firesafety standard.
(h) New York State’s cigarette firesafety standard is based upon decades of research by the National Institute of Standards and Technology, Congressional research groups, and private industry. This cigarette firesafety standard minimizes costs to the state; minimally burdens cigarette manufacturers, distributors, and retail sellers; and, therefore, should become law in this state.
(i) It is therefore fitting and proper for this state to adopt the cigarette firesafety standard that is in effect in the State of New York to reduce the likelihood that cigarettes will cause fires and result in deaths, injuries, and property damages.
(3) DEFINITIONS.For the purposes of this section:
(a) “Agent” means any person authorized by the Division of Alcoholic Beverages and Tobacco of the Department of Business and Professional Regulation to purchase and affix stamps on packages of cigarettes.
(b) “Cigarette” means:
1. Any roll for smoking, whether made wholly or in part of tobacco or any other substance, irrespective of size or shape, and whether such tobacco or substance is flavored, adulterated, or mixed with any other ingredient, the wrapper or cover of which is made of paper or any other substance or material other than tobacco; or
2. Any roll for smoking that is wrapped in any substance containing tobacco and that, because of the type of tobacco used in the filler or its packaging and labeling, is likely to be offered to, or purchased by, consumers as a cigarette as described in subparagraph 1.
(c) “Division” means the Division of Alcoholic Beverages and Tobacco of the Department of Business and Professional Regulation.
(d) “Manufacturer” means:
1. Any entity that manufactures or produces, or causes to be manufactured or produced, regardless of location, cigarettes that such manufacturer intends to be sold in this state, including cigarettes intended to be sold in the United States through an importer;
2. Any entity, regardless of location, that first purchases cigarettes manufactured anywhere and not intended by the original manufacturer or maker to be sold in the United States and that intends to resell such cigarettes in the United States; or
3. Any entity that becomes a successor of an entity described in subparagraph 1. or subparagraph 2.
(e) “Quality control and quality assurance program” means laboratory procedures implemented to ensure that operator bias, systematic and nonsystematic methodological errors, and equipment-related problems do not affect the results of laboratory testing. Such a program shall ensure that the testing repeatability remains within the required repeatability values stated in subparagraph (4)(a)6. for all test trials used to certify cigarettes in accordance with this section.
(f) “Repeatability” means the range of values within which the results of repeated cigarette test trials from a single laboratory will fall 95 percent of the time.
(g) “Retail dealer” means:
1. Any person, other than a manufacturer or wholesale dealer, engaged in selling cigarettes; or
2. Any person who owns, operates, or maintains one or more cigarette or tobacco-product vending machines in, at, or upon premises owned or occupied by any other person.
(h) “Sale” means any transfer of title or possession or both, exchange or barter, conditional or otherwise, in any manner or by any means whatever or any agreement therefor. In addition to cash and credit sales, the giving of cigarettes as samples, prizes, or gifts and the exchanging of cigarettes for any consideration other than money are considered sales.
(i) “Sell” means to execute a sale or to offer or agree to execute a sale.
(j) “Wholesale dealer” means any person, other than a manufacturer, who sells cigarettes to retail dealers or other persons for purposes of resale.
(4) TEST METHOD AND PERFORMANCE STANDARD.
(a) Except as provided in paragraph (f), no cigarettes may be sold or offered for sale in this state, or sold or offered for sale to persons located in this state, unless the cigarettes have been tested in accordance with the test method and meet the performance standard specified in this subsection, a written certification has been filed by the manufacturer with the division in accordance with subsection (5), and the cigarettes have been marked in accordance with subsection (6).
1. Testing of cigarettes shall be conducted in accordance with the American Society for Testing and Materials standard E2187-04, “Standard Test Method for Measuring the Ignition Strength of Cigarettes.”
2. Testing shall be conducted on 10 layers of filter paper.
3. No more than 25 percent of the cigarettes tested in a test trial in accordance with this subsection shall exhibit full-length burns. Forty replicate tests shall comprise a complete test trial for each cigarette tested.
4. The performance standard required by this subsection shall only be applied to a complete test trial.
5. Written certifications shall be based upon testing conducted by a laboratory that has been accredited pursuant to standard ISO/IEC 17025 of the International Organization for Standardization or another comparable accreditation standard required by the State Fire Marshal.
6. Laboratories conducting testing in accordance with this subsection shall implement a quality control and quality assurance program that includes a procedure that will determine the repeatability of the testing results. The repeatability value shall be no greater than 0.19.
7. This subsection does not require additional testing if cigarettes are tested consistently with this section for any other purpose.
8. The State Fire Marshal may, in his or her discretion or upon the request of the division, perform or sponsor testing to determine a cigarette’s compliance with the required performance standard. Any such discretionary compliance testing by the State Fire Marshal shall be conducted in accordance with this subsection.
(b) Each cigarette listed in a certification submitted pursuant to subsection (5) that uses lowered permeability bands in the cigarette paper to achieve compliance with the performance standard set forth in this subsection shall have at least two nominally identical bands on the paper surrounding the tobacco column. At least one complete band shall be located at least 15 millimeters from the lighting end of the cigarette. For cigarettes on which the bands are positioned by design, there shall be at least two bands fully located at least 15 millimeters from the lighting end and 10 millimeters from the filter end of the tobacco column, or 10 millimeters from the labeled end of the tobacco column for nonfiltered cigarettes.
(c) A manufacturer of a cigarette that the State Fire Marshal determines cannot be tested in accordance with the test method prescribed in subparagraph (a)1. shall propose a test method and performance standard for the cigarette to the State Fire Marshal. Upon approval of the proposed test method and a determination by the State Fire Marshal that the performance standard proposed by the manufacturer is equivalent to the performance standard prescribed in subparagraph (a)3., the manufacturer may employ such test method and performance standard to certify such cigarette pursuant to subsection (5). If the State Fire Marshal determines that another state has enacted reduced cigarette ignition propensity standards that include a test method and performance standard that are the same as those contained in this section, and if the State Fire Marshal finds that the officials responsible for implementing those requirements have approved the proposed alternative test method and performance standard for a particular cigarette proposed by a manufacturer as meeting the firesafety standards of that state’s law or regulation under a legal provision comparable to this subsection, the State Fire Marshal shall authorize that manufacturer to employ the alternative test method and performance standard to certify that cigarette for sale in this state unless the State Fire Marshal demonstrates a reasonable basis why the alternative test should not be accepted under this section. All other applicable requirements of this subsection shall apply to the manufacturer.
(d) Each manufacturer shall maintain copies of the reports of all tests conducted on all cigarettes offered for sale for a period of 3 years and shall make copies of the reports available to the division, the State Fire Marshal, and the Attorney General upon written request. Any manufacturer who fails to make copies of the reports available within 60 days after receiving a written request shall be subject to a civil penalty not to exceed $10,000 for each day after the 60th day that the manufacturer does not make such copies available.
(e) The State Fire Marshal may adopt a subsequent American Society for Testing and Materials Standard Test Method for Measuring the Ignition Strength of Cigarettes upon a finding that such subsequent method does not result in a change in the percentage of full-length burns exhibited by any tested cigarette when compared to the percentage of full-length burns the same cigarette would exhibit when tested in accordance with American Society for Testing and Materials Standard E2187-04 and the performance standard in subparagraph (a)3.
(f) The requirements of paragraph (a) shall not prohibit:
1. Wholesale or retail dealers from selling their existing inventory of cigarettes on or after the effective date of this section if the wholesale or retail dealer can establish that state tax stamps were affixed to the cigarettes prior to the effective date and the wholesale or retail dealer can establish that the inventory was purchased prior to the effective date in comparable quantity to the inventory purchased during the same period of the prior year; or
2. The sale of cigarettes solely for the purpose of consumer testing. For purposes of this subparagraph, the term “consumer testing” means an assessment of cigarettes that is conducted by or is under the control and direction of a manufacturer for the purpose of evaluating consumer acceptance of such cigarettes and that uses only the quantity of cigarettes that is reasonably necessary for such assessment.
(g) It is the intent of the Legislature by this section to promote uniformity among the states in the regulation of reduced cigarette ignition propensity. As a result, the resolution of issues regarding the interpretation and implementation of this section should be made in a manner consistent with the New York Fire Safety Standards for Cigarettes, New York Executive Law, Section 156-C, as amended, and Part 429 of Title 19 New York Codes, Rules, and Regulations, as amended, and the interpretation and implementation thereof, as they exist on March 1, 2008.
(5) CERTIFICATION AND PRODUCT CHANGE.
(a) Each manufacturer shall submit to the division a written certification attesting that:
1. Each cigarette listed in the certification has been tested in accordance with subsection (4).
2. Each cigarette listed in the certification meets the performance standard set forth in subsection (4).
(b) Each cigarette listed in the certification shall be described with the following information:
1. Brand, or trade name, on the package.
2. Style, such as light or ultra light.
3. Length in millimeters.
4. Circumference in millimeters.
5. Flavor, such as menthol or chocolate, if applicable.
6. Filter or nonfilter.
7. Package description, such as soft pack or box.
8. Marking pursuant to subsection (6).
9. The name, address, and telephone number of the testing laboratory, if different from the name, address, and telephone number of the manufacturer that conducted the test.
10. The date the testing occurred.
(c) Each certification shall be made available to the Attorney General for purposes consistent with this section and to the State Fire Marshal for the purposes of ensuring compliance with this subsection.
(d) Each cigarette certified under this subsection shall be recertified every 3 years.
(e) If a manufacturer has certified a cigarette pursuant to this subsection and thereafter makes any change to such cigarette that is likely to alter its compliance with the reduced cigarette ignition propensity standards required by this section, that cigarette shall not be sold or offered for sale in this state until the manufacturer retests the cigarette in accordance with the testing standards set forth in subsection (4) and maintains records of that retesting as required by subsection (4). Any altered cigarette that does not meet the performance standard set forth in subsection (4) may not be sold in this state.
(6) MARKING OF CIGARETTE PACKAGING.
(a) Cigarettes that are certified by a manufacturer in accordance with subsection (5) shall be marked to indicate compliance with the requirements of subsection (4). The marking shall be in 8-point type or larger and consist of:
1. Modification of the universal product code to include a visible mark printed at or around the area of the universal product code. The mark may consist of alphanumeric or symbolic characters permanently stamped, engraved, embossed, or printed in conjunction with the universal product code;
2. Any visible combination of alphanumeric or symbolic characters permanently stamped, engraved, or embossed upon the cigarette package or cellophane wrap; or
3. Printed, stamped, engraved, or embossed text that indicates that the cigarettes meet the standards of this section.
(b) A manufacturer shall use only one marking and shall apply this marking uniformly for all brands and all packages, including, but not limited to, packs, cartons, and cases, marketed by that manufacturer.
(c) The division shall be notified as to the marking that is selected.
(d) Prior to the certification of any cigarette, a manufacturer shall present its proposed marking to the division for approval. Upon receipt of the request, the division shall approve or disapprove the marking offered, except that the division shall approve:
1. Any marking in use and approved for sale in the State of New York pursuant to the New York Fire Safety Standards for Cigarettes; or
2. The letters “FSC,” which signify “Fire Standards Compliant,” appearing in 8-point type or larger and permanently printed, stamped, engraved, or embossed on the package at or near the universal product code.

Proposed markings shall be deemed approved if the division fails to act within 10 business days after receiving a request for approval.

(e) No manufacturer shall modify its approved marking unless the modification has been approved by the division in accordance with this subsection.
(f) Manufacturers certifying cigarettes in accordance with subsection (5) shall provide a copy of the certifications to all wholesale dealers and agents to which they sell cigarettes and shall also provide sufficient copies of an illustration of the package marking used by the manufacturer pursuant to this subsection for each retail dealer to which the wholesale dealers or agents sell cigarettes. Wholesale dealers and agents shall provide a copy of these package markings received from manufacturers to all retail dealers to which they sell cigarettes. Wholesale dealers, agents, and retail dealers shall permit the division, the State Fire Marshal, the Attorney General, and their employees to inspect markings of cigarette packaging marked in accordance with this subsection.
(7) PENALTIES.
(a) A manufacturer, wholesale dealer, agent, or any other person or entity that knowingly sells or offers to sell cigarettes, other than through retail sale, in violation of subsection (4) shall be subject to a civil penalty not to exceed $100 for each pack of such cigarettes sold or offered for sale. In no case shall the penalty against any such person or entity exceed $100,000 during any 30-day period.
(b) A retail dealer who knowingly sells or offers to sell cigarettes in violation of subsection (4) shall be subject to a civil penalty not to exceed $100 for each pack of such cigarettes sold or offered for sale. In no case shall the penalty against any retail dealer exceed $25,000 during any 30-day period.
(c) In addition to any penalty prescribed by law, any corporation, partnership, sole proprietor, limited partnership, or association engaged in the manufacture of cigarettes that knowingly makes a false certification pursuant to subsection (5) shall be subject to a civil penalty of at least $75,000 and not to exceed $250,000 for each such false certification.
(d) Any person violating any other provision of this section shall be subject to a civil penalty not to exceed $1,000 for a first offense and not to exceed $5,000 for each subsequent offense.
(e) Any penalties collected under this subsection shall be deposited into the Insurance Regulatory Trust Fund of the Department of Financial Services to support costs associated with the responsibilities of the State Fire Marshal under this section.
(f) In addition to any other remedy provided by law, the division, the State Fire Marshal, or the Attorney General may file an action in circuit court for a violation of this section, including petitioning for injunctive relief or to recover any costs or damages suffered by the state because of a violation of this section, including enforcement costs relating to the specific violation and attorney’s fees. Each violation of this section or of rules adopted under this section constitutes a separate civil violation for which the division, the State Fire Marshal, or the Attorney General may obtain relief.
(g) Whenever any law enforcement personnel or duly authorized representative of the division discovers any cigarettes that have not been marked in the manner required by subsection (6), such personnel or representative is authorized and empowered to seize and take possession of such cigarettes. Such cigarettes shall be turned over to the division and shall be forfeited to the state. Cigarettes seized pursuant to this paragraph shall be destroyed; however, prior to the destruction of any such cigarette, the true holder of the trademark rights in the cigarette brand shall be permitted to inspect the cigarette.
(8) IMPLEMENTATION.
(a) The division and the State Fire Marshal may adopt rules to implement the provisions of this section.
(b) The division, in the regular course of conducting inspections of wholesale dealers, agents, and retail dealers as authorized pursuant to chapter 210, may inspect such cigarettes to determine if the cigarettes are marked as required by subsection (6).
(9) INSPECTION.To enforce the provisions of this section, the Attorney General, the State Fire Marshal, the division, and their duly authorized representatives and other law enforcement personnel are authorized to examine the books, papers, invoices, and other records of any person in possession, control, or occupancy of any premises where cigarettes are placed, stored, sold, or offered for sale, as well as the stock of cigarettes on the premises. Every person in the possession, control, or occupancy of any premises where cigarettes are placed, sold, or offered for sale is directed and required to give the Attorney General, the State Fire Marshal, the division, and their duly authorized representatives and other law enforcement personnel the means, facilities, and opportunity for the examinations authorized by this subsection.
(10) SALE OUTSIDE OF FLORIDA.Nothing in this section shall be construed to prohibit any person or entity from manufacturing or selling cigarettes that do not meet the requirements of subsection (4) if the cigarettes are or will be stamped for sale in another state or are packaged for sale outside the United States and that person or entity has taken reasonable steps to ensure that such cigarettes will not be sold or offered for sale to persons located in this state.
(11) PREEMPTION.
(a) This section shall be repealed if a federal reduced cigarette ignition propensity standard that preempts this section is adopted and becomes effective.
(b) Notwithstanding any other provision of law, local governmental units of this state may not enact or enforce any ordinance or other local law or rule conflicting with, or preempted by, any provision of this act or any policy of this state expressed by this act, whether that policy be expressed by inclusion of a provision in this act or by exclusion of that subject from this act.
History.s. 1, ch. 2008-129; s. 19, ch. 2013-183.
Note.Former s. 633.042.
633.1423 State Fire Marshal direct-support organization.
(1) DEFINITION.As used in this section, the term “organization” means the direct-support organization established under this section.
(2) ORGANIZATION ESTABLISHED.The division may establish a direct-support organization, to be known as the “State Fire Marshal Safety and Training Force,” whose sole purpose is to support the safety and training of firefighters and to recognize exemplary service. The organization must:
(a) Be a not-for-profit corporation incorporated under chapter 617 and approved by the Department of State.
(b) Be organized and operated to raise funds; request and receive grants, gifts, and bequests of money; conduct programs and activities; acquire, receive, hold, invest, and administer, in its own name, securities, funds, or property; and make grants and expenditures to or for the direct or indirect benefit of the division. Grants and expenditures may include the cost of education or training of firefighters, or the recognition of exemplary service of firefighters.
(c) Be determined by the division to operate in a manner that is:
1. Consistent with the goals of the division and laws relating to the safety and training of firefighters.
2. In the best interest of the state.
3. In accordance with the adopted goals and mission of the division.
(d) Use all of its grants and expenditures solely for the purpose of educating, training, and recognizing firefighters, and not for advertising using the likeness or name of any elected official nor for the purpose of lobbying as defined in s. 11.045(1).
(e) Be subject to an annual financial audit in accordance with s. 215.981.
(3) CONTRACT.The organization shall operate under written contract with the division. The contract must provide for:
(a) Certification by the division that the organization is complying with the terms of the contract and in a manner consistent with the goals and purposes of the department and in the best interest of the state. Such certification must be made annually and reported in the official minutes of a meeting of the organization.
(b) The reversion of moneys and property held by the organization for firefighter safety, training, and recognition to the division if the organization is no longer approved to operate by the division or if the organization ceases to exist, or to the state if the division ceases to exist.
(4) BOARD OF DIRECTORS.The organization shall be governed by a board of directors. The State Fire Marshal, or his or her designee, shall appoint a president of the board. The board of directors shall be appointed by the president of the board.
(5) USE OF PROPERTY.The division may authorize, without charge, appropriate use of fixed property and facilities of the division by the organization, subject to this subsection.
(a) The department may prescribe any condition with which the organization must comply in order to use the division’s property or facilities.
(b) The department may not authorize the use of the division’s property or facilities if the organization does not provide equal membership and employment opportunities to all persons regardless of race, religion, sex, age, or national origin.
(c) The department shall adopt rules prescribing the procedures by which the organization is governed and any conditions with which the organization must comply to use the division’s property or facilities.
(6) DEPOSITORY ACCOUNT.Any moneys received by the organization may be held in a separate depository account in the name of the organization and subject to the contract with the division.
(7) ANNUAL BUDGETS AND REPORTS.The organization shall submit to the division its annual budget and financial reports, its federal Internal Revenue Service Application for Recognition of Exemption Form 1023, and its federal Internal Revenue Service Return of Organization Exempt from Income Tax Form 990.
(8) ANNUAL AUDIT.The organization shall provide for an annual financial audit in accordance with s. 215.981.
(9) DIVISION’S RECEIPT OF PROCEEDS.Proceeds received by the division from the organization shall be deposited into the Insurance Regulatory Trust Fund.
(10) REPEAL.This section is repealed October 1, 2028, unless reviewed and saved from repeal by the Legislature.
History.s. 44, ch. 2023-144.
PART II
FIRE SAFETY AND PREVENTION
633.202 Florida Fire Prevention Code.
633.204 Florida Fire Code Advisory Council.
633.206 Uniform firesafety standards.
633.208 Minimum firesafety standards.
633.212 Legislative intent; informal interpretations of the Florida Fire Prevention Code.
633.214 Ordinances relating to firesafety; definitions; penalties.
633.216 Inspection of buildings and equipment; orders; firesafety inspection training requirements; certification; disciplinary action.
633.217 Influencing a firesafety inspector; prohibited acts.
633.218 Inspections of state buildings and premises; tests of firesafety equipment; building plans to be approved.
633.222 Buildings with light-frame truss-type construction; notice requirements; enforcement.
633.224 Automatic fire sprinkler systems for one-family dwellings, two-family dwellings, and mobile homes.
633.226 Exemptions; farm outbuildings; standpipe systems installed by plumbing contractors.
633.228 Violations; orders to cease and desist, correct hazardous conditions, preclude occupancy, or vacate; enforcement; penalties.
633.202 Florida Fire Prevention Code.
(1) The State Fire Marshal shall adopt, by rule pursuant to ss. 120.536(1) and 120.54, the Florida Fire Prevention Code which shall contain or incorporate by reference all firesafety laws and rules that pertain to and govern the design, construction, erection, alteration, modification, repair, and demolition of public and private buildings, structures, and facilities and the enforcement of such firesafety laws and rules. The State Fire Marshal shall adopt a new edition of the Florida Fire Prevention Code every third year.
(2) The State Fire Marshal shall adopt the current edition of the National Fire Protection Association’s Standard 1, Fire Prevention Code but may not adopt a building, mechanical, accessibility, or plumbing code. The State Fire Marshal shall adopt the current edition of the Life Safety Code, NFPA 101, current editions, by reference. The State Fire Marshal may modify the selected codes and standards as needed to accommodate the specific needs of the state. Standards or criteria in the selected codes shall be similarly incorporated by reference. The State Fire Marshal shall incorporate within sections of the Florida Fire Prevention Code provisions that address uniform firesafety standards as established in s. 633.206. The State Fire Marshal shall incorporate within sections of the Florida Fire Prevention Code provisions addressing regional and local concerns and variations.
(3) No later than 180 days before the triennial adoption of the Florida Fire Prevention Code, the State Fire Marshal shall notify each municipal, county, and special district fire department of the triennial code adoption and steps necessary for local amendments to be included within the code. No later than 120 days before the triennial adoption of the Florida Fire Prevention Code, each local jurisdiction shall provide the State Fire Marshal with copies of its local fire code amendments. The State Fire Marshal has the option to process local fire code amendments that are received less than 120 days before the adoption date of the Florida Fire Prevention Code.
(a) The State Fire Marshal shall review or cause the review of local amendments to determine:
1. If the local amendment should be adopted as a statewide provision;
2. That the local amendment does not provide a lesser degree of lifesafety than the code otherwise provides; and
3. That the local amendment does not reference a different edition of the national fire codes or other national standard than the edition provided or referenced in the uniform or minimum firesafety codes adopted by the State Fire Marshal or prescribed by statute.
(b) Any local amendment to the Florida Fire Prevention Code adopted by a local government shall be effective only until the adoption of the new edition of the Florida Fire Prevention Code, which shall be every third year. At such time, the State Fire Marshal shall adopt such amendment as part of the Florida Fire Prevention Code or rescind the amendment. The State Fire Marshal shall immediately notify the respective local government of the rescission of the amendment and the reason for the rescission. After receiving such notice, the respective local government may readopt the rescinded amendment. Incorporation of local amendments as regional and local concerns and variations shall be considered as adoption of an amendment pursuant to this section.
(4) The State Fire Marshal shall update, by rule adopted pursuant to ss. 120.536(1) and 120.54, the Florida Fire Prevention Code every 3 years. Once initially adopted and subsequently updated, the Florida Fire Prevention Code shall be adopted for use statewide without adoptions by local governments. When updating the Florida Fire Prevention Code, the State Fire Marshal shall consider changes made by the national model fire codes incorporated into the Florida Fire Prevention Code, the State Fire Marshal’s own interpretations, declaratory statements, appellate decisions, and approved statewide and local technical amendments.
(5) Upon the conclusion of a triennial update to the Florida Fire Prevention Code and notwithstanding any other provisions of law, the State Fire Marshal may address the issues identified in this subsection by amending the Florida Fire Prevention Code, subject only to the rule adoption procedures of chapter 120. Following the approval of any amendments to the Florida Fire Prevention Code by the State Fire Marshal and publication on the State Fire Marshal’s website, authorities having jurisdiction to enforce the Florida Fire Prevention Code may enforce the amendments to the code. The State Fire Marshal may approve only amendments that are needed to address:
(a) Conflicts within the updated Florida Fire Prevention Code;
(b) Conflicts between the updated Florida Fire Prevention Code and the Florida Building Code adopted pursuant to chapter 553;
(c) The omission of Florida-specific amendments that were previously adopted in the Florida Fire Prevention Code; or
(d) Unintended results from the integration of Florida-specific amendments that were previously adopted with the model code.
(6) The Florida Fire Prevention Code does not apply to, and no code enforcement action shall be brought with respect to, zoning requirements or land use requirements. Additionally, a local code enforcement agency may not administer or enforce the Florida Fire Prevention Code to prevent the siting of any publicly owned facility, including, but not limited to, correctional facilities, juvenile justice facilities, or state universities, community colleges, or public education facilities. This section shall not be construed to prohibit local government from imposing built-in fire protection systems or fire-related infrastructure requirements needed to properly protect the intended facility.
(7) Any local amendment adopted by a local government must strengthen the Fire Prevention Code requirements of the minimum firesafety code.
(8) Within 30 days after a local government adopts a local amendment, the local government must transmit the amendment to the Florida Building Commission and the State Fire Marshal.
(9) The State Fire Marshal shall make rules that implement this section and ss. 633.104 and 633.208 for the purpose of accomplishing the objectives set forth in those sections.
(10) Notwithstanding other provisions of this chapter, if a county or a municipality within that county adopts an ordinance providing for a local amendment to the Florida Fire Prevention Code and that amendment provides a higher level of protection to the public than the level specified in the Florida Fire Prevention Code, the local amendment becomes effective without approval of the State Fire Marshal and is not rescinded pursuant to this section, provided that the ordinance meets one or more of the following criteria:
(a) The local authority has adopted, by ordinance, a fire service facilities and operation plan that outlines goals and objectives for related equipment, personnel, and capital improvement needs of the local authority related to the specific amendment for the next 5 years;
(b) The local authority has adopted, by ordinance, a provision requiring proportionate reduction in, or rebate or waivers of, impact or other fees or assessments levied on buildings that are built or modified in compliance with the more stringent firesafety standards required by the local amendment; or
(c) The local authority has adopted, by ordinance, a growth management plan that requires buildings and structures to be equipped with more stringent firesafety requirements required by the local amendment when these firesafety requirements are used as the basis for planning infrastructure development, uses, or housing densities.

Except as provided in s. 633.206, the local appeals process shall be the venue if there is a dispute between parties affected by the provisions of the more stringent local firesafety amendment adopted as part of the Florida Fire Prevention Code pursuant to the authority in this subsection. Local amendments adopted pursuant to this subsection shall be deemed local or regional variations and published as such in the Florida Fire Prevention Code. The act of publishing locally adopted firesafety amendments to the Florida Fire Prevention Code may not be construed to mean that the State Fire Marshal approves or denies the authenticity or appropriateness of the locally adopted firesafety provision, and the burden of protecting the local firesafety amendment remains solely with the adopting local governmental authority.

(11) The design of interior stairways within dwelling units, including stair tread width and riser height, landings, handrails, and guards, must be consistent with chapter 10 of the Florida Building Code.
(12)(a) The State Fire Marshal shall issue an expedited declaratory statement relating to interpretations of the Florida Fire Prevention Code according to the following guidelines:
1. The declaratory statement shall be rendered in accordance with s. 120.565, except that a final decision must be issued by the State Fire Marshal within 45 days after the division’s receipt of a petition seeking an expedited declaratory statement. The State Fire Marshal shall give notice of the petition and the expedited declaratory statement or the denial of the petition in the next available issue of the Florida Administrative Register after the petition is filed and after the statement or denial is rendered.
2. The petitioner must be the owner of the disputed project or the owner’s representative.
3. The petition for an expedited declaratory statement must be:
a. Related to an active project that is under construction or must have been submitted for a permit.
b. The subject of a written notice citing a specific provision of the Florida Fire Prevention Code which is in dispute.
c. Limited to a single question that is capable of being answered with a “yes” or “no” response.
(b) A petition for a declaratory statement which does not meet all of the requirements of this subsection must be denied without prejudice. This subsection does not affect the right of the petitioner as a substantially affected person to seek a declaratory statement under s. 633.104(6).
(13) A condominium, cooperative, or multifamily residential building that is less than four stories in height and has an exterior corridor providing a means of egress is exempt from installing a manual fire alarm system as required in s. 9.6 of the most recent edition of the Life Safety Code adopted in the Florida Fire Prevention Code.
(14) The Legislature finds that the electronic filing of construction plans will increase governmental efficiency, reduce costs, and increase timeliness of processing permits. If the fire code administrator or fire official provides for electronic filing, any construction plans, drawings, specifications, reports, final documents, or documents prepared or issued by a licensee may be dated and electronically signed and sealed by the licensee in accordance with part I of chapter 668, and may be transmitted electronically to the fire code administrator or fire official for approval.
(15) For one-story or two-story structures that are less than 10,000 square feet, whose occupancy is defined in the Florida Building Code and the Florida Fire Prevention Code as business or mercantile, a fire official shall enforce the wall fire-rating provisions for occupancy separation as defined in the Florida Building Code.
(16)(a) As used in this subsection, the term:
1. “Agricultural pole barn” means a nonresidential farm building in which 70 percent or more of the perimeter walls are permanently open and allow free ingress and egress.
2. “Drone port” has the same meaning as provided in s. 330.41(2).
3. “Nonresidential farm building” has the same meaning as provided in s. 604.50.
(b) Notwithstanding any other provision of law:
1. A nonresidential farm building in which the occupancy is limited by the property owner to no more than 35 persons is exempt from the Florida Fire Prevention Code, including the national codes and Life Safety Code incorporated by reference.
2. An agricultural pole barn is exempt from the Florida Fire Prevention Code, including the national codes and the Life Safety Code incorporated by reference.
3. Except for an agricultural pole barn, a structure on a farm, as defined in s. 823.14(3)(c), which is used by an owner for agritourism activity, as defined in s. 570.86, for which the owner receives consideration must be classified in one of the following classes:
a. Class 1: A nonresidential farm building that is used by the owner 12 or fewer times per year for agritourism activity with up to 100 persons occupying the structure at one time. A structure in this class is subject to annual inspection for classification by the local authority having jurisdiction. This class is not subject to the Florida Fire Prevention Code but is subject to rules adopted by the State Fire Marshal pursuant to this section.
b. Class 2: A nonresidential farm building that is used by the owner for agritourism activity with up to 300 persons occupying the structure at one time. A structure in this class is subject to annual inspection for classification by the local authority having jurisdiction. This class is not subject to the Florida Fire Prevention Code but is subject to rules adopted by the State Fire Marshal pursuant to this section.
c. Class 3: A structure or facility that is used primarily for housing, sheltering, or otherwise accommodating members of the general public. A structure or facility in this class is subject to annual inspection for classification by the local authority having jurisdiction. This class is subject to the Florida Fire Prevention Code.
4. A drone port is exempt from provisions of the Florida Fire Prevention Code, including national codes and the Life Safety Code incorporated by reference, concerning fire protection systems as defined in s. 633.102.
(c) The State Fire Marshal shall adopt rules to administer this section, including, but not limited to:
1. The use of alternative lifesafety and fire prevention standards for structures in Classes 1 and 2;
2. Notification and inspection requirements for structures in Classes 1 and 2;
3. The application of the Florida Fire Prevention Code for structures in Class 3; and
4. Any other standards or rules deemed necessary in order to facilitate the use of structures for agritourism activities.
(17) A tent up to 900 square feet is exempt from the Florida Fire Prevention Code, including the national codes incorporated by reference.
(18)(a) The local authority having jurisdiction shall determine the minimum radio signal strength for fire department communications in all new and existing buildings. Two-way radio communication enhancement systems or equivalent systems may be used to comply with the minimum radio signal strength requirements. However, two-way radio communication enhancement systems or equivalent systems are not required in apartment buildings 75 feet or less in height that are constructed using wood framing, provided that the building has less than 150 dwelling units and that all dwelling units discharge to the exterior or to a corridor that leads directly to an exit as defined by the Florida Building Code. Evidence of wood frame construction shall be shown by the owner providing building permit documentation which identifies the construction type as wood frame. Existing high-rise buildings as defined by the Florida Building Code are not required to comply with minimum radio strength for fire department communications and two-way radio communication enhancement systems as required by the Florida Fire Prevention Code until January 1, 2025. However, by January 1, 2024, an existing high-rise building that is not in compliance with the requirements for minimum radio strength for fire department communications must apply for an appropriate permit for the required installation with the local government agency having jurisdiction and must demonstrate that the building will become compliant by January 1, 2025. Existing high-rise apartment buildings are not required to comply until January 1, 2025. However, existing high-rise apartment buildings are required to apply for the appropriate permit for the required communications installation by January 1, 2024.
(b) Except as provided in this subsection, all new and existing buildings must meet the minimum radio signal strength requirements for public safety agency communications as provided in the Florida Fire Prevention Code.
(c) The local authority having jurisdiction as defined in the Florida Fire Prevention Code may require:
1. The installation of a two-way radio communication enhancement system in a new or existing building if the interior of the building does not meet the minimum radio signal strength as required in the Florida Fire Prevention Code.
2. An assessment of a new or existing building’s interior radio coverage and signal strength, for purposes of determining the need for a two-way radio communication enhancement system within the building, not more frequently than once every 3 years for an existing high-rise building and an existing building having more than 12,000 total gross square feet and once every 5 years for all other existing buildings, unless:
a. Such building undergoes Level III building alteration or rehabilitation as defined in the Florida Building Code;
b. Such building undergoes reconstruction as determined by the Florida Fire Prevention Code;
c. A public safety agency reports to the local authority having jurisdiction that the agency’s communication devices failed to function correctly inside a building due to poor signal coverage; or
d. A building is determined to be an imminent life safety threat to first responders.
(d) Any modification to an existing system or any installation of a new system must have the express consent of the frequency licenseholder of the frequencies for which the system is intended to amplify. The consent must be maintained in a recordable format that can be presented to a Federal Communications Commission representative or other relevant agency investigating radio interference.
(e) If public safety agency communications signal strength or delivered audio quality, as defined in the Florida Fire Prevention Code, is determined by the local authority having jurisdiction to be inadequate at the exterior of the building, a two-way radio communication enhancement system or minimum radio strength assessment is not required.
(f) If a local authority having jurisdiction modifies its public safety emergency communication system such that modifications to existing two-way radio communication enhancement system installations are required, the local authority having jurisdiction must give owners of the existing two-way radio communication enhancement systems at least 180 days’ notice before requiring any modification.
(g) Notwithstanding paragraph (f), a local authority having jurisdiction that requires an existing building to retrofit its two-way radio communication enhancement system after the effective dates in paragraph (a) must give the building owner at least 1 year to complete the retrofit. The 1-year period begins when the local authority having jurisdiction cites the building owner with a notice of code violation in accordance with chapter 162.
(h) The following occupancies or buildings are not required to meet minimum radio signal strength requirements or have a radio signal strength assessment for public safety agency communications:
1. One- and two-family dwellings and townhouses.
2. Buildings having less than 12,000 total gross square feet with no underground areas.
3. Apartments and transient public lodging establishments that are less than three stories high and that have direct access from the apartment or guest area to an exterior means of egress.
4. Wood frame apartment buildings that are not required to install two-way radio communication enhancement systems or equivalent systems pursuant to paragraph (a).
(i) The provisions of s. 633.208 and this section which authorize local adoption of more stringent requirements than those specified in the Florida Fire Prevention Code and minimum firesafety codes do not apply to the requirements in this subsection. The local authority having jurisdiction may not enforce requirements that are more stringent than those specified in the Florida Fire Prevention Code and this subsection with respect to the requirement for, design of, or installation of a two-way radio communication enhancement system.
(j) The State Fire Marshal shall incorporate this subsection into the Florida Fire Prevention Code and may adopt rules to implement, interpret, and enforce this subsection.
(19) Areas of refuge shall be provided if required by the Florida Building Code, Accessibility. Required portions of an area of refuge shall be accessible from the space they serve by an accessible means of egress.
(20)(a) In apartment occupancies with enclosed corridors served by interior or exterior exit stairs, doorstep refuse and recycling collection containers, which stand upright on their own and do not leak liquids when standing upright, must be allowed in exit access corridors when all of the following conditions exist:
1. The maximum doorstep refuse and recycling collection container size does not exceed 13 gallons.
2. Waste, which is in a doorstep refuse and recycling collection container, is not placed in the exit access corridors for single periods exceeding 5 hours.
3. Doorstep refuse and recycling collection containers do not occupy the exit access corridors for single periods exceeding 12 hours.
4. Doorstep refuse and recycling collection containers do not reduce the means of egress width below that required under NFPA Life Safety Code 101:31, as adopted under the Florida Fire Prevention Code.
5. Management staff have written policies and procedures in place and enforce them to ensure compliance with this paragraph, and, upon request, provide a copy of such policies and procedures to the authority having jurisdiction.
(b) In apartment occupancies with open-air corridors or balconies served by exterior exit stairs, doorstep refuse and recycling collection containers, which stand upright on their own and do not leak liquids when standing upright, must be allowed in exit access corridors when all of the following conditions exist:
1. The maximum doorstep refuse and recycling collection container size does not exceed 27 gallons.
2. Waste, which is in a doorstep refuse and recycling collection container, is not placed in the exit access corridors for single periods exceeding 5 hours.
3. Doorstep refuse and recycling collection containers do not reduce the means of egress width below that required under NFPA Life Safety Code 101:31, as adopted under the Florida Fire Prevention Code.
4. Management staff have written policies and procedures in place and enforce them to ensure compliance with this paragraph, and, upon request, provide a copy of such policies and procedures to the authority having jurisdiction.
(c) The authority having jurisdiction may approve alternative containers and storage arrangements that are demonstrated to provide an equivalent level of safety to that provided under paragraphs (a) and (b).
History.s. 58, ch. 98-287; ss. 102, 103, ch. 2000-141; s. 43, ch. 2001-186; s. 123, ch. 2005-2; s. 23, ch. 2005-147; s. 7, ch. 2006-65; s. 4, ch. 2008-192; s. 6, ch. 2010-174; s. 47, ch. 2010-176; s. 1, ch. 2011-196; s. 17, ch. 2012-13; s. 54, ch. 2013-14; s. 1, ch. 2013-134; s. 21, ch. 2013-183; s. 27, ch. 2014-154; s. 1, ch. 2016-83; s. 27, ch. 2016-129; s. 1, ch. 2018-152; s. 4, ch. 2021-7; s. 25, ch. 2021-113; s. 1, ch. 2021-130; s. 55, ch. 2022-4; s. 1, ch. 2022-210; s. 3, ch. 2023-137; s. 2, ch. 2023-296; s. 27, ch. 2024-140.
Note.Former s. 633.0215.
633.204 Florida Fire Code Advisory Council.
(1) There is created within the department the Florida Fire Code Advisory Council with 11 members appointed by the State Fire Marshal. The council shall advise and recommend to the State Fire Marshal changes to and interpretation of the uniform firesafety standards adopted under s. 633.206, the Florida Fire Prevention Code, and those portions of the Florida Fire Prevention Code that have the effect of conflicting with building construction standards that are adopted pursuant to ss. 633.202 and 633.206. The members of the council shall represent the following groups and professions:
(a) One member shall be the State Fire Marshal, or his or her designated appointee who shall be an administrative employee of the marshal.
(b) One member shall be an administrative officer from a fire department representing a municipality, a county, or a special district selected from a list of persons submitted by the Florida Fire Chiefs Association.
(c) One member shall be an architect licensed in the state selected from a list of persons submitted by the Florida Association/American Institute of Architects.
(d) One member shall be an engineer with fire protection design experience registered to practice in the state selected from a list of persons submitted by the Florida Engineering Society.
(e) One member shall be an administrative officer from a building department of a county or municipality selected from a list of persons submitted by the Building Officials Association of Florida.
(f) One member shall be a contractor licensed in the state selected from a list submitted by the Florida Home Builders Association.
(g) One member shall be a Florida firefighter selected from a list submitted by the Florida Professional Firefighters Association.
(h) One member shall be a Florida certified firesafety inspector selected from a list submitted by the Florida Fire Marshals and Inspectors Association.
(i) One member shall be selected from a list submitted by the Department of Education.
(j) One member shall be selected from a list submitted by the Chancellor of the State University System.
(k) One member shall be representative of the general public.
(2) The State Fire Marshal and the Florida Building Commission shall coordinate efforts to provide consistency between the Florida Building Code and the Florida Fire Prevention Code.
(3) The council shall meet at least semiannually to advise the State Fire Marshal’s Office on matters subject to this section.
(4) The council may review proposed changes to the Florida Fire Prevention Code and the uniform firesafety standards pursuant to s. 633.202(4).
(5) The council and Florida Building Commission shall cooperate through joint representation and coordination of codes and standards to resolve conflicts in their development, updating, and interpretation.
(6) Each appointee shall serve a 4-year term. No member shall serve more than two consecutive terms. A member of the council may not be paid a salary as such member, but each shall receive travel and expense reimbursement as provided in s. 112.061.
History.ss. 17, 18, ch. 87-287; s. 24, ch. 88-149; ss. 4, 5, ch. 91-429; s. 451, ch. 97-102; s. 61, ch. 98-287; s. 50, ch. 99-3; s. 106, ch. 2000-141; s. 58, ch. 2010-176; s. 22, ch. 2013-183.
Note.Former s. 633.72.
633.206 Uniform firesafety standards.The Legislature hereby determines that to protect the public health, safety, and welfare it is necessary to provide for firesafety standards governing the construction and utilization of certain buildings and structures. The Legislature further determines that certain buildings or structures, due to their specialized use or to the special characteristics of the person utilizing or occupying these buildings or structures, should be subject to firesafety standards reflecting these special needs as may be appropriate.
(1) The department shall establish uniform firesafety standards that apply to:
(a) All new, existing, and proposed state-owned and state-leased buildings.
(b) All new, existing, and proposed hospitals, nursing homes, assisted living facilities, adult family-care homes, correctional facilities, public schools, transient public lodging establishments, public food service establishments, mobile food dispensing vehicles, elevators, migrant labor camps, mobile home parks, lodging parks, recreational vehicle parks, recreational camps, residential and nonresidential child care facilities, facilities for the developmentally disabled, motion picture and television special effects productions, tunnels, energy storage systems, and self-service gasoline stations, of which standards the State Fire Marshal is the final administrative interpreting authority.

In the event there is a dispute between the owners of the buildings specified in paragraph (b) and a local authority requiring a more stringent uniform firesafety standard for sprinkler systems, the State Fire Marshal shall be the final administrative interpreting authority and the State Fire Marshal’s interpretation regarding the uniform firesafety standards shall be considered final agency action.

(2)(a) With respect to the uniform firesafety standards, the department shall develop uniform statewide standards which are reasonably prudent with respect to protecting life, safety, and property and which take into consideration the characteristics of the people utilizing the subject buildings and structures and other hazards associated with the subject buildings and structures throughout the state.
(b) A local authority may not require more stringent uniform firesafety standards with respect to buildings or structures subject to such standards except as provided in paragraph (c). A local authority may, on a case-by-case basis, in order to meet special situations arising from historic, geographic, or unusual conditions, with respect to a building or structure which is subject to the uniform firesafety standards, authorize equivalent alternative standards for such building or structure; however, the alternative requirements shall not result in a level of protection to life, safety, or property less stringent than the applicable uniform firesafety standards. All such local authorities shall enforce, within their firesafety jurisdiction, the uniform firesafety standards for those buildings specified in paragraph (1)(b) and the minimum firesafety standards adopted pursuant to s. 394.879.
(c) A local authority may require more stringent uniform firesafety standards for sprinkler systems in buildings specified in paragraph (b), for which the construction contract is let after January 1, 1994, if the following conditions are met:
1. The local authority has adopted, by ordinance, a fire service facilities and operation plan that outlines goals and objectives for related equipment, personnel, and capital improvement needs of the local authority for the next 5 years.
2. The local authority has adopted, by ordinance, a provision requiring proportionate reductions in, or rebate or waivers of, impact or other fees or assessments levied on buildings that are built or modified in compliance with the more stringent sprinkler standards.
3. The local authority has adopted, by ordinance, a plan that requires buildings specified in paragraph (b) to be equipped with an automatic sprinkler system installed in compliance with the provisions prescribed in standards as established by the National Fire Protection Association and adopted by the State Fire Marshal.

In the event there is a dispute between the owners of the buildings specified in paragraph (b) and a local authority requiring a more stringent uniform firesafety standard for sprinkler systems, the State Fire Marshal shall be the final administrative interpreting authority and the State Fire Marshal’s interpretation regarding the uniform firesafety standards shall be considered final agency action.

(3) In establishing the uniform firesafety standards and the minimum firesafety standards, as required by s. 394.879, the department shall consider types of construction materials and their flame spread and smoke characteristics, occupancy levels, means of egress, special hazard protection, smoke barriers, interior finish, and fire protection systems or equipment and occupancy features necessary to minimize danger to life from fire, smoke, fumes, or panic. In considering these factors, the department shall develop minimum standards which are reasonably prudent with respect to protecting life, safety, and property.
(4)(a) Notwithstanding any provision of law to the contrary, each nursing home licensed under part II of chapter 400 shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with s. 9 of National Fire Protection Association, Inc., Life Safety Code, no later than December 31, 2010.
(b) The division may grant up to two 1-year extensions of the time limits for compliance in subparagraph (a)2. if the division determines that the nursing home has been prevented from complying for reasons beyond its control.
(c) The division is authorized to adopt any rule necessary for the implementation and enforcement of this subsection. The division shall enforce this subsection in accordance with the provisions of this chapter, and any nursing home licensed under part II of chapter 400 that is in violation of this subsection may be subject to administrative sanctions by the division pursuant to this chapter.
(d) Adjustments shall be made to the provider Medicaid rate to allow reimbursement over a 5-year period for Medicaid’s portion of the costs incurred to meet the requirements of this subsection. Funding for this adjustment shall come from existing nursing home appropriations.
History.s. 5, ch. 87-287; s. 2, ch. 90-359; s. 29, ch. 93-150; s. 2, ch. 93-276; s. 44, ch. 95-210; s. 7, ch. 95-379; s. 4, ch. 99-179; s. 3, ch. 2002-287; s. 1392, ch. 2003-261; s. 2, ch. 2005-234; s. 2, ch. 2008-192; s. 23, ch. 2013-183; s. 28, ch. 2024-140.
Note.Former s. 633.022.
633.208 Minimum firesafety standards.
(1) The Florida Fire Prevention Code adopted by the State Fire Marshal, which shall operate in conjunction with the Florida Building Code, shall be deemed adopted by each municipality, county, and special district with firesafety responsibilities. The minimum firesafety codes do not apply to buildings and structures subject to the uniform firesafety standards under s. 633.206 and buildings and structures subject to the minimum firesafety standards adopted pursuant to s. 394.879.
(2)(a) Pursuant to subsection (1), each municipality, county, and special district with firesafety responsibilities shall enforce the Florida Fire Prevention Code as the minimum firesafety code required by this section.
(b) If a municipality, county, or special district determines that the building plans for a building permit application do not comply with the Florida Fire Prevention Code or the Life Safety Code, or local amendments thereto, the local fire official must identify the specific plan features that do not comply with the applicable codes, identify the specific code chapters and sections upon which the determination is based, and provide this information to the permit applicant.
(c) After a municipality, county, or special district issues a building permit, it may not make or require any substantive changes to the building plans except those required for compliance with the Florida Fire Prevention Code or the Life Safety Code, or local amendments thereto. If a municipality, county, or special district makes or requires substantive changes to building plans after a permit is issued, the local fire official must identify the specific plan features that do not comply with the Florida Fire Prevention Code or the Life Safety Code, or local amendments thereto; identify the specific code chapters and sections upon which the finding is based; and provide this information to the permitholder.
(d) A local fire official who is also a certified firesafety inspector and who fails to comply with paragraph (b) or paragraph (c) is subject to disciplinary action against his or her certificate under s. 633.216(5)(f).
(3) Such code shall be a minimum code, and a municipality, county, or special district with firesafety responsibilities may adopt more stringent firesafety standards, subject to the requirements of this subsection. Such county, municipality, or special district may establish alternative requirements to those requirements which are required under the minimum firesafety standards on a case-by-case basis, in order to meet special situations arising from historic, geographic, or unusual conditions, if the alternative requirements result in a level of protection to life, safety, or property equal to or greater than the applicable minimum firesafety standards. For the purpose of this subsection, the term “historic” means that the building or structure is listed on the National Register of Historic Places of the United States Department of the Interior.
(a) The local governing body shall determine, following a public hearing which has been advertised in a newspaper of general circulation at least 10 days before the hearing, if there is a need to strengthen the requirements of the minimum firesafety code adopted by such governing body. The determination must be based upon a review of local conditions by the local governing body, which review demonstrates that local conditions justify more stringent requirements than those specified in the minimum firesafety code for the protection of life and property or justify requirements that meet special situations arising from historic, geographic, or unusual conditions.
(b) Such additional requirements may not be discriminatory as to materials, products, or construction techniques of demonstrated capabilities.
(c) Paragraphs (a) and (b) apply solely to the local enforcing agency’s adoption of requirements more stringent than those specified in the Florida Fire Prevention Code and the Life Safety Code that have the effect of amending building construction standards. Upon request, the enforcing agency must provide a person making application for a building permit, or any state agency or board with construction-related regulation responsibilities, a listing of all such requirements and codes.
(d) A local government which adopts amendments to the minimum firesafety code must provide a procedure by which the validity of such amendments may be challenged by any substantially affected party to test the amendment’s compliance with this section.
1. Unless the local government agrees to stay enforcement of the amendment, or other good cause is shown, the challenging party shall be entitled to a hearing on the challenge within 45 days.
2. For purposes of such challenge, the burden of proof shall be on the challenging party, but the amendment may not be presumed to be valid or invalid.

This subsection gives local government the authority to establish firesafety codes that exceed the Florida Fire Prevention Code adopted by the State Fire Marshal. The Legislature intends that local government give proper public notice and hold public hearings before adopting more stringent firesafety codes. A substantially affected person may appeal, to the department, the local government’s resolution of the challenge, and the department shall determine if the amendment complies with this section. Actions of the department are subject to judicial review pursuant to s. 120.68. The department shall consider reports of the Florida Building Commission, pursuant to part IV of chapter 553, when evaluating building code enforcement.

(4) The new building or structure provisions enumerated within the Florida Fire Prevention Code adopted pursuant to this section shall apply only to buildings or structures for which the building permit is issued on or after the effective date of the current edition of the Florida Fire Prevention Code. Subject to subsection (5), the existing building or structure provisions enumerated within the firesafety code adopted pursuant to this section shall apply to buildings or structures for which the building permit was issued or the building or structure was constructed before the effective date of this act.
(5) With regard to existing buildings, the Legislature recognizes that it is not always practical to apply any or all of the provisions of the Florida Fire Prevention Code and that physical limitations may require disproportionate effort or expense with little increase in fire or life safety. Before applying the minimum firesafety code to an existing building, the local fire official shall determine whether a threat to lifesafety or property exists. If a threat to lifesafety or property exists, the fire official shall apply the applicable firesafety code for existing buildings to the extent practical to ensure a reasonable degree of lifesafety and safety of property or shall fashion a reasonable alternative that affords an equivalent degree of lifesafety and safety of property. The local fire official may consider the fire safety evaluation systems found in NFPA 101A: Guide on Alternative Approaches to Life Safety, adopted by the State Fire Marshal, as acceptable systems for the identification of low-cost, reasonable alternatives. It is acceptable to use the Fire Safety Evaluation System for Board and Care Facilities using prompt evacuation capabilities parameter values on existing residential high-rise buildings. The decision of the local fire official may be appealed to the local administrative board described in s. 553.73.
(6) Nothing herein shall preclude a municipality, county, or special district from requiring a structure to be maintained in accordance with the Florida Fire Prevention Code.
(7) Electrically operated single station smoke detectors required for residential buildings are not required to be interconnected within individual living units in all buildings having direct access to the outside from each living unit and having three stories or less. This subsection does not apply to any residential building required to have a manual or an automatic fire alarm system.
(8)(a) The provisions of the Life Safety Code, as contained in the Florida Fire Prevention Code, do not apply to one-family and two-family dwellings. However, fire sprinkler protection may be permitted by local government in lieu of other fire protection-related development requirements for such structures. While local governments may adopt fire sprinkler requirements for one-family and two-family dwellings under this subsection, it is the intent of the Legislature that the economic consequences of the fire sprinkler mandate on home owners be studied before the enactment of such a requirement. After the effective date of this act, any local government that desires to adopt a fire sprinkler requirement on one-family or two-family dwellings must prepare an economic cost and benefit report that analyzes the application of fire sprinklers to one-family or two-family dwellings or any proposed residential subdivision. The report must consider the tradeoffs and specific cost savings and benefits of fire sprinklers for future owners of property. The report must include an assessment of the cost savings from any reduced or eliminated impact fees if applicable, the reduction in special fire district tax, insurance fees, and other taxes or fees imposed, and the waiver of certain infrastructure requirements including the reduction of roadway widths, the reduction of water line sizes, increased fire hydrant spacing, increased dead-end roadway length, and a reduction in cul-de-sac sizes relative to the costs from fire sprinkling. A failure to prepare an economic report shall result in the invalidation of the fire sprinkler requirement to any one-family or two-family dwelling or any proposed subdivision. In addition, a local jurisdiction or utility may not charge any additional fee, above what is charged to a non-fire sprinklered dwelling, on the basis that a one-family or two-family dwelling unit is protected by a fire sprinkler system.
(b)1. A county, municipality, special taxing district, public utility, or private utility may not require an impact fee or payment for a separate water connection for a one-family or two-family dwelling fire sprinkler system if the capacity required is hydraulically available at the property line. The accountholder of the one-family or two-family dwelling must notify the county, municipality, special district, public utility, or private utility of the installation of the separate water connection in the applicable permit. The separate water connection may only be used for one-family or two-family dwelling fire sprinkler systems and if used for other purposes, full base and volume charges may be applied.
2. A county, municipality, special district, public utility, or private utility may not charge a water or sewer rate to a one-family or two-family dwelling that requires a larger water meter solely due to the installation of fire sprinklers above that which is charged to a one-family and two-family dwelling with a base meter. If the installation of fire sprinklers in a one-family or two-family dwelling requires the installation of a larger water meter, only the difference in actual cost between the base water meter and the larger water meter may be charged by the water utility provider.
(9) Before imposing a fire sprinkler requirement on any one- or two-family dwelling, a local government must provide the owner of any one- or two-family dwelling a letter documenting specific infrastructure or other tax or fee allowances and waivers that are listed in but not limited to those described in subsection (8) for the dwelling. The documentation must show that the cost savings reasonably approximate the cost of the purchase and installation of a fire protection system.
(10) Notwithstanding subsection (8), a property owner may not be required to install fire sprinklers in any residential property based upon the use of such property as a rental property or any change in or reclassification of the property’s primary use to a rental property.
(11) Notwithstanding subsection (8), a single-family or two-family dwelling that is a certified recovery residence, as defined in s. 397.311, or that is a recovery residence, as defined in s. 397.311, that has a charter from an entity recognized or sanctioned by Congress may not be reclassified for purposes of enforcing the Florida Fire Prevention Code solely due to such use.
History.s. 6, ch. 87-287; s. 1, ch. 88-362; s. 8, ch. 91-110; s. 2, ch. 91-189; s. 8, ch. 95-379; s. 59, ch. 98-287; ss. 104, 105, ch. 2000-141; s. 3, ch. 2001-64; s. 1393, ch. 2003-261; s. 17, ch. 2005-147; s. 157, ch. 2008-4; s. 2, ch. 2010-99; s. 49, ch. 2010-176; s. 24, ch. 2013-183; s. 2, ch. 2016-83; s. 28, ch. 2016-129; s. 22, ch. 2016-132; s. 14, ch. 2017-149; s. 7, ch. 2021-128; s. 2, ch. 2023-229.
Note.Former s. 633.025.
633.212 Legislative intent; informal interpretations of the Florida Fire Prevention Code.It is the intent of the Legislature that the Florida Fire Prevention Code be interpreted by fire officials and local enforcement agencies in a manner that reasonably and cost-effectively protects the public safety, health, and welfare; ensures uniform interpretations throughout this state; and provides just and expeditious processes for resolving disputes regarding such interpretations. It is the further intent of the Legislature that such processes provide for the expeditious resolution of the issues presented and that the resulting interpretation of such issues be published on the website of the division.
(1) The division shall by rule establish an informal process of rendering nonbinding interpretations of the Florida Fire Prevention Code. The division may contract with and refer interpretive issues to a third party, selected based upon cost effectiveness, quality of services to be performed, and other performance-based criteria, which has experience in interpreting and enforcing the Florida Fire Prevention Code. It is the intent of the Legislature that the division establish a Fire Code Interpretation Committee composed of seven persons and seven alternates, equally representing each area of the state, to which a party can pose questions regarding the interpretation of the Florida Fire Prevention Code provisions. The alternate member may respond to a nonbinding interpretation if a member is unable to respond.
(2) Each member and alternate member of the Fire Code Interpretation Committee must be certified as a firesafety inspector pursuant to s. 633.216(2) and must have a minimum of 5 years of experience interpreting and enforcing the Florida Fire Prevention Code. Each member and alternate member must be approved by the division and deemed by the division to have met these requirements for at least 30 days before participating in a review of a nonbinding interpretation.
(3) Each nonbinding interpretation of code provisions must be provided within 15 business days after receipt of a request for interpretation. The response period established in this subsection may be waived only with the written consent of the party requesting the nonbinding interpretation and the division. Nonbinding interpretations shall be advisory only and nonbinding on the parties or the State Fire Marshal.
(4) In order to administer this section, the division shall charge a fee for nonbinding interpretations. The fee may not exceed $150 for each request for a review or interpretation. The division may authorize payment of fees directly to the nonprofit organization under contract pursuant to subsection (1).
(5) A party requesting a nonbinding interpretation who disagrees with the interpretation issued under this section may apply for a declaratory statement from the State Fire Marshal pursuant to s. 633.104(6).
(6) The division shall issue or cause to be issued a nonbinding interpretation of the Florida Fire Prevention Code pursuant to this section when requested to do so upon submission of a petition by a fire official or by the owner or owner’s representative or the contractor or contractor’s representative of a project in dispute. The division shall adopt a petition form by rule, and the petition form must be published on the State Fire Marshal’s website. The form must, at a minimum, require:
(a) The name and address of the local fire official, including the address of the county, municipality, or special district.
(b) The name and address of the owner or owner’s representative or the contractor or contractor’s representative.
(c) A statement of the specific sections of the Florida Fire Prevention Code being interpreted by the local fire official.
(d) An explanation of how the petitioner’s substantial interests are being affected by the local interpretation of the Florida Fire Prevention Code.
(e) A statement of the interpretation of the specific sections of the Florida Fire Prevention Code by the local fire official.
(f) A statement of the interpretation that the petitioner contends should be given to the specific sections of the Florida Fire Prevention Code and a statement supporting the petitioner’s interpretation.
(g) A single question that is capable of being answered with a “yes” or “no” response.
(7) Upon receipt of a petition that meets the requirements of subsection (6), the division shall immediately provide copies of the petition to the Fire Code Interpretation Committee, and shall publish the petition and any response submitted by the local fire official on the State Fire Marshal’s website.
(8) The committee shall conduct proceedings as necessary to resolve the issues and give due regard to the petition, the facts of the matter at issue, specific code sections cited, and any statutory implications affecting the Florida Fire Prevention Code. The committee shall issue an interpretation regarding the provisions of the Florida Fire Prevention Code within 15 days after the filing of a petition. The committee shall issue an interpretation based upon the Florida Fire Prevention Code or, if the code is ambiguous, the intent of the code. The committee’s interpretation shall be provided to the petitioner and shall include a notice that if the petitioner disagrees with the interpretation, the petitioner may file a request for a declaratory statement by the State Fire Marshal under s. 633.104(6). The committee’s interpretation shall be provided to the State Fire Marshal, and the division shall publish the declaratory statement on the State Fire Marshal’s website and in the Florida Administrative Register.
History.s. 18, ch. 2005-147; s. 93, ch. 2006-1; s. 50, ch. 2010-176; s. 55, ch. 2013-14; s. 25, ch. 2013-183; s. 28, ch. 2014-154.
Note.Former s. 633.026.
633.214 Ordinances relating to firesafety; definitions; penalties.
(1) As used in this section:
(a) A “firesafety inspector” is an individual certified by the division, officially assigned the duties of conducting firesafety inspections of buildings and facilities on a recurring or regular basis, investigating civil infractions relating to firesafety, and issuing citations pursuant to this section on behalf of the state or any county, municipality, or special district with firesafety responsibilities.
(b) “Citation” means a written notice, issued only after a written warning has been previously issued and a minimum time period of 45 days, except for major structural changes, which may be corrected within an extended adequate period of time, from the date of the issuance of the warning whereby the party warned may correct the alleged violation, issued to a person by a firesafety inspector, that the firesafety inspector has probable cause to believe that the person has committed a civil infraction in violation of a duly enacted ordinance and that the county court will hear the charge. The citation must contain:
1. The date and time of issuance.
2. The name and address of the person.
3. The date and time the civil infraction was committed.
4. The facts constituting probable cause.
5. The Florida Fire Prevention Code ordinance violated.
6. The name and authority of the firesafety inspector.
7. The procedure for the person to follow in order to pay the civil penalty or to contest the citation.
8. The applicable civil penalty if the person elects to contest the citation.
9. The applicable civil penalty if the person elects not to contest the citation.
10. A conspicuous statement that if the person fails to pay the civil penalty within the time allowed or fails to appear in court to contest the citation, then she or he shall be deemed to have waived her or his right to contest the citation and that, in such case, judgment may be entered against the person for an amount up to the maximum civil penalty.
(c) “Ordinance” means any ordinance enacted by the governing body of a county or municipality that is a civil infraction relating to firesafety codes.
(2) A county or municipality that has created a code enforcement board or special magistrate system pursuant to chapter 162 may enforce firesafety code violations as provided in chapter 162. The governing body of a county or municipality which has not created a code enforcement board or special magistrate system for firesafety under chapter 162 may enact ordinances relating to firesafety codes, which ordinances shall provide:
(a) That a violation of such an ordinance is a civil infraction.
(b) A maximum civil penalty not to exceed $500.
(c) A civil penalty of less than the maximum civil penalty if the person who has committed the civil infraction does not contest the citation.
(d) For the issuance of a citation by an officer who has probable cause to believe that a person has committed a violation of an ordinance relating to firesafety or the Florida Fire Prevention Code.
(e) For the contesting of a citation in the county court.
(f) Such procedures and provisions necessary to implement any ordinances enacted under the authority of this section.
(3) A person who willfully refuses to sign and accept a citation issued by a firesafety inspector commits a misdemeanor of the second degree, punishable as provided in s. 775.082 or s. 775.083.
(4) This section does not prevent any county, municipality, or special district from enacting any ordinance relating to firesafety codes which is identical to this chapter or any state law, except as to penalty; however, a county, municipal, or special district ordinance relating to firesafety codes may not conflict with this chapter or any other state law.
History.s. 1, ch. 88-222; s. 156, ch. 91-224; s. 9, ch. 95-379; s. 422, ch. 97-102; s. 1394, ch. 2003-261; s. 95, ch. 2004-11; s. 26, ch. 2013-183.
Note.Former s. 633.052.
633.216 Inspection of buildings and equipment; orders; firesafety inspection training requirements; certification; disciplinary action.The State Fire Marshal and her or his agents or persons authorized to enforce laws and rules of the State Fire Marshal shall, at any reasonable hour, when the State Fire Marshal has reasonable cause to believe that a violation of this chapter or s. 509.215, or a rule adopted thereunder, or a minimum firesafety code adopted by the State Fire Marshal or a local authority, may exist, inspect any and all buildings and structures which are subject to the requirements of this chapter or s. 509.215 and rules adopted thereunder. The authority to inspect shall extend to all equipment, vehicles, and chemicals which are located on or within the premises of any such building or structure.
(1) Each county, municipality, and special district that has firesafety enforcement responsibilities shall employ or contract with a firesafety inspector. Except as provided in s. 633.312(2), (3), and (4), the firesafety inspector must conduct all firesafety inspections that are required by law. The governing body of a county, municipality, or special district that has firesafety enforcement responsibilities may provide a schedule of fees to pay only the costs of inspections conducted pursuant to this subsection and related administrative expenses. Two or more counties, municipalities, or special districts that have firesafety enforcement responsibilities may jointly employ or contract with a firesafety inspector.
(2) Except as provided in s. 633.312(2), every firesafety inspection conducted pursuant to state or local firesafety requirements shall be by a person certified as having met the inspection training requirements set by the State Fire Marshal. Such person shall meet the requirements of s. 633.412(1)-(4), and:
(a) Have satisfactorily completed the firesafety inspector certification examination as prescribed by division rule; and
(b)1. Have satisfactorily completed, as determined by division rule, a firesafety inspector training program of at least 200 hours established by the department and administered by education or training providers approved by the department for the purpose of providing basic certification training for firesafety inspectors; or
2. Have received training in another state which is determined by the division to be at least equivalent to that required by the department for approved firesafety inspector education and training programs in this state.
(3) A firefighter certified pursuant to s. 633.408 may conduct firesafety inspections, under the supervision of a certified firesafety inspector, while on duty as a member of a fire department company conducting inservice firesafety inspections without being certified as a firesafety inspector, if such firefighter has satisfactorily completed an inservice fire department company inspector training program of at least 24 hours’ duration as provided by rule of the department.
(4) Every firesafety inspector certificate is valid for a period of 4 years from the date of issuance. Renewal of certification is subject to the affected person’s completing proper application for renewal and meeting all of the requirements for renewal as established under this chapter or by rule adopted under this chapter, which must include completion of at least 54 hours during the preceding 4-year period of continuing education as required by the rule of the department.
(5) The State Fire Marshal may deny, refuse to renew, suspend, or revoke the certificate of a firesafety inspector if the State Fire Marshal finds that any of the following grounds exist:
(a) Any cause for which issuance of a certificate could have been refused had it then existed and been known to the division.
(b) Violation of this chapter or any rule or order of the State Fire Marshal.
(c) Falsification of records relating to the certificate.
(d) Failure to meet any of the renewal requirements.
(e) Making or filing a report or record that the certificateholder knows to be false, or knowingly inducing another to file a false report or record, or knowingly failing to file a report or record required by state or local law, or knowingly impeding or obstructing such filing, or knowingly inducing another person to impede or obstruct such filing.
(f) Failing to properly enforce applicable fire codes or permit requirements within this state which the certificateholder knows are applicable by committing willful misconduct, gross negligence, gross misconduct, repeated negligence, or negligence resulting in a significant danger to life or property.
(g) Accepting labor, services, or materials at no charge or at a noncompetitive rate from a person who performs work that is under the enforcement authority of the certificateholder and who is not an immediate family member of the certificateholder. For the purpose of this paragraph, the term “immediate family member” means a spouse, child, parent, sibling, grandparent, aunt, uncle, or first cousin of the person or the person’s spouse or a person who resides in the primary residence of the certificateholder.
(6) The division and the Florida Building Code Administrators and Inspectors Board, established pursuant to s. 468.605, shall enter into a reciprocity agreement to facilitate joint recognition of continuing education recertification hours for certificateholders licensed under s. 468.609 and firesafety inspectors certified under subsection (2).
(7) The State Fire Marshal shall develop by rule an advanced training and certification program for firesafety inspectors having fire code management responsibilities. The program must be consistent with the appropriate provisions of NFPA 1037, or similar standards adopted by the division, and establish minimum training, education, and experience levels for firesafety inspectors having fire code management responsibilities.
(8) The department shall provide by rule for the certification of firesafety inspectors and fire code administrators.
History.s. 6, ch. 20671, 1941; s. 8, ch. 65-216; s. 4, ch. 67-78; ss. 13, 35, ch. 69-106; s. 3, ch. 70-299; s. 14, ch. 75-151; s. 1, ch. 77-174; s. 2, ch. 79-352; s. 1, ch. 81-205; s. 1, ch. 82-189; s. 4, ch. 84-243; s. 9, ch. 87-287; s. 2, ch. 88-222; s. 3, ch. 88-362; s. 4, ch. 93-276; s. 11, ch. 95-379; s. 424, ch. 97-102; s. 1396, ch. 2003-261; s. 9, ch. 2007-187; s. 1, ch. 2010-173; s. 52, ch. 2010-176; s. 47, ch. 2011-4; s. 3, ch. 2011-79; s. 27, ch. 2013-183; s. 157, ch. 2014-17; s. 43, ch. 2017-3; s. 39, ch. 2019-140; s. 56, ch. 2022-138.
Note.Former s. 633.06; s. 633.081.
633.217 Influencing a firesafety inspector; prohibited acts.
(1) A person may not influence a firesafety inspector by:
(a) Threatening, coercing, tricking, or attempting to threaten, coerce, or trick the firesafety inspector into violating any provision of the Florida Fire Prevention Code, any rule adopted by the State Fire Marshal, or any provision of this chapter.
(b) Offering any compensation to the firesafety inspector to induce a violation of the Florida Fire Prevention Code, any rule adopted by the State Fire Marshal, or any provision of this chapter.
(2) A firesafety inspector may not knowingly and intentionally request, solicit, accept, or agree to accept compensation offered as described in paragraph (1)(b).
History.s. 26, ch. 2021-113.
633.218 Inspections of state buildings and premises; tests of firesafety equipment; building plans to be approved.
(1)(a) It is the duty of the State Fire Marshal and her or his agents to inspect, or cause to be inspected, each state-owned building on a recurring basis established by rule, and to ensure that high-hazard occupancies are inspected at least annually, for the purpose of ascertaining and causing to be corrected any conditions liable to cause fire or endanger life from fire and any violation of the firesafety standards for state-owned buildings, this chapter, or the rules adopted pursuant hereto. The State Fire Marshal shall, within 7 days following an inspection, submit a report of such inspection to the head of the state agency responsible for the building.
(b) Except as provided in s. 255.45, the department head is responsible for ensuring that deficiencies noted in the inspection are corrected as soon as practicable.
(c) Each department shall, in its annual budget proposal, include requests for sufficient funds to correct any firesafety deficiencies noted by the State Fire Marshal.
(d) Each department shall, in its annual budget proposal and for all proposals for new construction or renovations to existing structures, include requests for sufficient funds to pay for any charges or fees imposed by the State Fire Marshal for review of plans, renovations, occupancy, or inspections, whether recurring or high hazard.
(e) For purposes of this section:
1.a. The term “high-hazard occupancy” means any building or structure:
(I) That contains combustible or explosive matter or flammable conditions dangerous to the safety of life or property;
(II) At which persons receive educational instruction;
(III) At which persons reside, excluding private dwellings; or
(IV) Containing three or more floor levels.
b. As used in this subparagraph, the phrase “building or structure”:
(I) Includes, but is not limited to, all hospitals and residential health care facilities, nursing homes and other adult care facilities, correctional or detention facilities, public schools, public lodging establishments, migrant labor camps, residential child care facilities, and self-service gasoline stations.
(II) Does not include any residential condominium where the declaration of condominium or the bylaws provide that the rental of units shall not be permitted for less than 90 days.
2. The term “state-owned building” includes contractor-operated correctional facilities as defined under s. 944.710.
(2) The State Fire Marshal and her or his agents may conduct performance tests on any electronic fire warning and smoke detection system, and any pressurized air-handling unit, in any state-owned building or state-leased building or space on a recurring basis as provided in subsection (1). The State Fire Marshal and her or his agents shall also ensure that fire drills are conducted in all high-hazard state-owned buildings or high-hazard state-leased occupancies at least annually.
(3) All construction of any new state-owned building or state-leased building or space or any renovation, alteration, or change of occupancy of any existing, state-owned building or state-leased building or space must comply with the uniform firesafety standards of the State Fire Marshal.
(a) For all new construction or renovation, alteration, or change of occupancy of state-leased space, compliance with the uniform firesafety standards shall be determined by reviewing the plans for the proposed construction or occupancy submitted by the lessor to the division for review and approval before commencement of construction or occupancy, which review shall be completed within 10 working days after receipt of the plans by the division.
(b) The plans for all construction of any new, or renovation or alteration of any existing, state-owned building are subject to the review and approval of the division for compliance with the uniform firesafety standards before commencement of construction or change of occupancy, which review shall be completed within 30 calendar days of receipt of the plans by the division.
(4) The division may inspect state-owned buildings and space and state-leased buildings and space as necessary before occupancy or during construction, renovation, or alteration to ascertain compliance with the uniform firesafety standards. Whenever the division determines by virtue of such inspection or by review of plans that construction, renovation, or alteration of state-owned buildings and state-leased buildings or space is not in compliance with the uniform firesafety standards, the division shall issue an order to cease construction, renovation, or alteration, or to preclude occupancy, of a building until compliance is obtained, except for those activities required to achieve such compliance.
(5) The division shall by rule provide a schedule of fees to pay for the costs of the inspections, whether recurring or high hazard, any firesafety review or plans for proposed construction, renovations, or occupancy, and related administrative expenses.
History.s. 15, ch. 75-151; s. 2, ch. 83-336; s. 2, ch. 84-143; s. 6, ch. 84-243; s. 19, ch. 89-233; s. 4, ch. 90-359; s. 5, ch. 91-189; s. 5, ch. 93-276; s. 12, ch. 95-379; s. 425, ch. 97-102; s. 60, ch. 98-287; s. 28, ch. 2013-183; s. 29, ch. 2019-140; s. 9, ch. 2024-84.
Note.Former s. 633.085.
633.222 Buildings with light-frame truss-type construction; notice requirements; enforcement.
(1) The owner of any commercial or industrial structure, or any multiunit residential structure of three units or more, that uses light-frame truss-type construction shall mark the structure with a sign or symbol approved by the State Fire Marshal in a manner sufficient to warn persons conducting fire control and other emergency operations of the existence of light-frame truss-type construction in the structure.
(2) The State Fire Marshal shall adopt rules necessary to implement the provisions of this section, including, but not limited to:
(a) The dimensions and color of such sign or symbol.
(b) The time within which commercial, industrial, and multiunit residential structures that use light-frame truss-type construction shall be marked as required by this section.
(c) The location on each commercial, industrial, and multiunit residential structure that uses light-frame truss-type construction where such sign or symbol must be posted.
(3) The State Fire Marshal, and local fire officials in accordance with s. 633.118, shall enforce this section. An owner who fails to comply with the requirements of this section is subject to penalties as provided in s. 633.228.
History.s. 5, ch. 2008-192; s. 29, ch. 2013-183.
Note.Former s. 633.027.
633.224 Automatic fire sprinkler systems for one-family dwellings, two-family dwellings, and mobile homes.
(1) It is unlawful for a person to engage in the business or act in the capacity of a contractor of automatic fire sprinkler systems for one-family dwellings, two-family dwellings, and mobile homes without having been duly certified and holding a current certificate as a Contractor I, Contractor II, or Contractor IV as defined in s. 633.102.
(2) A person who violates any provision of this section commits a misdemeanor of the second degree, punishable as provided in s. 775.082 or s. 775.083.
History.ss. 4, 5, ch. 84-107; ss. 2, 4, ch. 87-181; s. 4, ch. 91-429; s. 3, ch. 98-104; s. 30, ch. 2013-183.
Note.Former s. 633.60.
633.226 Exemptions; farm outbuildings; standpipe systems installed by plumbing contractors.
(1) This act does not apply to owners of property who are building or improving farm outbuildings.
(2) A licensed plumbing contractor is not required to be certified under this act to install standpipe systems and the following items connected thereto: overhead and underground water mains, fire hydrants and hydrant mains, hose connections, tanks and pumps; including sprinkler heads in trash chutes and in trash rooms, having no connection to an automatic sprinkler.
History.s. 19, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-174; s. 1, ch. 77-457; s. 8, ch. 78-141; s. 5, ch. 80-342; s. 2, ch. 81-318; s. 3, ch. 84-107; ss. 1, 2, ch. 85-128; s. 4, ch. 91-429; s. 31, ch. 2013-183.
Note.Former s. 633.557.
633.228 Violations; orders to cease and desist, correct hazardous conditions, preclude occupancy, or vacate; enforcement; penalties.
(1) If it is determined by the department that a violation specified in this subsection exists, the State Fire Marshal or her or his deputy may issue and deliver to the person committing the violation an order to cease and desist from such violation, to correct any hazardous condition, to preclude occupancy of the affected building or structure, or to vacate the premises of the affected building or structure. Such violations are:
(a) Except as set forth in paragraph (b), a violation of any provision of this chapter, of any rule adopted pursuant thereto, of any applicable uniform firesafety standard adopted pursuant to s. 633.206 which is not adequately addressed by any alternative requirements adopted on a local level, or of any minimum firesafety standard adopted pursuant to s. 394.879.
(b) A substantial violation of an applicable minimum firesafety standard adopted pursuant to s. 633.208 which is not reasonably addressed by any alternative requirement imposed at the local level, or an unreasonable interpretation of an applicable minimum firesafety standard, and which violation or interpretation clearly constitutes a danger to lifesafety.
(c) A building or structure which is in a dilapidated condition and as a result thereof creates a danger to life, safety, or property.
(d) A building or structure which contains explosive matter or flammable liquids or gases constituting a danger to life, safety, or property.
(2)(a) If, during the conduct of a firesafety inspection authorized by ss. 633.216 and 633.218, it is determined that a violation described in this section exists which poses an immediate danger to the public health, safety, or welfare, the State Fire Marshal may issue an order to vacate the building in question, which order shall be immediately effective and shall be an immediate final order under s. 120.569(2)(n). With respect to a facility under the jurisdiction of a district school board or community college board of trustees, the order to vacate shall be issued jointly by the district superintendent or college president and the State Fire Marshal.
(b) The State Fire Marshal may seek an injunction in the circuit court of the county in which the building is located to enforce an order issued pursuant to this subsection.
(3) A person who violates or fails to comply with any order under subsection (1) or subsection (2) commits a misdemeanor, punishable as provided in s. 633.124.
History.s. 10, ch. 65-216; s. 4, ch. 67-78; ss. 13, 35, ch. 69-106; s. 3, ch. 71-141; s. 21, ch. 78-95; s. 7, ch. 84-243; s. 11, ch. 87-287; s. 14, ch. 95-379; s. 276, ch. 96-410; s. 1743, ch. 97-102; s. 49, ch. 99-3; s. 1398, ch. 2003-261; s. 32, ch. 2013-183.
Note.Former s. 633.161.
PART III
FIRE PROTECTION AND SUPPRESSION
633.302 Florida Fire Safety Board; membership; duties; meetings; officers; quorum; compensation; seal.
633.304 Fire suppression equipment; license to install or maintain.
633.306 Requirements for installation, inspection, and maintenance of fire suppression equipment.
633.308 Standard service tag required on all fire extinguishers and preengineered systems; serial number required on all portable fire extinguishers; standard inspection tags required on all fire protection systems.
633.312 Inspection of fire control systems, fire hydrants, and fire protection systems.
633.314 Sale or use of certain types of fire extinguishers prohibited; penalty.
633.316 Fire suppression system contractors; disciplinary action.
633.318 Certificate application and issuance; permit issuance; examination and investigation of applicant.
633.322 County, municipal, and special district powers; effect of ch. 75-240.
633.324 Records concerning applicant; extent of confidentiality.
633.326 Certificate effective statewide; not transferable.
633.328 Issuance of certificate to individuals and business organizations.
633.332 Certificate; expiration; renewal; inactive certificate; continuing education.
633.334 Requirements for installation, inspection, and maintenance of fire protection systems.
633.336 Contracting without certificate prohibited; violations; penalty.
633.338 Disciplinary action; fire protection system contractors; grounds for denial, nonrenewal, suspension, or revocation of certificate or permit.
633.342 Violations subject to injunction.
633.344 Application of law regulating contracting and contractors.
633.346 Jurisdiction of State Fire Marshal over alarm system contractors and certified unlimited electrical contractors.
633.348 Requirements for fire alarm system equipment.
633.3482 Prohibited acts regarding alarm system contractors or certified unlimited electrical contractors; penalties.
633.302 Florida Fire Safety Board; membership; duties; meetings; officers; quorum; compensation; seal.
(1) The Florida Fire Safety Board is created consisting of seven members who are residents of this state. One shall be the State Fire Marshal, or her or his designee who shall be an administrative employee of the marshal; one shall be an administrative officer from a building department representing an incorporated municipality or a county; one shall be an administrative officer from a fire department representing an incorporated municipality or a county; two shall be contractors licensed pursuant to s. 633.318; and two shall be persons who hold valid licenses under s. 633.304.
(2)(a) To be eligible for appointment, each contractor must personally hold a current certificate of competency and a current license issued by the division, together with an unexpired occupational license to operate as a contractor issued by an incorporated municipality or a county; be actively engaged in such business and have been so engaged for a period of not less than 5 consecutive years before the date of her or his appointment; and be a resident of the state.
(b) To be eligible for appointment, each fire equipment dealer must personally hold a current Class A, B, or C and Class D fire equipment dealer license issued by the division, together with an unexpired occupational license to operate as a fire equipment dealer issued by an incorporated municipality or a county; must be actively engaged in such business and have been so engaged for a period of not less than 5 consecutive years before the date of appointment; and must be a resident of this state.
(3) The State Fire Marshal’s term on the board, or that of her or his designee, shall coincide with the State Fire Marshal’s term of office. All terms are for 4 years and expire on June 30 of the last year of the term. When the term of a member expires, the State Fire Marshal shall appoint a member to fill the vacancy for a term of 4 years. The State Fire Marshal may remove any appointed member for cause. A vacancy in the membership of the board for any cause must be filled by appointment by the State Fire Marshal for the balance of the unexpired term.
(4) The board shall act in an advisory capacity to the State Fire Marshal and shall meet regularly as the need presents itself. The board shall have the authority to review complaints and disputed administrative action and make recommendations for disciplinary action to the division at the request of the licenseholder, permitholder, or certificateholder. The board will serve in an advisory capacity to the division regarding rules, codes, standards, interpretations, and training. As soon as practicable after July 1, 2013, the board shall meet to elect officers from its membership, whose terms shall expire on June 30 and annually thereafter. A majority of the board shall constitute a quorum. A member of the advisory board may not be paid a salary as such member, but shall be reimbursed for necessary expenses while attending advisory board meetings, including travel in the performance of her or his duties, as provided in s. 112.061.
(5) The board shall adopt a seal for its use containing the words “Florida Fire Safety Board.”
History.ss. 6, 7, ch. 75-240; s. 4, ch. 78-323; ss. 1, 2, 3, ch. 81-264; s. 1, ch. 82-46; s. 13, ch. 84-243; ss. 1, 3, ch. 87-181; s. 5, ch. 91-429; s. 16, ch. 93-276; s. 1, ch. 97-19; s. 440, ch. 97-102; s. 5, ch. 97-124; s. 34, ch. 2013-183; s. 39, ch. 2018-102.
Note.Former s. 633.511.
633.304 Fire suppression equipment; license to install or maintain.
(1) It is unlawful for any organization or individual to engage in the business of servicing, repairing, recharging, testing, marking, inspecting, installing, or hydrotesting any fire extinguisher or preengineered system in this state except in conformity with this chapter. Each organization or individual that engages in such activity must possess a valid and subsisting license issued by the division. All fire extinguishers and preengineered systems required by statute or by rule must be serviced by an organization or individual licensed under this chapter. A licensee who receives appropriate training shall not be prohibited by a manufacturer from servicing any particular brand of fire extinguisher or preengineered system. The licensee is legally qualified to act for the business organization in all matters connected with its business, and the licensee must supervise all activities undertaken by such business organization. Each licensee shall maintain a specific business location. A further requirement, in the case of multiple locations where such servicing or recharging is taking place, is that each licensee who maintains more than one place of business where actual work is carried on must possess an additional license, as set forth in this section, for each location, except that a licensed individual may not qualify for more than five locations. A licensee is limited to a specific type of work performed depending upon the class of license held. Licenses are required for the following:
(a) Class A: To service, recharge, repair, install, or inspect all types of fire extinguishers and to conduct hydrostatic tests on all types of fire extinguishers.
(b) Class B: To service, recharge, repair, install, or inspect all types of fire extinguishers, including recharging carbon dioxide units and conducting hydrostatic tests on all types of fire extinguishers, except carbon dioxide units.
(c) Class C: To service, recharge, repair, install, or inspect all types of fire extinguishers, except recharging carbon dioxide units, and to conduct hydrostatic tests on all types of fire extinguishers, except carbon dioxide units.
(d) Class D: To service, repair, recharge, hydrotest, install, or inspect all types of preengineered fire extinguishing systems.

Any fire equipment dealer licensed pursuant to this subsection who does not want to engage in the business of servicing, inspecting, recharging, repairing, hydrotesting, or installing halon equipment must file an affidavit on a form provided by the division so stating. Licenses will be issued by the division to show the work authorized thereunder. It is unlawful, unlicensed activity for a person or firm to falsely hold himself or herself or a business organization out to perform any service, inspection, recharge, repair, hydrotest, or installation except as specifically described in the license. A fire equipment dealer licensed pursuant to this subsection who wishes to withdraw a previously filed halon equipment exemption affidavit and engage in the business of servicing, inspecting, recharging, repairing, hydrotesting, or installing halon equipment must submit a written statement requesting the withdrawal to the division. The dealer must also submit to an inspection by the State Fire Marshal or her or his designee in order to determine that the dealer possesses the equipment required to service, inspect, recharge, repair, hydrotest, or install halon equipment.

(2) A person who holds a valid fire equipment dealer license may maintain such license in an inactive status during which time he or she may not engage in any work under the definition of the license held. An inactive status license is void 4 years after the approval date of the inactive status application. To maintain inactive status, the inactive licensee must submit proof of continuing education and the inactive status fee before December 31 of each odd-numbered year.
(3) Each individual actually performing the work of servicing, recharging, repairing, hydrotesting, installing, testing, or inspecting fire extinguishers or preengineered systems must possess a valid and subsisting permit issued by the division. Permittees are limited as to specific type of work performed to allow work no more extensive than the class of license held by the licensee under whom the permittee is working. Permits will be issued by the division as follows:
(a) Portable permit: “Portable permittee” means a person who is limited to performing work no more extensive than the employing or contractually related licensee in the servicing, recharging, repairing, installing, or inspecting all types of portable fire extinguishers.
(b) Preengineered permit: “Preengineered permittee” means a person who is limited to the servicing, recharging, repairing, installing, or inspecting of all types of preengineered fire extinguishing systems.

Any fire equipment permittee licensed pursuant to this subsection who does not want to engage in servicing, inspecting, recharging, repairing, hydrotesting, or installing halon equipment must file an affidavit on a form provided by the division so stating. Permits will be issued by the division to show the work authorized thereunder. It is unlawful, unlicensed activity for a person or firm to falsely hold himself or herself out to perform any service, inspection, recharge, repair, hydrotest, or installation except as specifically described in the permit.

(4)(a) Such licenses and permits shall be issued by the division for 2 years beginning January 1, 2000, and each 2-year period thereafter and expiring December 31 of the second year. All licenses or permits issued will expire on December 31 of each odd-numbered year. The failure to renew a license or permit by December 31 of the second year will cause the license or permit to become inoperative. The holder of an inoperative license or permit may not engage in any activities for which a license or permit is required by this section. A license or permit which is inoperative because of the failure to renew it shall be restored upon payment of the applicable fee plus a penalty equal to the applicable fee, if the application for renewal is filed no later than the following March 31. If the application for restoration is not made before the March 31st deadline, the fee for restoration shall be equal to the original application fee and the penalty provided for herein, and, in addition, the State Fire Marshal shall require reexamination of the applicant. The fee for a license or permit issued for 1 year or less shall be prorated at 50 percent of the applicable fee for a biennial license or permit.
(b) After initial licensure, each licensee or permittee must successfully complete a course or courses of continuing education for fire equipment technicians of at least 16 hours. A license or permit may not be renewed unless the licensee or permittee produces documentation of the completion of at least 16 hours of continuing education for fire equipment technicians during the biennial licensure period. A person who is both a licensee and a permittee shall complete 16 hours of continuing education during each renewal period. Each licensee shall ensure that all permittees in his or her employment or through a contractual agreement meet their continuing education requirements. The State Fire Marshal shall adopt rules describing the continuing education requirements and shall have the authority upon reasonable belief, to audit a fire equipment dealer to determine compliance with continuing education requirements.
(c) The forms of such licenses and permits and applications therefor must be prescribed by the State Fire Marshal; in addition to such other information and data as that officer determines is appropriate and required for such forms, there must be included in such forms the following matters. Each such application must be in such form as to provide that the data and other information set forth therein shall be sworn to by the applicant or, if a corporation, by an officer thereof. An application for a permit must include the name of the licensee employing, or contractually related to, such permittee, and the permit issued in pursuance of such application must also set forth the name of such licensee. A permit is valid solely for use by the holder thereof in his or her employment by, or contractual relationship with, the licensee named in the permit.
(d) A license of any class may not be issued or renewed by the division and a license of any class does not remain operative unless:
1. The applicant has submitted to the State Fire Marshal evidence of registration as a Florida corporation or evidence of compliance with s. 865.09.
2. The State Fire Marshal or his or her designee has by inspection determined that the applicant possesses the equipment required for the class of license sought. The State Fire Marshal shall give an applicant a reasonable opportunity to correct any deficiencies discovered by inspection. To obtain such inspection, an applicant with facilities located outside this state must:
a. Provide a notarized statement from a professional engineer licensed by the applicant’s state of domicile certifying that the applicant possesses the equipment required for the class of license sought and that all such equipment is operable; or
b. Allow the State Fire Marshal or her or his designee to inspect the facility. All costs associated with the State Fire Marshal’s inspection must be paid by the applicant. The State Fire Marshal, in accordance with s. 120.54, may adopt rules to establish standards for the calculation and establishment of the amount of costs associated with any inspection conducted by the State Fire Marshal under this section. Such rules must include procedures for invoicing and receiving funds in advance of the inspection.
3. The applicant has submitted to the State Fire Marshal proof of insurance providing coverage for comprehensive general liability for bodily injury and property damage, products liability, completed operations, and contractual liability. The State Fire Marshal shall adopt rules providing for the amounts of such coverage, but such amounts may not be less than $300,000 for Class A or Class D licenses, $200,000 for Class B licenses, and $100,000 for Class C licenses; and the total coverage for any class of license held in conjunction with a Class D license may not be less than $300,000. The State Fire Marshal may, at any time after the issuance of a license or its renewal, require upon demand, and in no event more than 30 days after notice of such demand, the licensee to provide proof of insurance, on the insurer’s form, containing confirmation of insurance coverage as required by this chapter. Failure, for any length of time, to provide proof of insurance coverage as required must result in the immediate suspension of the license until proof of proper insurance is provided to the State Fire Marshal. An insurer that provides such coverage shall notify the State Fire Marshal of any change in coverage or of any termination, cancellation, or nonrenewal of any coverage.
4. The applicant applies to the State Fire Marshal, provides proof of experience, and successfully completes a prescribed training course that includes both written and practical training approved by the State Fire Marshal as applicable to the class of license being sought. This subparagraph does not apply to any holder of or applicant for a permit under paragraph (g) or to a business organization or a governmental entity seeking initial licensure or renewal of an existing license solely for the purpose of inspecting, servicing, repairing, marking, recharging, and maintaining fire extinguishers used and located on the premises of and owned by such organization or entity.
5. The applicant has a current retester identification number that is appropriate for the license for which the applicant is applying and that is listed with the United States Department of Transportation.
6. The applicant has passed, with a grade of at least 70 percent, a written examination testing his or her knowledge of the rules and statutes governing the activities authorized by the license and demonstrating his or her knowledge and ability to perform those tasks in a competent, lawful, and safe manner. Such examination must be developed and administered by the State Fire Marshal, or his or her designee in accordance with policies and procedures of the State Fire Marshal. An applicant shall pay a nonrefundable examination fee of $50 for each examination or reexamination scheduled. A reexamination may not be scheduled sooner than 30 days after any administration of an examination to an applicant. An applicant may not be permitted to take an examination for any level of license more than a total of four times during 1 year, regardless of the number of applications submitted. As a prerequisite to licensure of the applicant, he or she:
a. Must be at least 18 years of age.
b. Must have 4 years of proven experience as a fire equipment permittee at a level equal to or greater than the level of license applied for or have a combination of education and experience determined to be equivalent thereto by the State Fire Marshal. Having held a permit at the appropriate level for the required period constitutes the required experience.
c. Must not have been convicted of a felony or a crime punishable by imprisonment of 1 year or more under the law of the United States or of any state thereof or under the law of any other country. “Convicted” means a finding of guilt or the acceptance of a plea of guilty or nolo contendere in any federal or state court or a court in any other country, without regard to whether a judgment of conviction has been entered by the court having jurisdiction of the case. If an applicant has been convicted of any such felony, the applicant is excluded from licensure for a period of 4 years after expiration of sentence or final release by the Florida Commission on Offender Review unless the applicant, before the expiration of the 4-year period, has received a full pardon or has had her or his civil rights restored.

This subparagraph does not apply to any holder of or applicant for a permit under paragraph (g) or to a business organization or a governmental entity seeking initial licensure or renewal of an existing license solely for the purpose of inspecting, servicing, repairing, marking, recharging, hydrotesting, and maintaining fire extinguishers used and located on the premises of and owned by such organization or entity.

(e) A fire equipment dealer licensed under this section may apply to convert the license currently held to a higher licensing category, if the licensed dealer:
1. Submits an application for the license on a form in conformance with paragraph (c). The application must be accompanied by a fee as prescribed in s. 633.132 for the type of license requested.
2. Provides evidence of 2 years’ experience as a licensed dealer and meets such relevant educational requirements as are established by rule by the State Fire Marshal for purposes of upgrading a license.
3. Meets the requirements of paragraph (d).
(f) A fire equipment dealer licensed under this section may apply to convert the license currently held to a lower licensing category, if the licensed dealer:
1. Submits an application for the license on a form in conformance with paragraph (c). The application must be accompanied by a fee as prescribed in s. 633.132 for the type of license requested.
2. Submits proof of insurance providing coverage meeting the requirements prescribed in subparagraph (d)3.
3. Submits to an inspection of the facility to ensure all equipment associated with the higher class of license has been removed and submits the required reinspection fee.
(g) A permit of any class may not be issued or renewed to a person by the division, and a permit of any class does not remain operative, unless the person has:
1. Submitted a nonrefundable examination fee in the amount of $50.
2. Successfully completed a training course that includes both written and practical training approved by the State Fire Marshal as applicable to the class of license being sought.
3. Passed, with a grade of at least 70 percent, a written examination testing his or her knowledge of the rules and statutes governing the activities authorized by the permit and demonstrating his or her knowledge and ability to perform those tasks in a competent, lawful, and safe manner. Such examination must be developed and administered by the State Fire Marshal in accordance with the policies and procedures of the State Fire Marshal. An examination fee must be paid for each examination scheduled. A reexamination may not be scheduled sooner than 30 days after any administration of an examination to an applicant. An applicant may not be permitted to take an examination for any level of permit more than four times during 1 year, regardless of the number of applications submitted. As a prerequisite to taking the permit examination, the applicant must be at least 16 years of age.
(h) An applicant for a license or permit under this section who fails the examination may take it three more times during the 1-year period after he or she originally filed an application for the examination. If the applicant fails the examination within 1 year after the application date and he or she seeks to retake the examination, he or she must file a new application, pay the application and examination fees, and successfully complete a prescribed training course that includes both written and practical training approved by the State Fire Marshal as applicable to the class of license being sought. The applicant may not submit a new application within 6 months after the date of his or her fourth reexamination. An applicant who passes the examination but does not meet the remaining qualifications prescribed by law and rule within 1 year after the application date must file a new application, pay the application and examination fee, successfully complete a prescribed training course that includes both written and practical training approved by the State Fire Marshal as applicable to the class of license being sought, and pass the written examination.
(5)(a) No one that is being trained shall perform work requiring a permit unless an individual possessing a valid and current fire equipment permit for the type of work performed is physically present. The trainee must:
1. Be 18 years of age.
2. Possess on his or her person at all times a valid Florida driver license or a valid state identification card, issued by the Department of Highway Safety and Motor Vehicles. A trainee must produce identification to the State Fire Marshal or his or her designated representative upon demand.
(b) No more than two trainees shall be under the supervision of a single trainer, who shall be directly responsible for all work performed by any trainee while under his or her supervision. No trainee shall perform any work not within the scope of the license or permit held by the fire equipment dealer or permittee directly supervising his or her work.
(6) The State Fire Marshal shall adopt rules providing for the approval of the time, place, and curriculum of each training course required by this section.
(7) Every permittee must have a valid and subsisting permit upon his or her person at all times while engaging in the servicing, recharging, repairing, testing, inspecting, or installing of fire extinguishers and preengineered systems, and every licensee or permittee must be able to produce such license or permit upon demand. In addition, every permittee shall at all times carry an identification card containing his or her photograph and other identifying information as prescribed by the State Fire Marshal or the State Fire Marshal’s designee, which shall be produced on demand. The State Fire Marshal shall supply this card at a fee which shall be related to the cost of producing the card.
(8) The fees collected for any such licenses and permits and the filing fees for license and permit examination are hereby appropriated for the use of the State Fire Marshal in the administration of this chapter and shall be deposited in the Insurance Regulatory Trust Fund.
(9) This section does not apply to inspections by fire chiefs, fire inspectors, fire marshals, or insurance company inspectors.
(10) All fire extinguishers and preengineered systems that are required by statute or by rule must be serviced, recharged, repaired, hydrotested, tested, inspected, and installed in compliance with this chapter and with the rules adopted by the State Fire Marshal. The State Fire Marshal may adopt by rule the standards of the National Fire Protection Association and of other reputable national organizations.
(11) If the licensee leaves the business organization or dies, the business organization shall immediately notify the State Fire Marshal of the licensee’s departure, shall return the license to the State Fire Marshal, and shall have a grace period of 60 days in which to license another person under the provisions of this chapter, failing which the business shall no longer perform those activities for which a license under this section is required.
History.s. 6, ch. 65-216; s. 4, ch. 67-78; ss. 13, 35, ch. 69-106; s. 1, ch. 71-141; s. 3, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-457; ss. 1, 8, ch. 78-141; s. 2, ch. 81-318; s. 2, ch. 84-243; ss. 1, 2, ch. 85-128; s. 8, ch. 87-287; s. 15, ch. 89-233; s. 3, ch. 90-359; s. 3, ch. 91-189; s. 4, ch. 91-429; s. 3, ch. 93-276; s. 37, ch. 95-211; s. 10, ch. 95-379; s. 423, ch. 97-102; s. 1, ch. 97-124; s. 2, ch. 98-170; s. 53, ch. 98-419; s. 28, ch. 99-254; s. 1, ch. 2000-155; s. 5, ch. 2002-287; s. 1395, ch. 2003-261; s. 51, ch. 2010-176; s. 35, ch. 2013-183; s. 12, ch. 2014-191; s. 40, ch. 2018-102; s. 27, ch. 2021-113.
Note.Former s. 633.061.
633.306 Requirements for installation, inspection, and maintenance of fire suppression equipment.
(1) The requirements for installation of fire extinguishers and preengineered systems are as follows:
(a) Fire equipment dealers shall be licensed under s. 633.304.
(b) Equipment supplied shall be listed by a nationally recognized testing laboratory, such as Underwriters Laboratories, Inc., or Factory Mutual Laboratories, Inc. Equipment supplied for new installations or alterations of existing systems must be currently listed as described in this section. The State Fire Marshal shall adopt by rule procedures for determining whether a laboratory is nationally recognized, taking into account the laboratory’s facilities, procedures, use of nationally recognized standards, and any other criteria reasonably calculated to reach an informed determination.
(c) Equipment shall be installed in accordance with the applicable standards of the National Fire Protection Association and the manufacturer’s drawings and specifications, using only components and parts specified by the manufacturer or listed as equal parts by a nationally recognized testing laboratory, such as Underwriters Laboratories, Inc., or Factory Mutual Laboratories, Inc.
(d) Each piece of equipment supplied shall be guaranteed for a period of 1 year against defects in material or operation.
(e) The fire equipment dealer shall furnish the consumer with: the manufacturer’s descriptive literature, including the specifications and maintenance requirements as approved by the nationally recognized testing laboratory; the operating instructions for all equipment installed; the mechanical drawings and specifications for proper installation and use of equipment; and a diagram of the final installation, if applicable.
(2) Equipment shall be inspected, serviced, and maintained in accordance with the manufacturer’s maintenance procedures and with the applicable National Fire Protection Association standards.
History.s. 4, ch. 75-240; s. 2, ch. 80-342; s. 3, ch. 84-243; s. 16, ch. 89-233; s. 4, ch. 91-189; s. 3, ch. 98-170; s. 54, ch. 98-419; s. 36, ch. 2013-183; s. 30, ch. 2019-140.
Note.Former s. 633.065.
633.308 Standard service tag required on all fire extinguishers and preengineered systems; serial number required on all portable fire extinguishers; standard inspection tags required on all fire protection systems.
(1) The State Fire Marshal shall adopt by rule specifications as to the size, shape, color, and information and data contained thereon of service tags to be attached to all fire extinguishers and preengineered systems required by statute or by rule, whether they be portable, stationary, or on wheels when they are placed in service, installed, serviced, repaired, tested, recharged, or inspected. Fire extinguishers may be tagged only after meeting all standards as set forth by this chapter, the standards of the National Fire Protection Association, and manufacturer’s specifications. Preengineered systems may be tagged only after a system has been inspected, serviced, installed, repaired, tested, recharged, and hydrotested in compliance with this chapter, the standards of the National Fire Protection Association, and the manufacturer’s specifications, and after a report, as specified by rule, has been completed in detail, indicating any and all deficiencies or deviations from the manufacturer’s specifications and the standards of the National Fire Protection Association. A copy of the inspection report shall be provided to the owner at the time of inspection, and, if a system is found to be in violation of this chapter, the manufacturer’s specifications, or the standards of the National Fire Protection Association, a copy shall be forwarded to the state or local authority having jurisdiction within 30 days from the date of service. It shall be unlawful to place in service, service, test, repair, inspect, install, hydrotest, or recharge any fire extinguisher or preengineered system without attaching one of these tags completed in detail, including the actual month work was performed, or to use a tag not meeting the specifications set forth by the State Fire Marshal.
(2) All portable fire extinguishers required by statute or by rule must be listed by Underwriters Laboratories, Inc., or approved by Factory Mutual Laboratories, Inc., or listed by a nationally recognized testing laboratory in accordance with procedures adopted pursuant to s. 633.314(2), and carry an Underwriters Laboratories, Inc., or manufacturer’s serial number. These listings, approvals, and serial numbers may be stamped on the manufacturer’s identification and instructions plate or on a separate Underwriters Laboratories, Inc., or Factory Mutual Laboratories, Inc., plate soldered or attached to the extinguisher shell in some permanent manner.
(3) The State Fire Marshal shall adopt by rule specifications as to the size, shape, color, information, and data contained thereon of inspection tags to be attached to all types of fire protection systems and information required on an inspection report of such an inspection.
History.s. 7, ch. 65-216; s. 4, ch. 67-78; ss. 13, 35, ch. 69-106; s. 2, ch. 71-141; s. 17, ch. 89-233; s. 38, ch. 95-211; s. 2, ch. 97-124; s. 4, ch. 98-170; s. 55, ch. 98-419; s. 24, ch. 2005-147; s. 37, ch. 2013-183.
Note.Former s. 633.071.
633.312 Inspection of fire control systems, fire hydrants, and fire protection systems.
(1) The State Fire Marshal shall have the right to inspect any fire control system during and after construction to determine that such system meets the standards set forth in the laws and rules of the state.
(2) Fire hydrants and fire protection systems installed in public and private properties, except one-family or two-family dwellings, shall be inspected following procedures established in the nationally recognized inspection, testing, and maintenance standards publications NFPA-24 and NFPA-25 as set forth in the edition adopted by the State Fire Marshal. Quarterly, annual, 3-year, and 5-year inspections consistent with the contractual provisions with the owner shall be conducted by the certificateholder or permittees employed by the certificateholder pursuant to s. 633.318, except that:
(a) Public fire hydrants owned by a governmental entity shall be inspected following procedures established in the inspection, testing, and maintenance standards adopted by the State Fire Marshal or equivalent standards such as those contained in the latest edition of the American Water Works Association’s Manual M17, “Installation, Field Testing, and Maintenance of Fire Hydrants.”
(b) County, municipal, and special district utilities may perform fire hydrant inspections required by this section using designated employees. Such designated employees need not be certified under this chapter. However, counties, municipalities, or special districts that use designated employees are responsible for ensuring that the designated employees are qualified to perform such inspections.
(3)(a) The inspecting contractor shall provide to the building owner or hydrant owner and the local authority having jurisdiction a copy of the applicable uniform summary inspection report established under this chapter. The local authority having jurisdiction may accept uniform summary inspection reports by United States mail, by hand delivery, by electronic submission, or through a third-party vendor that collects the reports on behalf of the local authority having jurisdiction.
(b) The State Fire Marshal shall adopt rules to implement a uniform summary inspection report and submission procedures to be used by all third-party vendors and local authorities having jurisdiction. For purposes of this section, a uniform summary inspection report must record the address where the fire protection system or hydrant is located, the company and person conducting the inspection and their license number, the date of the inspection, and the fire protection system or hydrant inspection status, including a brief summary of each deficiency, critical deficiency, noncritical deficiency, or impairment found. A contractor’s detailed inspection report is not required to follow the uniform summary inspection report format. The State Fire Marshal shall establish by rule a submission procedure for each means provided under paragraph (a) by which a local authority having jurisdiction may accept uniform summary inspection reports. Each of the submission procedures must allow a contractor to attach additional documents with the submission of a uniform summary inspection report, including a physical copy of the contractor’s detailed inspection report. A submission procedure may not require a contractor to submit information contained within the detailed inspection report unless the information is required to be included in the uniform summary inspection report.
(4) The maintenance of fire hydrant and fire protection systems as well as corrective actions on deficient systems is the responsibility of the owner of the system or hydrant. Equipment requiring periodic testing or operation to ensure its maintenance shall be tested or operated as specified in the Fire Prevention Code, Life Safety Code, National Fire Protection Association standards, or as directed by the appropriate authority, provided that such appropriate authority may not require a sprinkler system not required by the Fire Prevention Code, Life Safety Code, or National Fire Protection Association standards to be removed regardless of its condition. This section does not prohibit governmental entities from inspecting and enforcing firesafety codes.
(5) At least once each year, each fire hydrant shall be opened fully and the water allowed to flow until all foreign materials have cleared the hydrant. The flow shall be maintained for not less than 1 minute.
(6) If a fire hydrant is made nonfunctional by the closing of a water supply valve, the valve must immediately be tagged with a red tag that is boldly marked “nonfunctional” and the local fire authority notified that the hydrant is nonfunctional.
History.s. 7, ch. 78-141; s. 25, ch. 2005-147; s. 9, ch. 2006-65; s. 2, ch. 2010-173; s. 53, ch. 2010-176; s. 38, ch. 2013-183; s. 31, ch. 2019-140.
Note.Former s. 633.082.
633.314 Sale or use of certain types of fire extinguishers prohibited; penalty.
(1)(a) It is unlawful to have for use any of the following types of fire extinguishers:
1. Carbon tetrachloride;
2. Chlorobromomethane;
3. Dibromodifluoromethane (commonly known as Halon 1202);
4. Dichlorodifluoromethane;
5. Azeotropic chloromethane;
6. 1,2 dibromo-2-chloro-1, 1,2 trifluoroethane;
7. 1,2 dibromo-2, 2-difluoroethane;
8. Methyl bromide;
9. Ethylene dibromide;
10. Hydrogen bromide;
11. Methylene bromide;
12. Bromodifluoromethane;
13. Any other toxic or poisonous vaporizing liquid fire extinguishers using extinguishing agents determined by the State Fire Marshal to be unacceptably harmful; and
14. Inverting water fire extinguishers.
(b) It is unlawful to offer for sale, sell, or give in this state any of the types of fire extinguishers listed in paragraph (a).
(2) It is unlawful for any person, directly or through an agent, to sell, offer for sale, or give in this state any make, type, or model of fire extinguisher, either new or used, unless such make, type, or model of extinguisher has first been tested and is currently approved or listed by Underwriters Laboratories, Inc., Factory Mutual Laboratories, Inc., or another testing laboratory recognized by the State Fire Marshal as nationally recognized in accordance with procedures adopted by rule, taking into account the laboratory’s facilities, procedures, use of nationally recognized standards, and any other criteria reasonably calculated to reach an informed determination, and unless such extinguisher carries an Underwriters Laboratories, Inc., or manufacturer’s serial number. Such serial number must be permanently affixed on the manufacturer’s identification and instruction plate.
(3) A person who violates this section commits a misdemeanor of the second degree, punishable as provided in s. 775.082 or s. 775.083.
History.ss. 1, 2, 3, ch. 70-417; s. 658, ch. 71-136; s. 2, ch. 78-141; s. 5, ch. 84-243; s. 18, ch. 89-233; s. 39, ch. 2013-183; s. 41, ch. 2018-102.
Note.Former s. 633.083.
633.316 Fire suppression system contractors; disciplinary action.
(1) The violation of any provision of this chapter or any rule adopted pursuant hereto or the failure or refusal to comply with any notice or order to correct a violation or any cease and desist order by a person who possesses a license or permit issued pursuant to s. 633.304 is cause for denial, nonrenewal, revocation, or suspension of such license or permit by the State Fire Marshal after such officer has determined that the person committed such violation. An order of suspension must state the period of such suspension, which period may not be in excess of 2 years from the date of such order. An order of revocation may be entered for a period not exceeding 5 years. Such orders shall effect suspension or revocation of all licenses or permits issued by the division to the person, and during such period a license or permit may not be issued by the division to such person. During the suspension or revocation of any license or permit, the former licensee or permittee may not engage in or attempt or profess to engage in any transaction or business for which a license or permit is required under this chapter or directly or indirectly own, control, or be employed in any manner by any firm, business, or corporation for which a license or permit under this chapter is required. If, during the period between the beginning of proceedings and the entry of an order of suspension or revocation by the State Fire Marshal, a new license or permit has been issued by the division to the person so charged, the order of suspension or revocation shall operate to suspend or revoke such new license or permit held by such person.
(2) The department shall not, so long as the revocation or suspension remains in effect, grant any new license or permit for the establishment of any new firm, business, or corporation of any person or qualifier that has or will have the same or similar management, ownership, control, employees, permittees, or licensees, or will use a same or similar name as a previously revoked or suspended firm, business, corporation, person, or qualifier.
(3) The State Fire Marshal may deny, nonrenew, suspend, or revoke the license or permit of:
(a) Any person, firm, or corporation the license of which under this chapter has been suspended or revoked;
(b) Any firm or corporation if an officer, qualifier, director, stockholder, owner, or person interested directly or indirectly in the firm or corporation has had his or her license or permit under this chapter suspended or revoked; or
(c) Any person who is or has been an officer, qualifier, director, stockholder, or owner of a firm or corporation, or who was interested directly or indirectly in a firm or corporation, the license or permit of which has been suspended or revoked under this chapter.
(4) In addition to the grounds set forth in subsection (1), it is cause for denial, nonrenewal, revocation, or suspension of a license or permit by the State Fire Marshal if she or he determines that the licensee or permittee has:
(a) Rendered inoperative a fire extinguisher or preengineered system required by statute or by rule, except during such time as the extinguisher or preengineered system is being inspected, serviced, repaired, hydrotested, or recharged, or except pursuant to court order.
(b) Falsified any record required to be maintained by this chapter or rules adopted pursuant hereto.
(c) Improperly serviced, recharged, repaired, hydrotested, tested, or inspected a fire extinguisher or preengineered system.
(d) While holding a permit or license, allowed another person to use the permit number or license number, or used a license number or permit number other than her or his valid license number or permit number.
(e) Failed to provide proof of insurance to the State Fire Marshal or failed to maintain in force the insurance coverage required by s. 633.304.
(f) Failed to obtain, retain, or maintain one or more of the qualifications for a license or permit as specified in this chapter.
(g) Made a material misstatement, misrepresentation, or committed a fraud in obtaining or attempting to obtain a license or permit.
(h) Failed to notify the State Fire Marshal, in writing, within 30 days after a change of residence, principal business address, or name.
(5) In addition, the department shall not issue a new license or permit if it finds that the circumstance or circumstances for which the license or permit was previously revoked or suspended still exist or are likely to recur.
History.s. 4, ch. 71-141; s. 21, ch. 78-95; s. 8, ch. 84-243; s. 12, ch. 87-287; s. 20, ch. 89-233; s. 7, ch. 93-276; s. 430, ch. 97-102; s. 5, ch. 98-170; s. 56, ch. 98-419; s. 1399, ch. 2003-261; s. 40, ch. 2013-183; s. 158, ch. 2014-17.
Note.Former s. 633.162.
633.318 Certificate application and issuance; permit issuance; examination and investigation of applicant.
(1) To obtain a fire protection system contractor’s certificate, an applicant shall submit to the division an application in writing, on a form provided by the division containing the information prescribed, which shall be accompanied by the fee fixed herein, containing a statement that the applicant desires the issuance of a certificate and stating the class of certificate requested.
(2)(a) Examinations shall be administered by the division and held at times and places within the state as the division determines, but there shall be at least two examinations a year. Each applicant shall take and pass an objective, written examination of her or his fitness for a certificate in the class for which the application is requested. There shall be a type of examination for each class of certificate for contractors as defined in s. 633.102. The examination must test the applicant’s ability to lay out, fabricate, install, alter, repair, and inspect fire protection systems and their appurtenances and must test the applicant’s fitness in business and financial management. The test must be based on applicable standards of the National Fire Protection Association and on relevant Florida and federal laws pertaining to the construction industry, safety standards, administrative procedures, and pertinent technical data.
(b) A passing grade on the examination is 70 percent, and such examinations may be developed by an independent professional testing agency. The tests shall be prepared, administered, and scored in compliance with generally accepted professional testing standards.
(c) The division shall solicit suggestions from affected persons regarding the content of examinations.
(d) A reexamination may not be scheduled sooner than 30 days after any administration of an examination to an applicant.
(e) An applicant may not be examined more than four times during 1 year for certification as a contractor pursuant to this section unless the person is or has been certified and is taking the examination to change classifications. If an applicant does not pass one or more parts of the examination, she or he may take any part of the examination three more times during the 1-year period beginning upon the date she or he originally filed an application to take the examination. If the applicant does not pass the examination within that 1-year period, she or he must file a new application and pay the application and examination fees in order to take the examination or a part of the examination again. However, the applicant may not file a new application sooner than 6 months after the date of her or his last examination. An applicant who passes the examination but does not meet the remaining qualifications as provided in applicable statutes and rules within 1 year after the application date must file a new application, pay the application and examination fee, successfully complete a prescribed training course approved by the State Fire College or an equivalent course approved by the State Fire Marshal, and retake and pass the written examination.
(3)(a) As a prerequisite to taking the examination for certification as a Contractor I, the applicant must be at least 18 years of age, be of good moral character, and possess 4 years’ proven experience in the employment of a fire protection system Contractor I or a combination of equivalent education and experience in both water-based and chemical fire suppression systems.
(b) As a prerequisite to taking the examination for certification as a Contractor II, the applicant must be at least 18 years of age, be of good moral character, and have 4 years of verifiable employment experience with a fire protection system as a Contractor I or Contractor II, or a combination of equivalent education and experience in water-based fire suppression systems.
(c) Required education and experience for certification as a Contractor I, Contractor II, Contractor III, or Contractor IV includes training and experience in both installation and system layout as defined in s. 633.102.
(d) As a prerequisite to taking the examination for certification as a Contractor III, the applicant must be at least 18 years of age, be of good moral character, and have 4 years of verifiable employment experience with a fire protection system as a Contractor I or Contractor II, or a combination of equivalent education and experience in chemical fire suppression systems.
(e) As a prerequisite to taking the examination for certification as a Contractor IV, the applicant must be at least 18 years old, be of good moral character, be licensed as a certified plumbing contractor under chapter 489, and successfully complete a training program acceptable to the State Fire Marshal of not less than 40 contact hours regarding the applicable installation standard used by the Contractor IV as described in NFPA 13D. The State Fire Marshal may adopt rules to administer this subsection.
(f) As a prerequisite to taking the examination for certification as a Contractor V, the applicant must be at least 18 years old, be of good moral character, and have been licensed as a certified underground utility and excavation contractor or certified plumbing contractor pursuant to chapter 489, have verification by an individual who is licensed as a certified utility contractor or certified plumbing contractor pursuant to chapter 489 that the applicant has 4 years’ proven experience in the employ of a certified underground utility and excavation contractor or certified plumbing contractor, or have a combination of education and experience equivalent to 4 years’ proven experience in the employ of a certified underground utility and excavation contractor or certified plumbing contractor.
(g) Within 30 days after the date of the examination, the division shall inform the applicant in writing whether she or he has qualified or not and, if the applicant has qualified, that she or he is eligible to be issued a certificate of competency, subject to compliance with the requirements of subsection (4).
(4) As a prerequisite to issuance of a certificate, the division must require the applicant to submit satisfactory evidence that she or he has obtained insurance providing coverage for comprehensive general liability for bodily injury and property damages, products liability, completed operations, and contractual liability. The division may adopt rules providing for the amount of insurance, but such amount shall not be less than $500,000 for a Contractor I, Contractor II, Contractor III, or Contractor V and shall not be less than $250,000 for a Contractor IV. An insurer which provides such coverage shall notify the division within 30 days of any material change in coverage or any termination, cancellation, or nonrenewal of such coverage. An insurer which fails to so notify the division shall be subject to the penalties provided under s. 624.4211.
(5) Upon satisfaction of the requirements of subsections (1), (2), (3), and (4), the certificate shall be issued forthwith. However, no certificate shall remain in effect if, after issuance, the certificateholder fails to maintain the insurance coverage required by this section.
(6) If an applicant for an original certificate, after having been notified to do so, does not appear for examination or does not pass the examination within 1 year from the date of filing her or his application, the fee paid by the applicant shall be forfeited. New applications for a certificate shall be accompanied by another application fee fixed by this chapter.
(7) The State Fire Marshal may, at any time subsequent to the issuance of the certificate or its renewal, require, upon demand and in no event more than 30 days after notice of the demand, the certificateholder to provide proof of insurance coverage on the insurer’s form containing confirmation of insurance coverage as required by this chapter. Failure to provide proof of insurance coverage as required, for any length of time, shall result in the immediate suspension of the certificate until proof of insurance is provided to the State Fire Marshal.
(8) An individual employed by a Contractor I or Contractor II certificateholder, as established in this section, who will be inspecting water-based fire protection systems as required under s. 633.312, must be issued a permit by the division to conduct such work. The permit is valid solely for use by the holder thereof in his or her employment by the certificateholder named in the permit. A permittee must have a valid and subsisting permit upon his or her person at all times while engaging in inspecting fire protection systems, and a permitholder must be able to produce such a permit upon demand. In addition, a permittee shall, at all times while performing inspections, carry an identification card containing his or her photograph and other identifying information as prescribed by the State Fire Marshal, and the permittee must produce the identification card and information upon demand. The permit and the identification may be one and the same. A permittee is limited as to the specific type of work performed, depending upon the class of certificate held by the certificateholder under whom the permittee is working. The permit class shall be known as a Water-Based Fire Protection Inspector whose permit allows the holder to inspect water sprinkler systems, water spray systems, foam-water sprinkler systems, foam-water spray systems, standpipes, combination standpipes and sprinkler systems, all piping that is an integral part of the system beginning at the point where the piping is used exclusively for fire protection, sprinkler tank heaters, air lines, thermal systems used in connection with sprinklers, and tanks and pumps connected thereto, excluding preengineered systems.
(9) It is the intent of the Legislature that the inspections and testing of automatic fire sprinkler systems for detached one-family dwellings, detached two-family dwellings, and mobile homes be accomplished by the owner, who is responsible for requesting service from a contractor when necessary. It is further intended that the NFPA-25 inspection of exposed underground piping and any attached appurtenances supplying a fire protection system be conducted by a Contractor I or Contractor II.
(10) The State Fire Marshal shall require the National Institute of Certification in Engineering Technologies (NICET), Sub-field of Inspection and Testing of Fire Protection Systems Level II or equivalent training and education as determined by the division as proof that the permitholders are knowledgeable about nationally accepted standards for the inspection of fire protection systems.
(11) It is intended that a certificateholder, or a permitholder who is employed by a certificateholder, conduct inspections required by this chapter. It is understood that after July 1, 2008, employee turnover may result in a depletion of personnel who are certified under the NICET Sub-field of Inspection and Testing of Fire Protection Systems Level II or equivalent training and education as required by the division. A certificateholder may obtain a provisional permit with an endorsement for inspection, testing, and maintenance of water-based fire extinguishing systems for an employee if the employee has initiated procedures for obtaining Level II certification from the National Institute for Certification in Engineering Technologies Sub-field of Inspection and Testing of Fire Protection Systems and achieved Level I certification or an equivalent level as determined by the State Fire Marshal through verification of experience, training, and examination. The division may establish rules to administer this subsection. After 2 years of provisional certification, the employee must have achieved NICET Level II certification or obtain equivalent training and education as determined by the division, or cease performing inspections requiring Level II certification. The provisional permit is valid only for the 2 calendar years after the date of issuance, may not be extended, and is not renewable. After the initial 2-year provisional permit expires, the certificateholder must wait 2 additional years before a new provisional permit may be issued. The intent is to prohibit the certificateholder from using employees who never reach NICET Level II status, or equivalent training and education as determined by the division, by continuously obtaining provisional permits.
History.ss. 9, 17, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-174; s. 1, ch. 77-457; ss. 4, 8, ch. 78-141; s. 3, ch. 80-342; s. 436, ch. 81-259; s. 2, ch. 81-318; ss. 14, 20, ch. 84-243; ss. 1, 2, ch. 85-128; s. 6, ch. 88-209; s. 9, ch. 90-359; s. 4, ch. 91-429; s. 8, ch. 93-154; s. 5, ch. 93-166; s. 18, ch. 93-276; s. 443, ch. 97-102; s. 26, ch. 2005-147; s. 10, ch. 2007-187; s. 55, ch. 2010-176; s. 41, ch. 2013-183; s. 42, ch. 2018-102.
Note.Former s. 633.521.
633.322 County, municipal, and special district powers; effect of ch. 75-240.
(1) This chapter does not limit the power of a municipality, county, or special district to regulate the quality and character of work performed by contractors through a system of permits, fees, and inspections which are designed to secure compliance with, and aid in the implementation of, state and local building laws or to enforce other local laws for the protection of the public health and safety.
(2) This chapter does not limit the power of a municipality, county, or special district to adopt any system of permits requiring submission to and approval by the municipality, county, or special district of plans and specifications for work to be performed by contractors before commencement of the work, except that a municipality, county, or special district may not require a fire protection system contractor’s shop drawings to be sealed by a professional engineer.
(3) An official authorized to issue building or other related permits shall ascertain that the applicant contractor is duly certified before issuing the permit. The evidence shall consist only of the exhibition to him or her of evidence of current certification.
(4) The State Fire Marshal shall inform each county and municipal building department, prior to November 1 of each year, of the names of the certified contractors and the type of certificate held.
History.s. 16, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-457; s. 8, ch. 78-141; s. 2, ch. 81-318; ss. 1, 2, ch. 85-128; s. 34, ch. 89-233; s. 4, ch. 91-429; s. 449, ch. 97-102; s. 3, ch. 98-35; s. 42, ch. 2013-183.
Note.Former s. 633.551.
633.324 Records concerning applicant; extent of confidentiality.
(1) Test material is made confidential by s. 119.071(1)(a). An applicant may waive in writing the confidentiality of his or her examination answer sheet for the purpose of discussion with the State Fire Marshal or his or her staff.
(2) All examination test questions, answer sheets, and grades shall be retained for a period of 2 years following the date of the examination.
History.s. 13, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-457; s. 8, ch. 78-141; s. 2, ch. 81-318; ss. 1, 2, ch. 85-128; s. 8, ch. 88-209; s. 4, ch. 91-429; s. 3, ch. 93-112; s. 19, ch. 93-276; s. 1, ch. 94-188; s. 4, ch. 95-398; s. 444, ch. 97-102; ss. 24, 48, ch. 2004-335; s. 51, ch. 2005-251; s. 43, ch. 2013-183.
Note.Former s. 633.527.
633.326 Certificate effective statewide; not transferable.When a certificateholder desires to engage in contracting in any area of the state, as a prerequisite therefor she or he shall only be required to exhibit to the local building official, tax collector, or other person in charge of the issuance of licenses and building permits in the area, evidence of holding a current certificate, accompanied by the fee for the occupational license and building permit required of other persons. It is a violation of this chapter for a certificateholder to sell or otherwise transfer her or his certificate to another person.
History.s. 9, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-457; s. 8, ch. 78-141; s. 2, ch. 81-318; s. 16, ch. 84-243; ss. 1, 2, ch. 85-128; s. 4, ch. 91-429; s. 445, ch. 97-102; s. 44, ch. 2013-183.
Note.Former s. 633.531.
633.328 Issuance of certificate to individuals and business organizations.
(1) When an individual proposes to do business in her or his own name, certifications, when granted, shall be issued only to that individual.
(2) If the applicant proposing to engage in contracting is a business organization, such as a partnership, corporation, business trust, or other legal entity, the application shall state the name of the partnership and its partners, the name of the corporation and its officers and directors, the name of the business trust and its trustees, or the name of such other legal entity and its members and shall furnish evidence of statutory compliance if a fictitious name is used. Such application shall also show that the person applying for the examination is an employee of and is legally qualified to act for the business organization in all matters connected with its contracting business and that she or he has authority to supervise and will supervise any construction undertaken by such business organization. The certification, when issued upon application of a business organization, shall be in the name of such business organization, and the name of the qualifying individual or individuals shall be noted thereon.
(3)(a) At least one member or supervising employee of the business organization as designated to the State Fire Marshal by such organization shall be certified under this chapter in order for the business organization to hold a current certificate as a contractor. If any individual so certified on behalf of such business organization ceases to be affiliated with such business organization, she or he shall inform the State Fire Marshal as provided in paragraph (b). A certified individual who is the sole contractor on behalf of a business organization may not affiliate simultaneously with another business organization. In addition, if such individual was the only certified individual affiliated with the business organization, the business organization shall immediately notify the State Fire Marshal of the individual’s termination and shall have a grace period of 60 days from the date of termination in which to certify another person under the provisions of this chapter, failing which the certification of the business organization shall expire without further operation of law.
(b) The certified individual shall also inform the State Fire Marshal in writing when she or he proposes to engage in contracting in her or his own name or to affiliate with another business organization, and she or he or such new business organization shall supply the same information to the State Fire Marshal as is required of applicants under this chapter. Each certified individual must pay to the department an amount equal to the original fee for certification of a new business entity.
(c) In the event of the death of a sole proprietor or in the event that a business organization has only one certificateholder and that person dies, the individual’s estate or personal representative or the business organization, as the case may be, shall immediately notify the State Fire Marshal of the individual’s death and shall have a grace period of 60 days from the date of death in which to certify another person under the provisions of this chapter, failing which the certification of the business organization shall expire without further operation of law.
(4) If the certified business organization makes application for an occupational license in any municipality or county of this state, the application must be made with the tax collector in the name of the business organization, and the license, when issued, shall be issued to the business organization upon payment of the appropriate licensing fee and exhibition to the tax collector of a valid certificate issued by the division.
History.s. 10, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-457; ss. 5, 8, ch. 78-141; s. 2, ch. 81-318; s. 17, ch. 84-243; ss. 1, 2, ch. 85-128; s. 9, ch. 88-209; s. 4, ch. 91-429; s. 446, ch. 97-102; s. 45, ch. 2013-183.
Note.Former s. 633.534.
633.332 Certificate; expiration; renewal; inactive certificate; continuing education.
(1) Certificates shall expire every 2 years at midnight on June 30. All certificates must be renewed every 2 years. The failure to renew a certificate before June 30 shall cause the certificate to become inoperative, and it is unlawful thereafter for a person to engage, offer to engage, or hold herself or himself out as engaging in contracting under the certificate unless the certificate is restored or reissued. A certificate which is inoperative because of failure to renew shall be restored on payment of the proper renewal fee if the application for restoration is made within 90 days after June 30. If the application for restoration is not made within the 90-day period, the fee for restoration must be equal to the original application fee, and, in addition, the State Fire Marshal must require examination or reexamination of the applicant.
(2) A person who holds a valid certificate may maintain such certificate in an inactive status during which time she or he may not engage in contracting. An inactive status certificate shall be void after a 2-year period. An inactive status certificate may be reactivated upon application to the State Fire Marshal and payment of the initial application fee.
(3)(a) A certificate for the Contractor I, II, and III classifications as defined in this chapter may not be renewed unless the certificateholder produces documentation of at least 32 contact hours of continuing education in the fire protection discipline during the biennial licensure period. Holders of Contractor IV certificates are required to obtain 14 contact hours of continuing education encompassing the appropriate National Fire Protection Association fire sprinkler documents before renewal. Holders of Contractor V certificates are required to obtain 14 contact hours of continuing education before renewal, at least 1 hour of which is in the fire protection discipline. Any continuing education hours approved pursuant to chapter 489 by the Construction Industry Licensing Board for underground utility and excavation contractors shall be considered as also approved to comply with Contractor V continuing education requirements. A Contractor V certificateholder shall provide to the State Fire Marshal evidence of approval of such coursework by the Construction Industry Licensing Board.
(b) Any continuing education hours approved by the department for a Contractor I, Contractor II, Contractor III, Contractor IV, or Contractor V certificateholder shall be considered as also approved to comply with continuing education requirements for licensees under the Construction Industry Licensing Board. Such continuing education requirements under this section may include seminars and conferences if the program and subject thereof is acceptable to the State Fire Marshal.
(c) The contact hours of continuing education must be obtained within the licensure period.
(4) The renewal period for the permit class is the same as that for the employing certificateholder. The continuing education requirements for permitholders are what is required to maintain NICET Sub-field of Inspection and Testing of Fire Protection Systems Level II, equivalent training and education as determined by the division, or higher certification plus 8 contact hours of continuing education approved by the State Fire Marshal during each biennial renewal period thereafter. It is the responsibility of the permitholder to maintain NICET II certification or equivalent training and education as determined by the division as a condition of permit renewal after July 1, 2008.
History.s. 11, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-457; ss. 6, 8, ch. 78-141; s. 2, ch. 81-318; s. 18, ch. 84-243; ss. 1, 2, ch. 85-128; s. 10, ch. 88-209; s. 31, ch. 89-233; s. 4, ch. 91-429; s. 20, ch. 95-379; s. 2, ch. 97-19; s. 447, ch. 97-102; s. 2, ch. 98-104; s. 80, ch. 2000-158; s. 28, ch. 2005-147; s. 11, ch. 2007-187; s. 57, ch. 2010-176; s. 46, ch. 2013-183.
Note.Former s. 633.537.
633.334 Requirements for installation, inspection, and maintenance of fire protection systems.
(1) The requirements for installation of fire protection systems are as follows:
(a) Contractors of fire protection systems shall be certified under s. 633.318.
(b) Equipment shall be listed by a nationally recognized testing laboratory, such as Underwriters Laboratories, Inc., or Factory Mutual Laboratories, Inc., or shall comply with nationally accepted standards. The State Fire Marshal shall adopt by rule procedures for determining whether a laboratory is nationally recognized, taking into account the laboratory’s facilities, procedures, use of nationally recognized standards, and any other criteria reasonably calculated to reach an informed determination.
(c) Equipment shall be installed in accordance with the applicable standards of the National Fire Protection Association and the manufacturer’s specifications.
(d) Each piece of equipment supplied shall be guaranteed for a period of 1 year against defects in material or operations.
(e) The contractor shall furnish the user with operating instructions for all equipment installed, together with a diagram of the final installation.
(2) Equipment shall be inspected, serviced, and maintained in accordance with the manufacturer’s maintenance procedures and with applicable National Fire Protection Association standards. The inspection of fire protection systems shall be conducted by a certificateholder or holder of a permit issued by the division. The permitholder may perform inspections on fire protection systems only while employed by the certificateholder. This section does not prohibit the authority having jurisdiction or insurance company representatives from reviewing the system in accordance with acceptable oversight standards.
(3) For contracts written after June 30, 2005, the contractor who installs the underground piping from the point of service is responsible for completing the installation to the aboveground connection flange, which by definition in this chapter is no more than 1 foot above the finished floor, before completing the Contractor’s Material and Test Certificate for Underground Piping document. Aboveground contractors may not complete the Contractor’s Material and Test Certificate for Underground Piping document for underground piping or portions thereof which have been installed by others.
(4) The Contractor V may install the cross-connection backflow prevention device as defined in this chapter on new installations following the engineer of record’s direction on the type and size of the device. The retrofitting of a backflow device on an existing fire protection system will cause a reduction in available water pressure and probable system malfunction. The development of aboveground fire protection system hydraulic calculations is a task of the Contractor I and II, as defined in this chapter. Accordingly, a Contractor V is expressly prohibited from retrofitting cross-connection backflow prevention devices on an existing fire protection system, and only a Contractor I or Contractor II who is tasked to recalculate the system and take corrective actions to ensure that the system will function with the available water supply may retroactively install these backflow devices on existing fire protection systems.
History.ss. 32, 40, ch. 89-233; s. 9, ch. 91-189; s. 4, ch. 91-429; s. 29, ch. 2005-147; s. 94, ch. 2006-1; s. 47, ch. 2013-183.
Note.Former s. 633.539.
633.336 Contracting without certificate prohibited; violations; penalty.
(1) It is unlawful for any organization or individual to engage in the business of layout, fabrication, installation, inspection, alteration, repair, or service of a fire protection system, other than a preengineered system, act in the capacity of a fire protection contractor, or advertise itself as being a fire protection contractor without having been duly certified and holding a valid and existing certificate, except as hereinafter provided. The holder of a certificate used to qualify an organization must be a full-time employee of the qualified organization or business. A certificateholder who is employed by more than one fire protection contractor during the same time is deemed not to be a full-time employee of either contractor. The State Fire Marshal shall revoke, for a period determined by the State Fire Marshal, the certificate of a certificateholder who allows the use of the certificate to qualify a company of which the certificateholder is not a full-time employee. A contractor who maintains more than one place of business must employ a certificateholder at each location. This subsection does not prohibit an employee acting on behalf of governmental entities from inspecting and enforcing firesafety codes, provided such employee is certified under s. 633.216.
(2) A fire protection contractor certified under this chapter may not:
(a) Enter into a written or oral agreement to authorize, or otherwise knowingly allow, a contractor who is not certified under this chapter to engage in the business of, or act in the capacity of, a fire protection contractor.
(b) Apply for or obtain a construction permit for fire protection work unless the fire protection contractor or the business organization qualified by the fire protection contractor has contracted to conduct the work specified in the application for the permit.
(3) The Legislature recognizes that special expertise is required for fire pump control panels and maintenance of electric and diesel pump drivers and that it is not economically feasible for all contractors to employ these experts full-time whose work may be limited. It is therefore deemed acceptable for a fire protection contractor licensed under this chapter to subcontract with companies providing advanced technical services for the installation, servicing, and maintenance of fire pump control panels and pump drivers. To ensure the integrity of the system and to protect the interests of the property owner, those providing technical support services for fire pump control panels and pump drivers must be under contract with a licensed fire protection contractor.
(4) A person who violates any provision of this act or commits any of the acts constituting cause for disciplinary action as herein set forth commits a misdemeanor of the second degree, punishable as provided in s. 775.082 or s. 775.083.
(5) In addition to the penalties provided in subsection (4), a fire protection contractor certified under this chapter or a person who violates any provision of this section or who commits any act constituting cause for disciplinary action is subject to:
(a) Suspension or revocation of the certificate pursuant to s. 633.338; and
(b) An administrative fine of up to $10,000 in any one proceeding for violations of subsection (1) or subsection (2), and if applicable, may be in addition to or in lieu of suspension or revocation of a certificate.

The State Fire Marshal shall adopt by rule guidelines that specify a range of designated penalties under this subsection based upon the severity and repetition of specific offenses and shall identify mitigating and aggravating circumstances that allow the State Fire Marshal to impose a penalty other than that provided for in the guidelines, and for variations and a range of penalties permitted under such circumstances.

History.s. 14, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-457; s. 8, ch. 78-141; s. 2, ch. 81-318; ss. 1, 2, ch. 85-128; s. 4, ch. 91-429; s. 21, ch. 95-379; s. 48, ch. 2013-183; s. 29, ch. 2016-129; s. 57, ch. 2022-138.
Note.Former s. 633.541.
633.338 Disciplinary action; fire protection system contractors; grounds for denial, nonrenewal, suspension, or revocation of certificate or permit.
(1) The State Fire Marshal shall investigate the alleged illegal action of any fire protection system contractor or permittee certified under this chapter and hold hearings pursuant to chapter 120.
(2) The following acts constitute cause for disciplinary action:
(a) Violation of any provision of this chapter or of any rule adopted pursuant thereto.
(b) Violation of the applicable building codes or laws of this state or any municipality or county thereof.
(c) Diversion of funds or property received for prosecution or completion of a specified construction project or operation when, as a result of the diversion, the contractor is, or will be, unable to fulfill the terms of her or his obligation or contract.
(d) Disciplinary action by any municipality, county, or special district, which action shall be reviewed by the State Fire Marshal before taking any disciplinary action.
(e) Failure to supervise the installation of the fire protection system covered by the building permit signed by the contractor.
(f) Rendering a fire protection system, standpipe system, or underground water supply main connecting to the system inoperative except when the fire protection system, standpipe system, or underground water supply main is being inspected, serviced, tested, or repaired, or except pursuant to court order.
(g) Improperly servicing, repairing, testing, or inspecting a fire protection, standpipe system, or underground water supply main connecting to the system.
(h) Failing to provide proof of insurance to the State Fire Marshal or failing to maintain in force the insurance coverage required by s. 633.318.
(i) Failing to obtain, retain, or maintain one or more of the qualifications for a certificate as specified in this chapter.
(j) Making a material misstatement, misrepresentation, or committing a fraud in obtaining or attempting to obtain a certificate.
(k) Failing to notify the State Fire Marshal, in writing, within 30 days after a change of residence address, principal business address, or name.
(3) The State Fire Marshal may suspend the contractor’s certificate for a period of up to 2 years. During that period, the contractor must cease all operations as a contractor, but the State Fire Marshal may authorize the certificateholder to complete any contracts then incomplete.
(4) During the suspension or revocation of the certificate, the former certificateholder shall not engage in or attempt to profess to engage in any transaction or business for which a certificate is required under this chapter or directly or indirectly own, control, or be employed in any manner by any firm or corporation for which a certificate under this chapter is required. The department shall not, so long as the revocation or suspension remains in effect, grant any new certificate for the establishment of any new firm, business, or corporation of any person that has or will have the same or similar management, ownership, control, or employees or that will use a same or similar name as a previously revoked or suspended firm, business, or corporation.
(5) The State Fire Marshal may deny, suspend, or revoke the certificate of:
(a) Any person, firm, or corporation the certificate of which under this chapter has been suspended or revoked.
(b) Any firm or corporation if an officer, director, stockholder, owner, or person interested directly or indirectly has had his or her certificate under this chapter suspended or revoked.
(c) Any person who is or has been an officer, director, stockholder, or owner of a firm or corporation, or who was interested directly or indirectly in a corporation, the certificate of which has been suspended or revoked under this chapter.
(6) The lapse or suspension of a certificate by operation of law or by order of the State Fire Marshal or a court or its voluntary surrender by a certificateholder does not deprive the State Fire Marshal of jurisdiction to investigate or act in disciplinary proceedings against the certificateholder.
(7) The filing of a petition in bankruptcy, either voluntary or involuntary, or the making of a composition of creditors or the appointment of a receiver for the business of the certificateholder may be considered by the State Fire Marshal as just cause for suspension of a certificate.
History.s. 15, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-457; s. 8, ch. 78-141; s. 2, ch. 81-318; s. 19, ch. 84-243; ss. 1, 2, ch. 85-128; s. 33, ch. 89-233; s. 4, ch. 91-429; s. 20, ch. 93-276; s. 448, ch. 97-102; s. 7, ch. 98-170; s. 58, ch. 98-419; s. 30, ch. 2005-147; s. 49, ch. 2013-183.
Note.Former s. 633.547.
633.342 Violations subject to injunction.A person who operates as a contractor without a current certificate or who violates any part of this chapter or any rule, decision, order, direction, demand, or requirement of the State Fire Marshal in relation thereto, or any part or provision thereof, may be enjoined by the courts of the state from any such violation or such unauthorized or unlawful contracting at the request of the State Fire Marshal, the board, or any resident or taxpayer of the state.
History.s. 15, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-457; s. 8, ch. 78-141; s. 2, ch. 81-318; ss. 1, 2, ch. 85-128; s. 15, ch. 87-287; s. 4, ch. 91-429; s. 50, ch. 2013-183.
Note.Former s. 633.549.
633.344 Application of law regulating contracting and contractors.
(1)(a) This chapter applies to any contractor performing work for the state or any county or municipality, as well as to contractors performing work pursuant to private contracts or agreements. Officers of the state or any county or municipality are required to determine compliance with this chapter before awarding any contracts for construction, improvement, remodeling, or repair.
(b) The state or any county or municipality may require that bids submitted for construction, improvement, remodeling, or repair of public buildings be accompanied by evidence that the bidder holds a current certificate.
(2) The provisions of this chapter relating to certification and contracting as a fire protection systems contractor shall apply to those so engaged in the business of contracting for fire protection systems.
History.ss. 5, 16, ch. 75-240; s. 3, ch. 76-168; s. 1, ch. 77-457; s. 8, ch. 78-141; s. 2, ch. 81-318; ss. 1, 2, ch. 85-128; s. 16, ch. 87-287; s. 35, ch. 89-233; s. 4, ch. 91-429; s. 51, ch. 2013-183.
Note.Former s. 633.554.
633.346 Jurisdiction of State Fire Marshal over alarm system contractors and certified unlimited electrical contractors.
(1) If the State Fire Marshal, in the course of its activities pursuant to s. 633.104(2), determines that an alarm system contractor or a certified unlimited electrical contractor working with an alarm system has violated any provision of this chapter or the rules of the State Fire Marshal, the State Fire Marshal shall have jurisdiction, notwithstanding any other provision of this chapter, to order corrective action by the alarm system contractor or the certified unlimited electrical contractor to bring the alarm system into compliance with applicable standards set forth in this chapter and the rules of the State Fire Marshal.
(2) Any order issued by the State Fire Marshal shall comply with the provisions of chapter 120 and allow a reasonable time for corrective action to be completed.
(3) The Department of Business and Professional Regulation and the Electrical Contractors’ Licensing Board may participate, at their discretion, but not as a party, in any proceedings relating to corrective action.
(4) The State Fire Marshal shall adopt standards, by rule, for the installation, maintenance, alteration, repair, monitoring, inspection, replacement, or servicing of fire alarms and fire alarm systems.
History.ss. 11, 14, ch. 87-254; ss. 22, 24, ch. 88-149; s. 4, ch. 91-429; s. 227, ch. 94-218; s. 231, ch. 98-200; s. 52, ch. 2013-183.
Note.Former s. 633.70.
633.348 Requirements for fire alarm system equipment.The requirements for fire alarm system equipment are:
(1) Equipment supplied shall be approved by a nationally recognized testing laboratory, and installed in accordance with its procedures. Any testing laboratory wishing to be considered “nationally recognized” by the State Fire Marshal shall submit an application to the State Fire Marshal for certification in accordance with procedures established by the State Fire Marshal by rule. The State Fire Marshal shall consider the applicant’s use of and compliance with nationally accepted testing procedures, the applicant’s inspection procedures including quality control, recognition by any other state or jurisdiction, and such other criteria as are reasonably necessary to reach an informed decision.
(2) Equipment shall be installed in accordance with the applicable standards of the National Fire Protection Association and procedures approved by said testing laboratory.
(3) Each piece of equipment supplied shall be warranted for a period of 1 year against defects in material or operation.
(4) The fire alarm system contractor or the certified unlimited electrical contractor shall furnish the user with appropriate documentation as required by the National Fire Protection Association standards, operating instructions for all equipment installed, together with a diagram of the final installation, except where the ownership of the system remains with the contractor.
(5) All fire alarm systems required by the State Fire Marshal’s rules shall be installed, serviced, tested, repaired, inspected, and improved in compliance with the provisions of the applicable standards of the National Fire Protection Association as adopted by rule.
(6) The State Fire Marshal shall promulgate specifications, by rule, regarding the information and data to be contained in the test certificate hereby required to be provided to the consumer when the fire alarm system is installed, serviced, tested, repaired, improved, or inspected. It shall be unlawful to install, service, test, repair, improve, or inspect any fire alarm system without providing the consumer with a completed test certificate.
(7) The State Fire Marshal shall promulgate by rule specifications as to the size, shape, and color and the information to be contained in the service tags hereby required to be attached to all fire alarm systems when they are installed, serviced, tested, repaired, inspected, or improved. It shall be unlawful to install, service, test, repair, inspect, or improve a fire system without attaching a completed tag, or to use a tag not meeting the specifications of the State Fire Marshal.
History.ss. 12, 14, ch. 87-254; s. 70, ch. 91-110; s. 10, ch. 91-189; s. 53, ch. 2013-183.
Note.Former s. 633.701.
633.3482 Prohibited acts regarding alarm system contractors or certified unlimited electrical contractors; penalties.
(1) It shall be unlawful for any person, directly or through an agent, to sell, offer for sale, or give any make, type, or model of fire alarm system, either new or used, unless such make, type, or model has been tested and is currently approved or listed by a nationally recognized testing laboratory.
(2) A person who violates this section commits a misdemeanor of the second degree, punishable as provided in s. 775.082 or s. 775.083.
(3) It is a misdemeanor of the first degree, punishable as provided in s. 775.082 or s. 775.083, for any fire alarm system contractor or certified unlimited electrical contractor to intentionally or willfully:
(a) Render inoperative any fire alarm system which is required by the State Fire Marshal’s rules, except when the system is being serviced, tested, repaired, inspected, or improved.
(b) Improperly install, service, test, repair, improve, or inspect a fire alarm system.
(c) Knowingly combine or conspire with a person by allowing one’s certificate to be used by an uncertified person with intent to evade this act. When a licensee allows his or her license to be used by one or more companies without having any active participation in the operation or management of the companies, such act constitutes prima facie evidence of any intent to evade this chapter.
(4) It is a misdemeanor of the first degree, punishable as provided in s. 775.082 or s. 775.083, for any person to intentionally or willfully install, service, test, repair, improve, or inspect a fire alarm system unless:
(a) The person is the holder of a valid and current active license as a certified unlimited electrical contractor, as defined in part II of chapter 489;
(b) The person is the holder of a valid and current active license as a licensed fire alarm contractor, as defined in part II of chapter 489;
(c) The person is authorized to act as a fire alarm system agent pursuant to s. 489.5185; or
(d) The person is exempt pursuant to s. 489.503.
History.ss. 13, 14, ch. 87-254; s. 71, ch. 91-110; s. 159, ch. 91-224; s. 450, ch. 97-102; s. 1, ch. 2005-116; s. 31, ch. 2005-147; s. 54, ch. 2013-183.
Note.Former s. 633.702.
PART IV
FIRE STANDARDS AND TRAINING
633.402 Firefighters Employment, Standards, and Training Council; organization; meetings; quorum; compensation; seal; special powers; firefighter training.
633.404 Additional standards authorized.
633.406 Classes of certification.
633.408 Firefighter and volunteer firefighter training and certification.
633.412 Firefighters; qualifications for certification.
633.414 Retention of firefighter and volunteer firefighter certifications.
633.415 Lifetime Firefighter designation.
633.416 Firefighter employment and volunteer firefighter service; saving clause.
633.418 Inservice training and promotion; participation.
633.422 Firefighters; supplemental compensation.
633.424 Falsification of qualifications.
633.426 Disciplinary action; standards for revocation of certification.
633.428 Florida State Fire College established.
633.432 Purpose of fire college.
633.434 Superintendent of college.
633.436 Use of Insurance Regulatory Trust Fund.
633.438 Procedure for making expenditures.
633.442 Buildings, equipment, and other facilities; use.
633.444 Division powers and duties; Florida State Fire College.
633.446 Fees.
633.402 Firefighters Employment, Standards, and Training Council; organization; meetings; quorum; compensation; seal; special powers; firefighter training.
(1) There is created within the department a Firefighters Employment, Standards, and Training Council of 15 members.
(a) The members shall be appointed as follows:
1. Two fire chiefs appointed by the Florida Fire Chiefs Association.
2. Two firefighters, who are not officers, appointed by the Florida Professional Firefighters Association.
3. Two firefighter officers, who are not fire chiefs, appointed by the State Fire Marshal.
4. One individual appointed by the Florida League of Cities.
5. One individual appointed by the Florida Association of Counties.
6. One individual appointed by the Florida Association of Special Districts.
7. One individual appointed by the Florida Fire Marshals’ and Inspectors’ Association.
8. One employee of the Florida Forest Service of the Department of Agriculture and Consumer Services appointed by the director of the Florida Forest Service.
9. One individual appointed by the State Fire Marshal.
10. One director or instructor of a state-certified firefighting training facility appointed by the State Fire Marshal.
11. One individual, appointed by the State Fire Marshal, who may not be a member or representative of the firefighting profession or of any local government.
12. One individual from the Department of Health, appointed by the Surgeon General.
(b) To be eligible for appointment as a member under subparagraph (a)1., subparagraph (a)2., subparagraph (a)3., subparagraph (a)8., or subparagraph (a)10., a person must have had at least 4 years’ experience in the firefighting profession. Members shall serve only as long as they continue to meet the criteria under which they were appointed, or unless a member has failed to appear at three consecutive and properly noticed meetings unless excused by the chair.
(2) Members shall be appointed for 4-year terms and in no event shall a member serve more than two consecutive terms. Any vacancy shall be filled in the manner of the original appointment for the remaining time of the term.
(3) The State Fire Marshal, in making her or his appointments, shall take into consideration representation by geography, population, and other relevant factors, in order that the membership on the council will be apportioned to give representation to the state at large rather than to a particular area.
(4) Membership on the council shall not disqualify a member from holding any other public office or being employed by a public entity, except that no member of the Legislature shall serve on the council.
(5) The council shall elect to 1-year terms a chair and a vice chair. A person may not serve more than two consecutive terms in either office.
(6) The council shall meet at the call of the chair, at the request of a majority of its membership, at the request of the department, or at such times as are prescribed by its rules, and a majority of the council shall constitute a quorum.
(7) Members of the council shall serve without compensation but shall be entitled to be reimbursed for per diem and travel expenses as provided by s. 112.061.
(8) The council may adopt a seal for its use containing the words “Firefighters Employment, Standards, and Training Council.”
(9) The council shall have special powers in connection with the employment and training of firefighters to:
(a) Recommend, for adoption by the division, uniform minimum standards for the employment and training of firefighters and training of volunteer firefighters.
(b) Recommend, for adoption by the division, minimum curriculum requirements for schools operated by or for any fire service provider for the specific purpose of training firefighter trainees, firefighters, and volunteer firefighters.
(c) Recommend, for adoption by the division, on matters relating to the funding, general operation, and administration of the Bureau of Fire Standards and Training (Florida State Fire College), including, but not limited to, all standards, training, curriculum, and the issuance of any certificate of competency required by this chapter.
(d) Make or support studies on any aspect of firefighting employment, education, and training or recruitment.
(e) Make recommendations concerning any matter within its purview pursuant to this section.
History.s. 1, ch. 70-110; ss. 1, 3, ch. 75-151; s. 3, ch. 77-107; s. 4, ch. 78-323; ss. 1, 3, 4, ch. 81-70; s. 1, ch. 82-46; ss. 1, 2, ch. 87-180; s. 5, ch. 91-429; s. 10, ch. 93-276; s. 433, ch. 97-102; s. 16, ch. 2002-404; s. 1401, ch. 2003-261; s. 56, ch. 2013-183; s. 28, ch. 2021-113.
Note.Former s. 163.471; s. 633.31.
633.404 Additional standards authorized.Nothing herein shall be construed to preclude a fire service provider from establishing qualifications and standards for hiring, training, or promoting firefighters that exceed the minimum set by the division.
History.ss. 16, 17, ch. 69-323; s. 1, ch. 75-151; s. 57, ch. 2013-183.
Note.Former s. 163.530; s. 633.42.
633.406 Classes of certification.
(1) The division may award one or more of the following certificates:
(a) Firefighter Certificate of Compliance.A Firefighter Certificate of Compliance may be awarded to a person who meets the requirements established in s. 633.408(4).
(b) Fire Safety Inspector Certificate of Compliance.A Fire Safety Inspector Certificate of Compliance may be awarded to a person who meets the requirements established in s. 633.216(2).
(c) Special Certificate of Compliance.A Special Certificate of Compliance may be awarded to a person who qualifies under s. 633.408(6).
(d) Forestry Certificate of Compliance.A Forestry Certificate of Compliance may be awarded to a person who has satisfactorily complied with a training program and successfully passed an examination as prescribed by rule, and who possesses the qualifications established in s. 590.02(1)(e).
(e) Fire Service Instructor Certificate.A Fire Service Instructor Certificate may be awarded to a person who demonstrates general or specialized knowledge, skills, and abilities in firefighting service and meets the qualification requirements prescribed by rule.
(f) Certificate of Competency.A Certificate of Competency may be awarded to a person who meets the experience, training, advanced education, or examination requirements as prescribed by rule, and is especially qualified for particular aspects of firefighting service.
(g) Volunteer Firefighter Certificate of Completion.A Volunteer Firefighter Certificate of Completion may be awarded to a person who has satisfactorily completed the training requirements as prescribed by rule for a volunteer firefighter.
(2) The division may establish by rule certificates, in addition to those provided in subsection (1), that the division may award in recognition of special training or education received by an individual, authorizing that individual to perform specialized firefighting services or provide specialized firefighting instruction, such as hazardous materials and urban search and rescue.
History.s. 58, ch. 2013-183.
633.408 Firefighter and volunteer firefighter training and certification.
(1) The division shall establish by rule:
(a) A Minimum Standards Course and course examination to provide the training required to obtain a Firefighter Certificate of Compliance.
(b) Courses and course examinations to provide training required to obtain a Volunteer Firefighter Certificate of Completion or a Special Certificate of Compliance.
(c) Courses to provide continuing training for firefighters and volunteer firefighters.
(d) Courses to provide training for career and volunteer firefighters related to cancer and mental health risks within the fire service. Such training must be a requirement for obtaining a Firefighter Certificate of Compliance, Volunteer Firefighter Certificate of Completion, or Special Certificate of Compliance. The training must include cancer and mental health awareness, prevention, mitigation, and treatment. The training must specifically include lifestyle, environmental, inherited, and occupational risks, and emphasize appropriate behavior, attitude, and cultural changes within the fire service. Certified firefighters shall have such training made available to them.
(2) Courses under subsection (1) may only be administered by education or training providers approved by the division pursuant to s. 633.128(1)(c) and taught by instructors certified pursuant to s. 633.128(1)(d).
(3)(a) Nothing herein shall require a fire service provider to pay the cost of such training.
(b) A fire service provider may pay part or all of the costs of tuition for attendance at approved courses.
(4) The division shall issue a firefighter certificate of compliance to an individual who does all of the following:
(a) Satisfactorily completes the Minimum Standards Course or has satisfactorily completed training for firefighters in another state which has been determined by the division to be at least the equivalent of the training required for the Minimum Standards Course.
(b) Passes the Minimum Standards Course certification within 12 months after completing the required courses.
(c) Possesses the qualifications in s. 633.412.
(5) The division shall issue a Volunteer Firefighter Certificate of Completion to any individual who satisfactorily completes the course established under paragraph (1)(b).
(6)(a) The division may issue a Special Certificate of Compliance to an individual who does all of the following:
1. Satisfactorily completes the course established by rule by the division and successfully passes any examination corresponding to such course to obtain a Special Certificate of Compliance.
2. Possesses the qualifications in s. 633.412.
(b) A Special Certificate of Compliance only authorizes an individual to serve as an administrative and command head of a fire service provider.
1. An individual employed as a fire chief, fire coordinator, fire director, or fire administrator must obtain a Special Certificate of Compliance within 1 year after beginning employment.
2. Before beginning employment as a command officer or in a position directing incident outcomes, an individual must obtain a Firefighter Certificate of Compliance or a Special Certificate of Compliance.
(7) An individual who fails an examination given under this section may retake the examination once within 6 months after the original examination date. If the individual does not retake the examination or fails the reexamination within such time, the individual must take the Minimum Standards Course for a Firefighter Certificate of Compliance or the course established under paragraph (1)(b) for a Special Certificate of Compliance before being reexamined. The division may grant an extension of the 6-month period based upon documented medical necessity and may establish reasonable preregistration deadlines for reexaminations.
(8)(a) Pursuant to s. 590.02(1)(e), the division shall establish a structural fire training program of not less than 40 hours. The division shall issue to a person satisfactorily complying with this training program and who has successfully passed an examination as prescribed by the division and who has met the requirements of s. 590.02(1)(e), a Wildland Firefighter Certificate of Compliance.
(b) An individual who holds a current and valid Wildland Firefighter Certificate of Compliance is entitled to the same rights, privileges, and benefits provided for by law as a firefighter.
(9) A Firefighter Certificate of Compliance or a Volunteer Firefighter Certificate of Completion issued under this section expires 4 years after the date of issuance unless renewed as provided in s. 633.414.
History.ss. 9, 17, ch. 69-323; s. 1, ch. 70-110; ss. 1, 6, ch. 75-151; s. 3, ch. 81-205; s. 11, ch. 84-243; s. 24, ch. 89-233; s. 2, ch. 92-187; s. 14, ch. 93-276; s. 16, ch. 95-379; s. 435, ch. 97-102; s. 4, ch. 97-124; s. 1, ch. 98-40; s. 59, ch. 2013-183; s. 159, ch. 2014-17; s. 23, ch. 2016-132; s. 1, ch. 2018-18; s. 43, ch. 2018-102; s. 8, ch. 2020-135; s. 58, ch. 2022-138.
Note.Former s. 163.495; s. 633.35.
633.412 Firefighters; qualifications for certification.A person applying for certification as a firefighter must:
(1) Be a high school graduate or the equivalent, as the term may be determined by the division, and at least 18 years of age.
(2) Not have been convicted of a misdemeanor relating to the certification or to perjury or false statements, or a felony or a crime punishable by imprisonment of 1 year or more under the law of the United States or of any state thereof or under the law of any other country, or dishonorably discharged from any of the Armed Forces of the United States. “Convicted” means a finding of guilt or the acceptance of a plea of guilty or nolo contendere, in any federal or state court or a court in any other country, without regard to whether a judgment of conviction has been entered by the court having jurisdiction of the case.
(3) Submit a set of fingerprints to the division with a current processing fee. The fingerprints will be forwarded to the Department of Law Enforcement for state processing and forwarded by the Department of Law Enforcement to the Federal Bureau of Investigation for national processing.
(4) Have a good moral character as determined by investigation under procedure established by the division.
(5) Be in good physical condition as determined by a medical examination given by a physician, surgeon, or physician assistant licensed to practice in the state pursuant to chapter 458; an osteopathic physician, surgeon, or physician assistant licensed to practice in the state pursuant to chapter 459; or an advanced practice registered nurse licensed to practice in the state pursuant to chapter 464. Such examination may include, but need not be limited to, the National Fire Protection Association Standard 1582. A medical examination evidencing good physical condition shall be submitted to the division, on a form as provided by rule, before an individual is eligible for admission into a course under s. 633.408.
(6) Be a nonuser of tobacco or tobacco products for at least 1 year immediately preceding application, as evidenced by the sworn affidavit of the applicant.
History.ss. 8, 17, ch. 69-323; s. 1, ch. 70-110; ss. 1, 6, ch. 75-151; s. 1, ch. 77-116; s. 2, ch. 81-205; s. 10, ch. 84-243; s. 3, ch. 88-209; s. 1, ch. 89-89; s. 23, ch. 89-233; s. 7, ch. 91-189; s. 13, ch. 93-276; s. 2, ch. 2005-76; s. 57, ch. 2013-116; s. 60, ch. 2013-183; s. 24, ch. 2016-132; s. 76, ch. 2018-106.
Note.Former s. 163.490; s. 633.34.
633.414 Retention of firefighter and volunteer firefighter certifications.
(1) In order for a firefighter to retain her or his Firefighter Certificate of Compliance or Special Certificate of Compliance, every 4 years he or she must meet the requirements for renewal provided in this chapter and by rule, which must include at least one of the following:
(a) Be active as a firefighter. As used in this section, the term “active” means being employed as a firefighter or providing service as a volunteer firefighter as evidenced by the individual’s name appearing on a fire service provider’s employment roster in the Florida State Fire College database or a letter by the fire service provider attesting to dates of employment.
(b) Maintain a current and valid fire service instructor certificate, instruct at least 40 hours during the 4-year period, and provide proof of such instruction to the division, which proof must be registered in an electronic database designated by the division.
(c) Before the expiration of the certificate, successfully complete a Firefighter Retention Refresher Course consisting of a minimum of 40 hours of training to be prescribed by rule.
(d) Before the expiration of the certificate, successfully retake and pass the Minimum Standards Course examination pursuant to s. 633.408.
(2) In order for a volunteer firefighter to retain her or his Volunteer Firefighter Certificate of Completion, every 4 years he or she must:
(a) Be active as a volunteer firefighter; or
(b) Successfully complete a refresher course consisting of a minimum of 40 hours of training to be prescribed by rule.
(3) Subsection (1) does not apply to state-certified firefighters who are certified and employed full-time, as determined by the fire service provider, as firesafety inspectors or fire investigators, regardless of their employment status as firefighters or volunteer firefighters.
(4) The 4-year period begins upon issuance of the certificate or separation from employment.
(5) A certificate for a firefighter or volunteer firefighter expires if he or she fails to meet the requirements of this section.
(6) The State Fire Marshal may deny, refuse to renew, suspend, or revoke the certificate of a firefighter or volunteer firefighter if the State Fire Marshal finds that any of the following grounds exists:
(a) Any cause for which issuance of a certificate could have been denied if it had then existed and had been known to the division.
(b) A violation of any provision of this chapter or any rule or order of the State Fire Marshal.
(c) Falsification of a record relating to any certificate issued by the division.

The 4-year period may, in the discretion of the department, be extended to 12 months after discharge from military service if the military service does not exceed 3 years, but in no event more than 6 years from the date of issue or renewal, if applicable, for an honorably discharged veteran of the United States Armed Forces or the spouse of such a veteran. A qualified individual must provide a copy of a military identification card, military dependent identification card, military service record, military personnel file, veteran record, discharge paper, or separation document that indicates such member is currently in good standing or such veteran is honorably discharged.

History.s. 17, ch. 95-379; s. 437, ch. 97-102; s. 54, ch. 2010-176; s. 61, ch. 2013-183; s. 25, ch. 2016-132; s. 47, ch. 2018-7; s. 59, ch. 2022-138.
Note.Former s. 633.352.
633.415 Lifetime Firefighter designation.
(1) A firefighter or volunteer firefighter may apply for a Lifetime Firefighter designation if he or she:
(a) Has at least 20 years of service;
(b) Has been employed by a fire service provider, as defined in s. 633.102(13), and is in good standing with his or her most recent fire service provider;
(c) Has no conviction or other disqualifying event under s. 633.412(2);
(d) Complies with s. 633.412(3); and
(e)1. Is recorded on a fire service provider roster in the division’s online electronic database; or
2. Was previously certified as a firefighter or volunteer firefighter in this state.
(2) A firefighter may have his or her Firefighter Certificate of Compliance or a Volunteer Firefighter Certificate of Completion placed into a Lifetime Firefighter designation by applying to the division at the time required to renew the certificate. The application shall be made on a form prescribed by the division.
(3) A Lifetime Firefighter may not engage in firefighting activities with a fire department unless he or she holds a current and valid Firefighter Certificate of Compliance or Special Certificate of Compliance issued by the division under s. 633.408.
(4) After the division approves a currently employed firefighter’s Lifetime Firefighter designation, the division shall, after the firefighter’s 4-year period pursuant to s. 633.414, issue in its online electronic database the Lifetime Firefighter designation upon the end of such period.
(5) If a firefighter’s Firefighter Certificate of Compliance or Volunteer Firefighter Certificate of Completion is current upon the approval of a Lifetime Firefighter designation and he or she applies to renew such certification within the first 4 years after the date of such approval, he or she must successfully complete the Minimum Standards Course examination for a firefighter under s. 633.408(1)(a), or the course examinations under s. 633.408(1)(b) for a volunteer firefighter, and meet all requirements in s. 633.412.
(6) If a firefighter’s Firefighter Certificate of Compliance or Volunteer Firefighter Certificate of Completion has expired upon receiving the Lifetime Firefighter designation and he or she desires to perform firefighting services within the first 4 years after the date of approval of the Lifetime Firefighter designation, the firefighter must successfully complete the Minimum Standards Course examination for a firefighter under s. 633.408(1)(a), or the course examinations under s. 633.408(1)(b) for a volunteer firefighter, and meet all requirements in s. 633.412.
(7) A Lifetime Firefighter designation shall be revoked for any of the conditions stated in s. 633.426(3) or (4). The division may investigate and take such action under s. 633.426 to implement this subsection.
(8) The division may adopt rules pursuant to its authority under s. 633.104(1) to implement this section.
History.s. 1, ch. 2017-106.
633.416 Firefighter employment and volunteer firefighter service; saving clause.
(1) A fire service provider may not employ an individual to:
(a) Extinguish fires for the protection of life or property or to supervise individuals who perform such services unless the individual holds a current and valid Firefighter Certificate of Compliance. However, a person who is currently serving as a volunteer firefighter and holds a volunteer firefighter certificate of completion with a fire service provider, who is then employed as a regular or permanent firefighter by such fire service provider, may function, for a period of 1 year under the direct supervision of an individual holding a valid Firefighter Certificate of Compliance, in the same capacity in which he or she acted as a volunteer firefighter, provided that he or she has completed all training required by the volunteer organization. Under no circumstance can this period extend beyond 1 year either collectively or consecutively from the start of employment to obtain a Firefighter Certificate of Compliance; or
(b) Serve as the administrative and command head of a fire service provider for a period in excess of 1 year unless the individual holds a current and valid Firefighter Certificate of Compliance or Special Certificate of Compliance.
(2) A fire service provider may not retain the services of an individual volunteering to extinguish fires for the protection of life or property or to supervise individuals who perform such services unless the individual holds a current and valid Volunteer Firefighter Certificate of Completion.
(3)(a) A fire service provider must make a diligent effort to determine whether the individual has a current and valid certificate before employing or retaining an individual for the services under subsection (1) or subsection (2), including making a determination of whether the requirements set forth in s. 633.414 have been fulfilled.
(b) For the purposes of this subsection, the term “diligent effort” means contacting at least three of the individual’s previous employers to obtain her or his dates of employment and contacting the division to determine the certification status of the individual.
(4)(a) A fire service provider must notify the division electronically, as directed by rule by the division, within 10 days after:
1. The hiring of a firefighter.
2. The retention of a volunteer firefighter.
3. The cessation of employment of a firefighter.
4. A decision not to retain a volunteer firefighter.
(b) Notification under paragraph (a) must include:
1. The individual’s name.
2. The date on which he or she was hired or retained.
3. The last date of employment or retention before leaving the fire service provider.
4. Any other information deemed necessary by the division to determine compliance with ss. 633.414 and 633.426.
(5) If the fire service provider makes a determination that an individual has not met the requirements set forth in s. 633.414(1), the fire service provider must notify the division in writing within 10 days after making that determination.
(6) The division may conduct site visits to fire departments to monitor compliance with this section.
(7) For purposes of this section, the term “employ” means to pay an individual a salary, wage, or other compensation for the performance of work. The term does not include the payment of expenses, reasonable benefits, a nominal fee, or a combination thereof to a volunteer for a public or private fire service provider who is only paid in a manner that would be authorized for a volunteer under the federal Fair Labor Standards Act of 1938, as amended, 29 U.S.C. ss. 201 et seq., and its implementing rules.
(8) Firefighters employed on July 5, 1969, are not required to meet the provisions of ss. 633.408 and 633.412 as a condition of tenure or continued employment, and their failure to fulfill such requirements does not make them ineligible for any promotional examination for which they are otherwise eligible or affect in any way any pension rights to which they may be entitled on July 5, 1969.
History.s. 15, ch. 69-323; s. 1, ch. 75-151; s. 26, ch. 89-233; s. 10, ch. 2000-333; s. 62, ch. 2013-183; s. 29, ch. 2021-113.
Note.Former s. 163.525; s. 633.41.
633.418 Inservice training and promotion; participation.
(1)(a) The division shall by rule prescribe curricula and standards for advanced and specialized training courses and education in addition to those prescribed in ss. 633.408 and 633.412.
(b) The standards provided by this section do not bind any fire service provider as to the requirements it may have for promoting personnel.
(2) A fire service provider participating under this section shall adhere to the standards and procedures established by the division.
History.ss. 12, 17, ch. 69-323; s. 1, ch. 70-110; ss. 1, 6, ch. 75-151; s. 6, ch. 81-205; s. 63, ch. 2013-183.
Note.Former s. 163.510; s. 633.38.
633.422 Firefighters; supplemental compensation.
(1) QUALIFICATIONS FOR SUPPLEMENTAL COMPENSATION.The Legislature recognizes the need for supplemental compensation for firefighters who pursue higher educational opportunities that directly relate to the improvement of the health, safety, and welfare of firefighters and those who firefighters protect. The State Fire Marshal shall determine, and adopt by rule, the coursework or degrees that represent the best practices toward this goal in the field of firefighting.
(a) In addition to the compensation now paid by a fire service provider to any firefighter, every firefighter shall be paid supplemental compensation by the fire service provider when such firefighter is a full-time employee, as determined by the employing fire service provider, and has complied with one of the following criteria:
1. A firefighter who receives an associate degree from an accredited college, which degree is directly applicable to fire department duties, as outlined in policy guidelines adopted by rule by the division, shall be additionally compensated as outlined in paragraph (2)(a).
2. A firefighter, regardless of whether or not she or he earned an associate degree earlier, who receives from an accredited college or university a bachelor’s degree, which bachelor’s degree is directly applicable to fire department duties, as outlined in policy guidelines adopted by rule by the division, shall receive compensation as outlined in paragraph (2)(b).
(b) If any question arises as to the eligibility of any firefighter to receive supplemental compensation as provided in this section, the question, together with all facts relating thereto, must be submitted to the division for determination, and the decision of the division with regard to determination of eligibility shall be final, subject to chapter 120.
(2) SUPPLEMENTAL COMPENSATION.Supplemental compensation shall be determined as follows:
(a) Fifty dollars shall be paid monthly to each firefighter who qualifies under subparagraph (1)(a)1.
(b) One hundred and ten dollars shall be paid monthly to each firefighter who qualifies under subparagraph (1)(a)2.
(3) FUNDING.
(a) The fire service provider is responsible for the correct payment of firefighters pursuant to this section. The division may review, in a postaudit capacity, any action taken by an agency in administering the educational incentive program. The fire service provider shall take appropriate action when a postaudit shows that an action taken by the fire service provider was in error.
(b) Each fire service provider employing firefighters who are eligible for this compensation shall submit reports containing information relating to compensation paid as a result of this section to the division on March 31, June 30, September 30, and December 31 of each year.
(c) There is appropriated from the Police and Firefighter’s Premium Tax Trust Fund to the Firefighters’ Supplemental Compensation Trust Fund, which is created under the Department of Revenue, all moneys which have not been distributed to municipalities and special fire control districts in accordance with s. 175.121 as a result of the limitation contained in s. 175.122 on the disbursement of revenues collected pursuant to chapter 175 or as a result of any municipality or special fire control district not having qualified in any given year, or portion thereof, for participation in the distribution of the revenues collected pursuant to chapter 175. The total required annual distribution from the Firefighters’ Supplemental Compensation Trust Fund shall equal the amount necessary to pay supplemental compensation as provided in this section, provided that:
1. Any deficit in the total required annual distribution shall be made up from accrued surplus funds existing in the Firefighters’ Supplemental Compensation Trust Fund on June 30, 1990, for as long as such funds last. If the accrued surplus is insufficient to cure the deficit in any given year, the proration of the appropriation among the counties, municipalities, and special fire service taxing districts shall equal the ratio of compensation paid in the prior year to county, municipal, and special fire service taxing district firefighters pursuant to this section. This ratio shall be provided annually to the Department of Revenue by the division. Surplus funds that have accrued or accrue on or after July 1, 1990, shall be redistributed to municipalities and special fire control districts as provided in subparagraph 2.
2. By October 1 of each year, any funds that have accrued or accrue on or after July 1, 1990, and remain in the Firefighters’ Supplemental Compensation Trust Fund following the required annual distribution shall be redistributed by the Department of Revenue pro rata to those municipalities and special fire control districts identified by the Department of Management Services as being eligible for additional funds pursuant to s. 175.121(3)(b).
(d) Salary incentive payments to firefighters shall commence in the first full calendar month following the initial date of certification of eligibility by the division.
(e) Special fire service taxing districts are authorized to spend the funds necessary to ensure correct payment to firefighters.
(4) LEGISLATIVE FINDINGS.The payment of supplemental compensation and expenses of the administration provided by this section is found to serve a state, county, district, and municipal purpose and to provide benefit to the state and to its counties, municipalities, and districts.
(5) APPLICABILITY.For the purposes of this section, the department shall be considered a fire service provider responsible for the payment of supplemental compensation in accordance with this section to firefighters employed full time by the department.
History.ss. 1, 2, 3, 4, 5, 6, 7, 8, ch. 81-287; s. 2, ch. 82-189; s. 5, ch. 83-115; s. 130, ch. 83-216; s. 1, ch. 84-244; s. 5, ch. 88-209; s. 1, ch. 89-99; s. 8, ch. 91-189; s. 51, ch. 93-193; s. 10, ch. 95-250; s. 18, ch. 95-379; s. 438, ch. 97-102; s. 97, ch. 99-255; s. 1403, ch. 2003-261; s. 64, ch. 2013-183; s. 34, ch. 2016-165.
Note.Former s. 633.382.
633.424 Falsification of qualifications.An individual who willfully and knowingly falsifies her or his qualifications to the Bureau of Fire Standards and Training of the division commits a misdemeanor of the second degree, punishable as provided in s. 775.082 or s. 775.083.
History.s. 5, ch. 81-205; s. 1402, ch. 2003-261; s. 65, ch. 2013-183.
Note.Former s. 633.353.
633.426 Disciplinary action; standards for revocation of certification.
(1) For purposes of this section, the term:
(a) “Certificate” means any of the certificates issued under s. 633.406.
(b) “Certification” or “certified” means holding a certificate that is current and valid and that meets the requirements for renewal of certification pursuant to this chapter and the rules adopted under this chapter.
(c) “Convicted” means a finding of guilt, or the acceptance of a plea of guilty or nolo contendere, in any federal or state court or a court in any other country, without regard to whether a judgment of conviction has been entered by the court having jurisdiction of the case.
(2) Effective July 1, 2013, an individual who holds a certificate is subject to revocation for any of the following:
(a) Conviction of a misdemeanor relating to the certification or to perjury or false statements.
(b) Conviction of a felony or a crime punishable by imprisonment of 1 year or more under the law of the United States or of any state thereof, or under the law of any other country.
(c) Dishonorable discharge from any of the Armed Forces of the United States.
(3)(a) The certification of an individual shall be permanently revoked if the individual is:
1. Convicted of a misdemeanor relating to perjury or false statement.
2. Convicted of a felony or a crime punishable by imprisonment of 1 year or more under the law of the United States or of any state thereof, or under the law of any other country.
3. Dishonorably discharged from any of the Armed Forces of the United States.
(b) For individuals who are certified before July 1, 2013:
1. This subsection applies prospectively to convictions or dishonorable discharges entered on or after July 1, 2013.
2. Section 633.351 as it existed before July 1, 2013, applies to convictions entered before July 1, 2013.
(4) The certification of an individual shall be revoked if evidence is found which demonstrates that the certification was improperly issued by the division or was issued on the basis of false, incorrect, incomplete, or misleading information, or that the individual has demonstrated a lack of moral fitness or trustworthiness to carry out the responsibilities under the individual’s certification.
(5) After investigation, if the division has reason to believe that an individual who is certified may have been convicted of a felony or of a misdemeanor related to perjury or false statement in this state or any other state or jurisdiction, the division may require the individual to submit fingerprints to the division with a current processing fee. The fingerprints shall be forwarded by the division to the Department of Law Enforcement for state processing and shall be forwarded by the Department of Law Enforcement to the Federal Bureau of Investigation for national processing.
History.s. 4, ch. 81-205; s. 12, ch. 84-243; s. 4, ch. 88-209; s. 25, ch. 89-233; s. 6, ch. 90-359; s. 15, ch. 93-276; s. 22, ch. 95-379; s. 436, ch. 97-102; s. 66, ch. 2013-183; s. 26, ch. 2016-132.
Note.Former s. 633.351.
633.428 Florida State Fire College established.There is established a state institution to be known as the Florida State Fire College, to be located at or near Ocala, Marion County. The institution shall be operated by the division.
History.s. 3, ch. 25097, 1949; ss. 18, 35, ch. 69-106; ss. 1, 8, ch. 75-151; s. 1404, ch. 2003-261; s. 67, ch. 2013-183.
Note.Former s. 163.532; s. 633.43.
633.432 Purpose of fire college.The purposes of this part and of the Florida State Fire College are:
(1) To provide professional and volunteer firefighters with needful professional instruction and training in subjects, including, but not limited to, firefighting, fire prevention, hazardous materials, urban search and rescue, and emergency operations, at a minimum of cost to them and to their employers.
(2) To ensure the professionalism and competence of those performing firefighting, fire prevention, and associated fire protection functions by administering a system of certification and licensing.
(3) To develop new methods and practices of firefighting and fire prevention.
(4) To assist the state and county, municipal, and other local governments of this state and their agencies and officers in their investigation and determination of the causes of fires.
(5) To provide testing facilities for testing firefighting equipment.
(6) To disseminate useful information on fires, firefighting and fire prevention and other related subjects, to fire departments and others interested in such information.
(7) To do such other needful or useful things necessary to the promotion of public safety in the field of fire hazards and fire prevention work.

It is declared by the Legislature that the above purposes are legitimate state functions and are designed to promote public safety.

History.s. 4, ch. 25097, 1949; s. 1, ch. 75-151; s. 242, ch. 79-400; s. 19, ch. 95-379; s. 68, ch. 2013-183.
Note.Former s. 163.533; s. 633.44.
633.434 Superintendent of college.The division may employ a superintendent for the Florida State Fire College, who must be especially trained and qualified in firefighting, fire prevention and fire experimental work, and may employ on the recommendations of the superintendent such other instructors, experimental helpers and laborers as may be necessary to the proper conduct of the institution; and may proceed with the erection and detailed operation of the institution under ss. 633.428-633.444.
History.s. 10, ch. 25097, 1949; s. 3, ch. 57-401; ss. 18, 35, ch. 69-106; ss. 1, 10, ch. 75-151; s. 69, ch. 2013-183.
Note.Former s. 163.538; s. 633.48.
633.436 Use of Insurance Regulatory Trust Fund.The funds received from the Insurance Regulatory Trust Fund shall be used by the staff of the Florida State Fire College to provide all necessary services, training, equipment, and supplies to carry out the college’s responsibilities, including, but not limited to, the procurement of training resources and equipment and other useful information on fire, firefighting, and fire prevention, including public fire service information packages.
History.s. 5, ch. 82-189; s. 29, ch. 89-233; s. 39, ch. 96-418; s. 14, ch. 99-205; s. 1408, ch. 2003-261; s. 70, ch. 2013-183.
Note.Former s. 633.461.
633.438 Procedure for making expenditures.No moneys shall be spent for and on behalf of the Florida State Fire College except upon a written voucher drawn by the division, stating the nature of the expenditures and the person to whom the same shall be made payable, which voucher shall be submitted to the Chief Financial Officer and audited for approval by her or him; upon such approval, the Chief Financial Officer shall draw a warrant for the payment thereof, filing the original voucher in her or his office.
History.s. 7, ch. 25097, 1949; ss. 18, 35, ch. 69-106; ss. 1, 10, ch. 75-151; s. 15, ch. 85-61; s. 439, ch. 97-102; s. 1409, ch. 2003-261; s. 71, ch. 2013-183.
Note.Former s. 163.536; s. 633.47.
633.442 Buildings, equipment, and other facilities; use.The division shall have the power to prescribe and shall make the necessary rules for the use of buildings, equipment, and other facilities of the Florida State Fire College when they are not in use for the purposes set forth in this part.
History.s. 11, ch. 25097, 1949; ss. 18, 35, ch. 69-106; ss. 1, 10, ch. 75-151; s. 72, ch. 2013-183.
Note.Former s. 163.539; s. 633.49.
633.444 Division powers and duties; Florida State Fire College.
(1) The division, in performing its duties related to the Florida State Fire College, specified in this part, shall:
(a) Enter into agreements with public or private school districts, community colleges, junior colleges, or state universities to carry out its duties and responsibilities.
(b) Review and approve budget requests for the fire college educational program.
(c) Prepare the legislative budget request for the Florida State Fire College education program. The superintendent is responsible for all expenditures pursuant to appropriations.
(d) Implement procedures to obtain appropriate entitlement funds from federal and state grants to supplement the annual legislative appropriation. Such funds must be used expressly for the fire college educational programs.
(e) Approve and register in an electronic database an education or training provider, designated by the division, before the education or training provider may offer any course to fulfill any education or training requirement under this chapter. The division shall establish criteria, by rule, for the approval of such education or training providers, including courses taught. Only approved and registered education or training providers are eligible to provide instruction or training that will be recognized by the division as fulfilling any education or training requirement under this chapter.
(f) Recognize only courses offered by approved and registered training or education providers as fulfilling the education or training requirements under this chapter.
(2) Funds generated by the formula per full-time equivalent student may not exceed the level of state funding per full-time equivalent student generated through the Florida Education Finance Program or the State Community College Program Fund for students enrolled in comparable education programs provided by public school districts and community colleges. Funds appropriated for education and operational costs shall be deposited in the Insurance Regulatory Trust Fund to be used solely for purposes specified in s. 633.436 and may not be transferred to any other budget entity for purposes other than education.
(3) The division shall waive all living and incidental expenses associated with attending the Florida State Fire College for an active duty member of the United States Armed Forces, the spouse of such a member who was serving on active duty at the time of death and died within the 2 years preceding the spouse attending the college, an honorably discharged veteran of the United States Armed Forces, or the spouse or surviving spouse of such a veteran. A qualified individual must provide a copy of a military identification card, military dependent identification card, military service record, military personnel file, veteran record, discharge paper, or separation document that indicates such member is currently in good standing or such veteran is honorably discharged.
History.s. 1, ch. 90-189; s. 15, ch. 99-205; s. 1035, ch. 2002-387; s. 1410, ch. 2003-261; s. 73, ch. 2013-183; s. 48, ch. 2018-7; s. 44, ch. 2018-102.
Note.Former s. 633.50.
633.446 Fees.The division may fix and collect admission fees and other fees which it deems necessary to be charged for training given. All fees so collected shall be deposited in the Insurance Regulatory Trust Fund.
History.s. 6, ch. 25097, 1949; s. 1, ch. 61-515; ss. 18, 35, ch. 69-106; ss. 1, 10, ch. 75-151; s. 4, ch. 82-189; s. 28, ch. 89-233; s. 13, ch. 99-205; s. 1407, ch. 2003-261; s. 74, ch. 2013-183.
Note.Former s. 163.535; s. 633.46.
PART V
FLORIDA FIREFIGHTERS
OCCUPATIONAL SAFETY AND HEALTH ACT
633.502 Short title.
633.504 Definitions.
633.506 Legislative intent.
633.508 Workplace safety; rulemaking authority; division authority.
633.512 Compliance.
633.516 Studies of occupational diseases of firefighters or persons in other fire-related fields.
633.518 Studies, investigations, inspections, or inquiries by the division; refusal to admit; penalty.
633.520 Safety; firefighter employer responsibilities.
633.522 Firefighter employers; high frequency of work-related injuries; corrective plans; workplace safety committees and coordinators; failure to implement a safety and health program; cancellation.
633.526 Firefighter employer penalties.
633.528 Division cooperation with Federal Government; exemption from requirements for private firefighter employers.
633.532 Firefighter employee rights and responsibilities.
633.5341 False, fictitious, or fraudulent acts, statements, and representations prohibited; penalty; statute of limitations.
633.536 Expenses of administration.
633.502 Short title.Sections 633.502-633.536 may be cited as the “Florida Firefighters Occupational Safety and Health Act.”
History.s. 15, ch. 2002-404; s. 76, ch. 2013-183.
Note.Former s. 633.801.
633.504 Definitions.As used in this part, the term:
(1) “Firefighter employee” means a firefighter, volunteer firefighter, or individual providing support services who is engaged in any employment, public or private, under any appointment or contract of hire or apprenticeship, express or implied, oral or written, whether lawfully or unlawfully employed, responding to or assisting with fire or medical emergencies, regardless of whether on duty, except those appointed under s. 590.02(1)(d).
(2) “Firefighter employer” means the state and all political subdivisions of this state, all public and quasi-public corporations in this state, and a person carrying on any employment for this state, political subdivisions of this state, and public and quasi-public corporations in this state which employs firefighter employees, except those appointed under s. 590.02(1)(d).
(3) “Firefighter employment” or “employment” means any service performed by a firefighter employee for the firefighter employer.
(4) “Firefighter place of employment” or “place of employment” means the physical location at which the firefighter employee is employed or deployed.
History.s. 15, ch. 2002-404; s. 1412, ch. 2003-261; s. 77, ch. 2013-183.
Note.Former s. 633.802.
633.506 Legislative intent.It is the intent of the Legislature to enhance firefighter occupational safety and health in the state through the implementation and maintenance of policies, procedures, practices, rules, and standards that reduce the incidence of firefighter employee accidents, firefighter employee occupational diseases, and firefighter employee fatalities compensable under chapter 440 or otherwise. The Legislature further intends that the division develop a means by which the division can identify individual firefighter employers with a high frequency or severity of work-related injuries, conduct safety inspections of those firefighter employers, and assist those firefighter employers in the development and implementation of firefighter employee safety and health programs. In addition, it is the intent of the Legislature that the division administer and enforce this part; provide assistance to firefighter employers, firefighter employees, and insurers; and enforce the policies, rules, and standards set forth in this part.
History.s. 15, ch. 2002-404; s. 78, ch. 2013-183.
Note.Former s. 633.803.
633.508 Workplace safety; rulemaking authority; division authority.
(1) The division shall assist in making the firefighter employee place of employment a safer place to work and decreasing the frequency and severity of on-the-job injuries in such workplace.
(2) The division shall have the authority to adopt rules for the purpose of ensuring safe working conditions for all firefighter employees by authorizing the enforcement of effective standards, by assisting and encouraging firefighter employers to maintain safe working conditions, and by providing for education and training in the field of safety, including training related to cancer and mental health risks within the fire service. Specifically, the division may by rule adopt the most current edition of all or any part of subparts C through T and subpart Z of 29 C.F.R. s. 1910; the National Fire Protection Association, Inc., Publication 1403, Standard on Live Fire Training Evolutions, as limited by subsection (6); and ANSI A 10.4.
(3) With respect to 29 C.F.R. s. 1910.134(g)(4), the two individuals located outside the immediately dangerous to life and health atmosphere may be assigned to an additional role, such as incident commander, pumper operator, engineer, or driver, so long as such individual can immediately perform assistance or rescue activities without jeopardizing the safety or health of any firefighter employee working at an incident.
(4) The provisions of chapter 440 that pertain to workplace safety apply to the division.
(5) The division may adopt any rule necessary to implement, interpret, and make specific the provisions of this section, provided the division may not adopt by rule any other standard or standards of the Occupational Safety and Health Administration or the National Fire Protection Association relating solely to this part and firefighter employment safety without specific legislative authority.
(6)(a) The division shall adopt rules for live fire training that all firefighter employees subject to this chapter must complete. The division shall also adopt rules for a training and certification process for live fire training instructors.
(b) Such rules for training must include:
1. Sections of the most current edition of the National Fire Protection Association, Inc., Publication 1402, Guide to Building Fire Service Training Centers, relating to establishing policies and procedures for effective use of such permanent facilities or structures.
2. Sections of the most current edition of the National Fire Protection Association, Inc., Publication 1403, Standard on Live Fire Training Evolutions, excluding, however:
a. Any chapter entitled “Referenced Publications.”
b. References to the National Fire Protection Association, Inc., Publication 1975, Station Uniform.
c. Provisions of the National Fire Protection Association, Inc., Publication 1001, not adopted under rule 69A-37.
d. Any reference to an authority having jurisdiction in the National Fire Protection Association, Inc., Publication 1403, defined as the organization, office, or individual responsible for approving equipment, materials, installations, and procedures.
3. A 40-hour training program for live fire training instructors, including:
a. Live fire instructional techniques.
b. Training safety in acquired or permanent facilities or props.
c. Personnel safety.
d. Exterior props, including, but not limited to, liquid petroleum gas, other liquid fuels, and similar props.
(c) Each live fire training instructor is required to be a state certified fire safety instructor. All live fire training must be conducted by a certified live fire training instructor.
(d) This subsection does not apply to wildland or prescribed live fire training exercises sanctioned by the Florida Forest Service of the Department of Agriculture and Consumer Services or the National Wildfire Coordinating Group.
(7) The department shall:
(a) Investigate and prescribe by rule what safety devices, safeguards, or other means of protection must be adopted for the prevention of accidents and injuries in every firefighter employee place of employment or at any fire scene; determine what suitable devices, safeguards, or other means of protection for the prevention of occupational diseases must be adopted or followed in any or all such firefighter places of employment or at any emergency fire scene; and adopt reasonable rules for the prevention of accidents, the safety, protection, and security of firefighter employees engaged in interior firefighting, and the prevention of occupational diseases.
(b) Ascertain, fix, and order such reasonable standards and rules for the construction, repair, and maintenance of firefighter employee places of employment so as to render them safe. Such rules and standards shall be adopted in accordance with chapter 120.
(c) Adopt rules prescribing recordkeeping responsibilities for firefighter employers, which may include maintaining a log and summary of occupational injuries, diseases, and illnesses, for producing on request a notice of injury and firefighter employee accident investigation records, and prescribing a retention schedule for such records.
History.s. 15, ch. 2002-404; s. 4, ch. 2005-117; s. 76, ch. 2012-7; s. 79, ch. 2013-183; s. 35, ch. 2016-165; s. 2, ch. 2018-18.
Note.Former s. 633.821.
633.512 Compliance.Failure of a firefighter employer or an insurer to comply with this part, or with any rules adopted under this part, constitutes grounds for the department to seek remedies, including injunctive relief, by making appropriate filings with the circuit court.
History.s. 15, ch. 2002-404; s. 80, ch. 2013-183; s. 36, ch. 2016-165.
Note.Former s. 633.817.
633.516 Studies of occupational diseases of firefighters or persons in other fire-related fields.The division may contract for studies, subject to the availability of funding, of occupational diseases of firefighters or persons in other fire-related fields and the ways and means for the control and prevention of such occupational diseases. When such a study or another study that is wholly or partly funded under an agreement, including a contract or grant, with the department tracks a disease of an individual firefighter or a person in another fire-related field, the division may, with associated security measures, release the confidential information, including a social security number, of that individual to a party who has entered into an agreement with the department.
History.s. 15, ch. 2002-404; s. 81, ch. 2013-183; s. 32, ch. 2017-175.
Note.Former s. 633.805.
633.518 Studies, investigations, inspections, or inquiries by the division; refusal to admit; penalty.
(1) The department shall make studies, investigations, inspections, or inquiries with respect to compliance with this part or any rules authorized under this part and the causes of firefighter employee injuries, illnesses, safety-based complaints, or Line of Duty Deaths (LODD) as defined in rule in firefighter employee places of employment and shall make such recommendations to the Legislature and firefighter employers and insurers as the department considers proper to prevent or reduce future occurrences. In making such studies, investigations, inspections, or inquiries, the department may cooperate with any agency of the United States charged with the duty of enforcing any law securing safety against injury in any place of firefighter employment covered by this part or any agency or department of the state engaged in enforcing any law to ensure safety for firefighter employees.
(2) The division by rule may adopt procedures for conducting investigations, inspections, or inquiries of firefighter employers under this part.
(3) The division and authorized representatives of the division may enter and inspect any firefighter employee’s place of employment at any reasonable time for the purpose of investigating compliance with this part and conducting inspections for the proper enforcement of this part. A firefighter employer who refuses to admit any member of the division or authorized representative of the division to any place of employment or to allow investigation and inspection pursuant to this section commits a misdemeanor of the second degree, punishable as provided in s. 775.082 or s. 775.083.
History.s. 15, ch. 2002-404; s. 82, ch. 2013-183; s. 37, ch. 2016-165.
Note.Former s. 633.806.
633.520 Safety; firefighter employer responsibilities.
(1) Each firefighter employer shall furnish and use safety devices and safeguards, adopt and use methods and processes reasonably adequate to render such an employment and place of employment safe, and do every other thing reasonably necessary to protect the lives, health, and safety of such firefighter employees. As used in this section, the terms “safe” and “safety,” as applied to any employment or place of employment, mean such freedom from danger as is reasonably necessary for the protection of the lives, health, and safety of firefighter employees, including conditions and methods of sanitation and hygiene. Safety devices and safeguards required to be furnished by the firefighter employer by this section or by the division under authority of this section do not include personal apparel and protective devices that replace personal apparel normally worn by firefighter employees during regular working hours.
(2) The division shall adopt rules to establish employers’ cancer prevention best practices related to personal protective equipment, decontamination, fire suppression equipment, and fire stations.
History.s. 15, ch. 2002-404; s. 83, ch. 2013-183; s. 32, ch. 2019-140.
Note.Former s. 633.807.
633.522 Firefighter employers; high frequency of work-related injuries; corrective plans; workplace safety committees and coordinators; failure to implement a safety and health program; cancellation.
(1) The division shall develop a means to identify individual firefighter employers with a high frequency of firefighter employee work-related injuries. The division shall conduct safety inspections of those firefighter employers so identified to ensure compliance with this part or the division’s rules and make recommendations based upon current safety and health practices and to assist such firefighter employers in reducing the number of work-related injuries. The division may not assess penalties as a result of such inspections. Copies of any report made as the result of such an inspection shall be provided to the firefighter employer and its insurer. Firefighter employers shall submit a plan for the correction of any noncompliance issues to the division for approval in accordance with division rule. The division shall promptly review the plan submitted and approve or disapprove the plan within 60 days, or such plan shall be deemed approved. Upon approval by the division, the plan shall be implemented by the firefighter employer. If the plan is not submitted, does not provide corrective actions for all deficiencies, is not complete, or is not implemented, the fire service provider shall be subject to s. 633.526.
(2) In order to promote health and safety in firefighter employee places of employment in this state:
(a) Each firefighter employer of 20 or more firefighter employees shall establish and administer a workplace safety committee in accordance with rules adopted under this section.
(b) Each firefighter employer of fewer than 20 firefighter employees with a high frequency or high severity of work-related injuries, as identified by the division, shall establish and administer a workplace safety committee or designate a workplace safety coordinator who shall establish and administer workplace safety activities in accordance with rules adopted under this section.
(3) The division shall adopt rules:
(a) Prescribing the membership of the workplace safety committees so as to ensure an equal number of firefighter employee representatives who are volunteers or are elected by their peers and firefighter employer representatives, and specifying the frequency of meetings.
(b) Requiring firefighter employers to make adequate records of each meeting and to file and to maintain the records subject to inspection by the division.
(c) Prescribing the duties and functions of the workplace safety committee and workplace safety coordinator which include, but are not limited to:
1. Establishing procedures for workplace safety inspections by the committee.
2. Establishing procedures for investigating all workplace accidents, safety-related incidents, illnesses, and deaths.
3. Evaluating accident prevention and illness prevention programs.
4. Prescribing guidelines for the training of safety committee members.
(4) The composition, selection, and function of workplace safety committees shall be a mandatory topic of negotiations with any certified collective bargaining agent for firefighter employers that operate under a collective bargaining agreement. Firefighter employers that operate under a collective bargaining agreement that contains provisions governing the formation and operation of workplace safety committees that meet or exceed the minimum requirements contained in this section, or firefighter employers who otherwise have existing workplace safety committees that meet or exceed the minimum requirements established by this section, are in compliance with this section.
(5) Firefighter employees shall be compensated their regular hourly wage while engaged in workplace safety committee or workplace safety coordinator training, meetings, or other duties prescribed under this section.
(6) If a firefighter employer fails to implement a corrective plan, the insurer or self-insurer’s fund that is providing coverage for the firefighter employer may cancel the contract for insurance with the firefighter employer. In the alternative, the insurer or fund may terminate any discount or deviation granted to the firefighter employer for the remainder of the term of the policy. If the contract is canceled or the discount or deviation is terminated, the insurer must make such reports as are required by law.
History.s. 15, ch. 2002-404; s. 84, ch. 2013-183.
Note.Former s. 633.809.
633.526 Firefighter employer penalties.If any firefighter employer violates or fails or refuses to comply with this part, or with any rule adopted by the division under such sections in accordance with chapter 120 for the prevention of injuries, accidents, or occupational diseases or with any lawful order of the division in connection with this part, or fails or refuses to furnish or adopt any safety device, safeguard, or other means of protection prescribed by division rule under this part for the prevention of accidents or occupational diseases, the division may:
(1) Issue an administrative cease and desist order, enforceable in the circuit court in the jurisdiction where the violation is occurring or has occurred.
(2) Assess an administrative fine against a firefighter employer of not less than $100 or more than $1,000 for each violation and each day a violation is committed.
(3) Assess against the firefighter employer a civil penalty of not less than $100 nor more than $5,000 for each day the violation, omission, failure, or refusal continues after the firefighter employer has been given written notice of such violation, omission, failure, or refusal. The total penalty for each violation shall not exceed $50,000. The division shall adopt rules requiring penalties commensurate with the frequency or severity of safety violations. Hearings requested under this section shall be conducted in Tallahassee. All penalties assessed and collected under this section shall be deposited in the Insurance Regulatory Trust Fund.
History.s. 15, ch. 2002-404; s. 1413, ch. 2003-261; s. 85, ch. 2013-183.
Note.Former s. 633.811.
633.528 Division cooperation with Federal Government; exemption from requirements for private firefighter employers.
(1) The division shall cooperate with the Federal Government so that duplicate inspections will be avoided while at the same time ensuring safe firefighter employee places of employment for the citizens of this state.
(2) A private firefighter employer is not subject to the requirements set forth in part IV and this part if the private firefighter employer meets the requirements of this part and:
(a) The private firefighter employer is subject to the federal regulations in 29 C.F.R. ss. 1910 and 1926.
(b) The private firefighter employer has adopted and implemented a written safety program that conforms to the requirements of 29 C.F.R. ss. 1910 and 1926.
(c) The private firefighter employer provides the division with a written statement that certifies compliance with this subsection.
(3) The division may enter at any reasonable time any place of private firefighter employment for the purpose of verifying the accuracy of the written certification. If the division determines that the private firefighter employer has not complied with the requirements of subsection (2), the private firefighter employer shall be subject to the rules of the division until the private firefighter employer complies with subsection (2), which must be verified by a reinspection by the division.
(4) This section shall not restrict the division’s performance of any duties pursuant to a written contract between the division and the federal Occupational Safety and Health Administration.
History.s. 15, ch. 2002-404; s. 86, ch. 2013-183.
Note.Former s. 633.812.
633.532 Firefighter employee rights and responsibilities.
(1) Each firefighter employee of a firefighter employer covered under this part shall comply with rules adopted by the division and with reasonable workplace safety and health standards, rules, policies, procedures, and work practices established by the firefighter employer and the workplace safety committee. A firefighter employee who knowingly fails to comply with this subsection may be disciplined or discharged by the firefighter employer.
(2) A firefighter employer may not discharge, threaten to discharge, cause to be discharged, intimidate, coerce, otherwise discipline, or in any manner discriminate against a firefighter employee for any of the following reasons:
(a) The firefighter employee has testified or is about to testify, on her or his own behalf or on behalf of others, in any proceeding instituted under this part;
(b) The firefighter employee has exercised any other right given under this part; or
(c) The firefighter employee is engaged in activities relating to the workplace safety committee.
(3) Pay, a position, seniority, or any other benefit may not be lost for exercising any right under, or for seeking compliance with any requirement of, this part.
History.s. 15, ch. 2002-404; s. 87, ch. 2013-183.
Note.Former s. 633.816.
633.5341 False, fictitious, or fraudulent acts, statements, and representations prohibited; penalty; statute of limitations.
(1) A firefighter employer who knowingly and willfully falsifies or conceals a material fact, who makes a false, fictitious, or fraudulent statement or representation, or who makes or uses any false document knowing the document to contain any false, fictitious, or fraudulent entry or statement to an insurer of workers’ compensation insurance under this part commits a misdemeanor of the second degree, punishable as provided in s. 775.082 or s. 775.083.
(2) A person may not, in any matter within the jurisdiction of the division, knowingly and willfully falsify or conceal a material fact; make any false, fictitious, or fraudulent statement or representation; or make or use any false document, knowing the same to contain any false, fictitious, or fraudulent statement or entry. A person who violates this section commits a misdemeanor of the second degree, punishable as provided in s. 775.082 or s. 775.083. The statute of limitations for prosecution of an act committed in violation of this section is 5 years after the date the act was committed or, if not discovered within 30 days after the act was committed, 5 years after the date the act was discovered.
History.s. 15, ch. 2002-404; s. 88, ch. 2013-183.
Note.Former s. 633.818.
633.536 Expenses of administration.The amounts that are needed to administer this part shall be disbursed from the Insurance Regulatory Trust Fund.
History.s. 15, ch. 2002-404; s. 1414, ch. 2003-261; s. 89, ch. 2013-183.
Note.Former s. 633.814.